Tablas ingeniería eléctrica

  1. 1. TABLA No. 5 DIMENSIONES DE LOS CONDUCTORES ELECTRICOS DESNUDOS CALIBRE SECCIÓN DIÁMETROAWG o MCM CIRCULAR MIL Mm2 PULGADAS MILIMETROS 20 1 022 0.518 0.032 0.812 18 1 824 0.823 0.040 1.024 16 2 583 1.309 0.051 1.291 14 4 107 2.080 0.064 1.628 12 6 530 3.310 0.081 2.053 10 10 380 5.260 0.102 2.588 8 16 510 8.370 0.129 3.264 6 26 250 13.300 0.162 4.115 4 41 740 21.150 0.204 5.189 2 66 370 33.630 0.258 6.543 1/0 105 400 53.480 0.325 8.252 2/0 133 100 67.420 0.365 9.266 3/0 167 800 85.030 0.410 10.403 4/0 211 600 107.230 0.460 11.684 250 250 000 126.640 0.575 14.605 300 300 000 152.000 0.630 16.000 350 350 000 177.350 0.681 17.300 400 400 000 202.710 0.728 18.490 500 500 000 253.350 0.814 20.680 600 600 000 304.000 0.893 22.680 700 700 000 354.710 0.964 24.690 750 750 000 379.840 0.998 25.350 800 800 000 405.160 1.031 26.190 900 900 000 455.810 1.093 27.760 1000 1 000 000 506.450 1.152 29.260 1250 1 250 000 633.060 1.289 32.740 1500 1 500 000 759.680 1.412 35.870 1750 1 750 000 886.290 1.526 38.760 2000 2 000 000 1 012.900 1.631 41.420 TABLA No. 6
  2. 2. CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE, AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30º C. CALIBRE TIPOS T, TW, UF (60º C) THW, THWN, RHW, XHW (75º C) AWG o MCM TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE 14 15 20 15 20 12 20 25 20 25 10 30 30 30 40 8 40 60 50 70 6 55 80 65 95 4 70 105 85 125 2 95 140 115 170 1/0 125 195 150 230 2/0 145 225 175 265 3/0 165 260 200 310 4/0 195 300 230 360 250 215 340 255 405 300 240 375 285 445 350 260 420 310 505 400 280 455 335 545 500 320 515 380 620 600 355 575 420 690 700 385 630 460 755 750 400 655 475 785 800 410 680 490 815 900 435 730 520 870 1000 455 780 545 935 FACTORES DE CORRECCIÓN PARA TEMPERATURAS AMBIENTES MAYORES DE 30º C 31 A 35º C 0.91 0.91 0.94 0.94 36 A 40º C 0.82 0.82 0.88 0.88 41 A 45º C 0.71 0.71 0.82 0.82 46 A 50º C 0.58 0.58 0.75 0.75 51 A 55º C 0.41 0.41 0.67 0.67 56 A 60º C 0.58 0.58 61 A 79º C 0.41 0.41NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifrasdadas, de 7 a 9 conductores, la ampacidad se reduce al 70% ; al 50% si hay de 10 a 20conductores y, al 45% si hay de 21 a 30 conductores en un tubo. En un sistema balanceado,el neutro no cuenta como conductor para los efectos de esta nota. TABLA No. 7
  3. 3. CAPACIDAD DE CORRIENTE EN AMPERES PARA CONDUCTORES DE COBRE, AISLADOS Y, PARA UNA TEMPERATURA AMBIENTE DE 30° C CALIBRE THHW, RHH, THHN, XHHW (90º C) VINICON, AVA, AVL (110º C) AWG o MCM TUBO o DUCTO EN AIRE TUBO o DUCTO EN AIRE 14 25 35 30 40 12 30 40 35 50 10 40 55 45 65 8 55 80 60 85 6 75 105 80 120 4 95 140 105 160 2 130 190 135 210 1/0 170 260 190 285 2/0 195 300 215 330 3/0 225 350 245 380 4/0 260 405 275 445 250 290 455 315 495 300 320 505 345 555 350 350 570 390 610 400 380 615 420 665 500 430 700 470 765 600 475 780 525 855 700 500 850 560 940 750 535 885 580 980 800 550 900 600 1 020 1000 615 1 055 680 1 165 FACTORES DE CORRECCION PARA TEMPERATURAS AMBIENTES MAYORES DE 30º C 31 A 35º C 0.96 0.96 0.97 0.97 36 A 40º C 0.91 0.91 0.94 0.94 41 A 45º C 0.87 0.87 0.90 0.90 46 A 50º C 0.82 0.82 0.87 0.87 51 A 55º C 0.76 0.76 0.83 0.83 56 A 60º C 0.71 0.71 0.79 0.79NOTAS: Para 4 a 6 conductores en un tubo, la ampacidad se reduce al 80% de las cifrasdadas. De 7 a 9 conductores, la ampacidad se reduce al 70% ; de 10 a 20 al 50% y de 21 a30 al 45%. En un sistema balanceado, el neutro no cuenta como conductor para los efectosde esta nota.
  4. 4. TABLA No. 8NUMERO MAXIMO DE CONDUCTORES TIPO T, TW, THW, THHW, XHHW QUE PUEDEN INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE. CALIBRE DIAMETRO NOMINAL DEL TUBO EN MILÍMETROSCONDUCTOR 13 19 25 32 38 51 63 76 89 102 127 152 14 9 15 25 44 60 99 142 12 7 12 19 35 47 78 111 171 10 5 9 15 26 36 60 85 111 176 8 2 4 7 12 17 28 40 62 84 108 6 1 2 4 7 10 16 23 36 48 62 97 141 4 1 1 3 5 7 12 17 27 36 47 73 106 2 1 1 2 4 5 9 13 20 27 34 54 78 1/0 - 1 1 2 3 5 8 12 16 21 33 49 2/0 - 1 1 1 3 5 7 10 14 18 29 41 3/0 - 1 1 1 2 4 6 9 12 15 24 35 4/0 - - 1 1 1 3 5 7 10 13 20 29 250 1 1 1 2 4 6 8 10 16 23 300 1 1 1 2 3 5 7 9 14 20 350 1 1 1 3 4 6 8 12 18 400 1 1 1 2 4 5 7 11 16 500 1 1 1 1 3 4 6 9 14 600 1 1 1 3 3 5 7 11 750 1 1 1 2 3 4 6 9 800 1 1 1 1 3 4 6 8 900 1 1 1 3 3 5 8 1000 1 1 1 2 3 5 7
  5. 5. TABLA No. 9 NUMERO MAXIMO DE CONDUCTORES TIPO THWN Y THHN QUE PUEDEN INSTALARSE EN UN TUBO CONDUIT DE ACUERDO CON LOS FACTORES DE RELLENO AUTORIZADOS POR LAS NORMAS OFICIALES NOM-001-SEDE. CALIBRE DIÁMETRO NOMINAL DEL TUBO EN MILÍMETROSCONDUCTOR 13 19 25 32 38 51 63 76 89 102 127 152 14 13 24 39 69 94 154 12 10 18 29 51 70 114 164 10 6 11 18 32 44 73 104 160 8 3 5 9 16 22 36 51 79 106 136 6 1 4 6 11 15 26 37 57 76 98 154 4 1 2 4 7 9 16 22 35 47 60 94 137 2 1 1 3 5 7 11 16 25 33 43 67 97 1/0 1 1 3 4 7 10 15 21 27 42 61 2/0 1 1 2 3 6 8 13 17 22 35 51 3/0 1 1 1 3 5 7 11 14 18 29 42 4/0 1 1 1 2 4 6 9 12 15 24 35 250 1 1 1 3 4 7 10 12 20 28 300 1 1 1 3 4 6 8 11 17 24 350 1 1 2 3 5 7 9 15 21 400 1 1 1 3 5 6 8 13 19 500 1 1 1 2 4 5 7 11 16 750 1 1 1 2 3 4 7 11
  6. 6. TABLA No. 10CANTIDAD DE CONDUCTORES QUE PUEDEN ALOJARSE EN UN DUCTO DE LAMINA SECCIÓN CONDUCTOR DUCTOS DE LÁMINA CALIBRE CON AISLAMIENTO mm2 SECCION TRANSVER. mm2CONDUCTOR THWN, TW, THW MEDIDAS TOTAL 20% TOTALAWG o MCM THHN XHW EN mm 14 5.80 8.30 60 x 60 3 600 720 12 7.90 10.64 100 x 100 10 000 2 000 10 12.30 13.99 150 x 150 22 500 4 500 8 21.10 26.70 200 x 200 40 000 8 000 6 34.20 49.29 4 55.15 65.61 2 77.00 89.42 PARA USAR ESTA TABLA: 1.- Determinar cantidad, tipo y calibre de 1/0 123.50 143.99 conductores a canalizar. 2/0 147.60 169.72 2.- Sumar sus secciones transversales. 3.- Escoger el ducto adecuado, utilizando 3/0 176.70 201.06 la columna del 20% de su sección - - 4/0 211.20 239.98 transversal. 250 261.30 298.65 300 302.60 343.07 350 346.19 386.88 400 384.30 430.05 500 463.00 514.72 600 572.27 628.70 750 673.91 735.04 1000 813.92 934.35
  7. 7. TABLA No. 11 RESISTENCIA DE CONDUCTORES CON CORRIENTE DIRECTA, FACTORES DECORRECCION AL OPERARLOS CON CORRIENTE ALTERNA POR EL EFECTO PIEL Y, REACTANCIA AL NEUTRO PARA UNA FRECUENCIA DE 60 HERTZ. CALIBRE RESISTENCIA FACTOR DE CORRECCIÓN REACTANCIA ENCONDUCTOR C. DIRECTA POR EFECTO PIEL OHMS / 1000 PIESAWG o MCM OHMS / 1000’ (1) (2) MÍNIMA MÁXIMA 14 3.0000 1.000 1.000 12 1.8700 1.000 1.000 10 1.1800 1.000 1.000 8 0.7400 1.000 1.000 0.041 0.045 6 0.4650 1.000 1.000 0.040 0.045 4 0.2920 1.000 1.000 0.037 0.050 2 0.1850 1.000 1.010 0.035 0.048 1/0 0.1600 1.000 1.020 0.034 0.048 2/0 0.0920 1.000 1.030 0.032 0.044 3/0 0.0730 1.000 1.040 0.031 0.044 4/0 0.0580 1.000 1.050 0.030 0.045 250 0.0490 1.005 1.060 0.030 0.044 300 0.0408 1.006 1.070 0.029 0.045 350 0.0350 1.009 1.080 0.029 0.044 400 0.0306 1.011 1.100 0.029 0.043 500 0.0245 1.018 1.130 0.028 0.038 600 0.0204 1.025 1.160 0.028 0.038 750 0.0163 1.039 1.210 0.028 0.035 1000 0.0123 1.067 1.300 0.028 0.038 1250 0.0098 1.102 1.410 0.028 0.038 1500 0.0082 1.142 1.530 0.028 0.038 1750 0.0070 1.185 1.659 0.027 0.037 2000 0.0061 1.233 1.800 0.027 0.038NOTAS: ( 1 ) Conductor en aire o en tubo no magnético. ( 2 ) Conductor en tubo de acero.♦ Los valores de la reactancia mínima se aplican para conductores juntos dentro de un tubo o de un ducto.♦ Los valores de la reactancia máxima se aplican para conductores separados en instalaciones aéreas o en ménsulas en galerías de conductores.♦ Para conductores en ductos o tubos de acero o, con armadura de acero, la reactancia aumenta en un 25%. Por lo tanto, multiplíquense los valores por 1.25.
  8. 8. TABLA No. 12 CAPACIDADES Y DIMENSIONES DE CARTUCHOS FUSIBLESCAPACIDAD EN 250 VOLTS 600 VOLTS AMPERES LARGO (mm) DIÁMETRO(mm) LARGO (mm) DIÁMETRO(mm) FUSIBLES TIPO TAPÓN10, 15, 20, 25 Y 30 --- --- --- --- FUSIBLES TIPO CASQUILLO 3, 5, 6, 10, 15, 20, 25 Y 30 53 14 125 1935, 40, 45, 50 Y 60 76 21 139 26 FUSIBLES TIPO NAVAJA 75, 90, 100 151 30 200 35 125, 150, 175, 200 181 42 244 47 225, 250, 300 219 56 295 65 500, 600 263 67 340 76
  9. 9. TABLA No. 13 CAPACIDAD Y DIMENSIONES DE LOS INTERRUPTORES TERMOMAGNETICOS CAPACIDAD No. DIMENSIONES ENMARCO CAPACIDAD EN INTERRUPTIVA DE CENTIMETROS AMPERES 240V 480V 600V POLOS ALTO ANCHO FONDO 15, 20, 30, 40, 50, 1 7.5 2.5 7.3 QL 70, 100 10000 --- --- 2 7.5 5.0 7.3 3 7.5 7.5 7.3 15, 20, 30, 40, 50, 1 15.3 3.5 8.6 FA 70, 100 10000 --- --- 2 15.3 7.0 8.6 3 15.3 10.5 8.6 15, 20, 30, 40, 50, FB 70, 100, 125, 150 18000 14000 14000 2 15.3 7.0 8.6 3 15.3 10.5 8.6 15, 20, 30, 40, 50, HFB 70, 100, 125, 150 65000 25000 18000 2 15.3 7.0 8.6 3 15.3 10.5 8.6 LB 125, 150, 175, 200, 225 25000 22000 22000 3 25.7 14.0 10.3 LB 250, 300, 350, 400 42000 30000 22000 3 25.7 14.0 10.3 125, 150, 175, HLB 200, 225, 250, 65000 35000 25000 3 25.7 14.0 10.3 300, 350, 400 LA 500, 600 42000 30000 22000 3 27.6 21.0 10.3 NB 700, 800, 1000, 1200 42000 30000 22000 3 41.2 21.0 14.0 PB 1400, 1600, 1800 2000, 2500, 3000 125000 100000 100000 3 56.2 30.5 22.9 NC (+) 800, 900, 1000, 1200 42000 30000 22000 3 1000, 1200, 1400 PC (+) 1600, 1800, 2000 125000 100000 100000 3 2500, 3000 MPC 3, 7, 15, 30, 50, 100, 150 25000 22000 22000 3 15.3 10.5 8.6NOTAS: (+) Interruptores con protección electrónica. MPC: Interruptor magnético instantáneo.
  10. 10. TABLA No. 14 CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE DIRECTAPOTENCIA EN VOLTAJE HP 115 VOLTS 230 VOLTS 550 VOLTS 0.50 4.6 2.3 -- 0.75 6.6 3.3 1.4 1.00 8.6 4.3 1.8 1.50 12.6 6.3 2.5 2.00 16.4 8.2 3.4 3.00 24.0 12.0 5.0 5.0 40.0 20.0 8.3 7.5 58.0 29.0 12.0 10.0 76.0 38.0 16.0 15.0 112.0 56.0 23.0 20.0 148.0 74.0 31.0 25.0 184.0 92.0 38.0 30.0 220.0 110.0 46.0 40.0 292.0 146.0 61.0 50.0 360.0 180.0 75.0 60.0 430.0 215.0 90.0 75.0 536.0 268.0 111.0 100.0 --- 355.0 148.0 125.0 --- 443.0 184.0 150.0 --- 534.0 220.0 200.0 --- 712.0 295.0
  11. 11. TABLA No. 15 CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA MONOFASICOSPOTENCIA EN VOLTAJES HP 115 VOLTS 230 VOLTS 440 VOLTS 1/6 3.2 1.6 --- ¼ 4.6 2.3 --- ½ 7.4 3.7 --- ¾ 10.2 5.1 --- 1.0 13.0 6.5 --- 1.5 18.4 9.2 --- 2.0 24.0 12.0 --- 3.0 34.0 17.0 --- 5.0 56.0 28.0 --- 7.5 80.0 40.0 21.0 10.0 100.0 50.0 26.0
  12. 12. TABLA No. 16CORRIENTE A PLENA CARGA DE MOTORES DE CORRIENTE ALTERNA TRIFASICOSPOTENCIA MOTORES DE INDUCCIÓN MOTORES SÍNCRONOS HP 220 V 440 V 550 V 2400 V 220 V 440 V 550 V 2300 V 1/2 2.0 1.0 0.8 --- --- --- --- --- 3/4 2.8 1.4 1.1 --- --- --- --- --- 1.0 3.5 1.8 1.4 --- --- --- --- --- 1.5 5.0 2.5 2.0 --- --- --- --- --- 2.0 6.5 3.3 2.6 --- --- --- --- --- 3.0 9.0 4.5 4.0 --- --- --- --- --- 5.0 15.0 7.5 6.0 --- --- --- --- --- 7.5 22.0 11.0 9.0 --- --- --- --- --- 10.0 27.0 14.0 11.0 --- --- --- --- --- 15.0 40.0 20.0 16.0 --- --- --- --- --- 20.0 52.0 26.0 21.0 --- --- --- --- --- 25.0 64.0 32.0 26.0 7.0 54.0 27.0 22.0 5.4 30.0 78.0 39.0 31.0 8.5 65.0 33.0 26.0 6.5 40.0 104.0 52.0 41.0 10.5 86.0 43.0 35.0 8.0 50.0 125.0 63.0 50.0 13.0 108.0 54.0 44.0 10.0 60.0 150.0 75.0 60.0 16.9 128.0 64.0 51.0 12.0 75.0 185.0 93.0 74.0 19.0 161.0 81.0 65.0 15.0 100.0 246.0 123.0 98.0 25.0 211.0 106.0 85.0 20.0 125.0 310.0 155.0 124.0 31.0 264.0 132.0 106.0 25.0 150.0 360.0 180.0 144.0 37.0 --- 158.0 127.0 30.0 200.0 480.0 240.0 192.0 48.0 --- 210.0 168.0 40.0 250.0 --- 300.0 300.0 --- 345.0 350.0 --- 406.0 400.0 --- 475.0
  13. 13. TABLA No. 17 CAPACIDAD O AJUSTE MAXIMO DEL DISPOSITIVO DE PROTECCION PARA LOS CIRCUITOS DERIVADOS DE LOS MOTORES POR CIENTO DE LA CORRIENTE A PLENA CARGA TIPO DE MOTOR FUSIBLES INT. TERMOMAGNÉTICO NORMAL ACC. RET. INSTANT. TIEMPO INV.Todos los motores monofásicos otrifásicos, jaula de ardilla, conarranque a tensión plena o conresistencias o reactancias:LETRA DE CÓDIGO “A” 150 150 700 150LETRA DE CÓDIGO “B a E” 250 175 700 200LETRA DE CÓDIGO “F a V” 300 175 700 250SIN LETRA CÓDIGO 300 175 700 250Todos los motores jaula de ardilla ysíncronos con arranque porautotransformador:LETRA DE CÓDIGO “A” 150 150 700 150LETRA DE CÓDIGO “B a E” 200 175 700 200LETRA DE CÓDIGO “F a V” 250 175 700 200SIN LETRA DE CÓDIGO 250 175 700 200Motores jaula de ardilla de altareactancia y no mayores de 30 A. 250 175 700 250Motores jaula de ardilla de altareactancia y mayores de 30 A. 200 175 700 200Motores de rotor devanado 150 150 700 150
  14. 14. TABLA No. 18RELACION QUE MUESTRA ALGUNAS DE LAS CAPACIDADES DE LOS ELEMENTOS TERMICOS UTILIZADOS PARA LA PROTECCION CONTRA SOBRECARGA DE LOS MOTORESCAPACIDAD EN AMPERES CAPACIDAD EN AMPERES CAPACIDAD EN AMPERES TAMAÑOS 0 Y 1 TAMAÑOS 0 Y 1 TAMAÑOS 2 A 8 0.167 - 0.187 5.040 - 5.590 91.80 - 105.0 0.188 - 0.210 5.600 - 6.250 106.0 - 121.0 0.211 - 0.237 6.260 - 6.920 122.0 - 135.0 0.238 - 0.266 6.930 - 7.750 126.0 - 139.0 0.267 - 0.298 7.760 - 8.630 140.0 - 157.0 0.299 - 0.334 8.640 - 9.590 158.0 - 175.0 0.335 - 0.376 9.600 - 10.60 176.0 - 196.0 0.377 - 0.422 10.70 - 11.90 197.0 - 218.0 0.423 - 0.474 12.00 - 13.30 219.0 - 243.0 0.475 - 0.532 13.40 - 14.70 244.0 - 270.0 0.533 - 0.598 14.80 - 16.60 264.0 - 295.0 0.599 - 0.672 16.70 - 18.80 296.0 - 330.0 0.673 - 0.757 18.90 - 21.20 331.0 - 369.0 0.758 - 0.855 21.30 - 23.90 370.0 - 410.0 0.856 - 0.959 24.00 - 27.00 411.0 - 458.0 0.969 - 1.070 459.0 - 512.0 1.080 - 1.210 TAMAÑOS 2 A 8 513.0 - 574.0 1.220 - 1.350 550.0 - 607.0 1.360 - 1.520 24.60 - 27.90 608.0 - 685.0 1.530 - 1.700 28.00 - 32.00 686.0 - 763.0 1.710 - 1.900 32.10 - 36.60 764.0 - 855.0 1.910 - 2.100 36.70 - 41.80 828.0 - 924.0 2.110 - 2.330 41.90 - 45.00 925.0 - 1 027 2.340 - 2.620 42.90 - 48.50 1 028 - 1 147 2.630 - 2.930 48.60 - 55.10 1 148 - 1 285 2.940 - 3.270 55.20 - 62.30 3.280 - 3.640 62.40 - 69.50 3.650 - 4.060 69.60 - 79.10 4.070 - 4.550 79.20 - 90.00 4.560 - 5.030 80.00 - 91.70
  15. 15. TABLA 19POTENCIA MAXIMA DEL BANCO DE CAPACITORES PARA COMPENSAR FACTORES DE POTENCIA DE MOTORES TRIFASICOS DE INDUCCION, LIMITANDO EL FENOMENO DE AUTOINDUCCION. POTENCIA VELOCIDAD DE SINCRONISMO DEL MOTOR EN R. P. M.MOTOR EN HP 3 600 1 800 1 200 900 720 600 10 2.5 4.0 4.0 5.0 5.0 6.5 15 2.5 5.0 5.0 7.5 7.5 10.0 20 5.0 5.0 5.0 7.5 10.0 12.5 25 5.0 7.5 7.5 10.0 10.0 15.0 30 7.5 10.0 10.0 10.0 12.5 15.0 40 10.0 10.0 10.0 12.5 15.0 17.5 50 12.5 12.5 12.5 15.0 20.0 22.5 60 15.0 15.0 15.0 17.5 22.5 25.0 75 17.5 17.5 17.5 20.0 27.5 30.0 100 22.5 22.5 22.5 25.0 35.0 37.5 125 25.0 27.5 27.5 30.0 40.0 47.5 150 32.5 32.5 35.0 37.5 47.5 55.0 200 42.5 42.5 42.5 45.0 60.0 67.5
  16. 16. TABLA No. 20MULTIPLICADORES DE KW PARA DETERMINAR LOS KVAR EN CAPACITORES, REQUERIDOS PARA CORREGIR EL FACTOR DE POTENCIA F. P. FACTOR DE POTENCIA CORREGIDOORIGINA 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.98 1.00 L 0.56 0.996 1.024 1.054 1.085 1.117 1.151 1.188 1.277 1.480 0.58 0.921 0.949 0.979 1.010 1.042 1.076 1.113 1.202 1.405 0.60 0.849 0.877 0.907 0.938 0.970 1.004 1.041 1.130 1.333 0.62 0.782 0.810 0.840 0.871 0.903 0.937 0.974 1.063 1.266 0.64 0.717 0.745 0.775 0.806 0.838 0.872 0.909 0.998 1.201 0.66 0.654 0.682 0.712 0.743 0.775 0.809 0.846 0.935 1.138 0.68 0.594 0.622 0.652 0.683 0.715 0.749 0.786 0.875 1.078 0.70 0.536 0.564 0.594 0.625 0.657 0.691 0.728 0.817 1.020 0.72 0.480 0.508 0.538 0.569 0.601 0.635 0.672 0.761 0.964 0.74 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.706 0.909 0.76 0.371 0.399 0.429 0.460 0.492 0.526 0.563 0.652 0.855 0.78 0.318 0.346 0.376 0.407 0.439 0.473 0.510 0.599 0.802 0.80 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.547 0.750 0.81 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.521 0.724 0.82 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.495 0.698 0.83 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.469 0.672 0.84 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.443 0.646 0.85 0.136 0.164 0.194 0.225 0.257 0.291 0.328 0.417 0.620 0.86 0.109 0.137 0.167 0.198 0.230 0.264 0.301 0.390 0.593 0.87 0.083 0.111 0.141 0.172 0.204 0.238 0.275 0.364 0.567 0.88 0.056 0.084 0.114 0.145 0.177 0.211 0.248 0.337 0.540 0.89 0.028 0.056 0.086 0.117 0.149 0.183 0.220 0.309 0.512 0.90 0.028 0.058 0.089 0.121 0.155 0.192 0.281 0.484 0.91 0.030 0.061 0.093 0.127 0.164 0.253 0.456 0.92 0.031 0.063 0.097 0.134 0.223 0.426 0.93 0.032 0.066 0.103 0.192 0.395 0.94 0.034 0.071 0.160 0.363 0.95 0.037 0.126 0.329 0.96 0.089 0.292 0.97 0.048 0.251 0.98 0.203 0.99 0.143
  17. 17. EJEMPLO:Se tiene una carga de 600 kilowatts con un factor de potencia de 0.80, que se desea corregira 0.92. Se entra a la columna de “factor de potencia original” con el dato de 0.80 y, en elmismo renglón , se busca la constante para corregir el factor de potencia a 0.92,encontrándose que es 0.324, el cual se multiplica por los 600 kilowatts de demanda. Setendrá así: 600 * 0.324 = 194.4siendo el resultado así obtenido, la capacidad del banco de capacitores en KVAR.
  18. 18. TABLA No. 21 FACTORES DE DEMANDA PROMEDIOTIPO DE SERVICIO F. DEMANDA TIPO DE SERVICIO F. DEMANDAAlumbrado público 1.00 Fábricas de cigarros 0.60Apartamentos 0.35 Fábricas de dulces 0.45Bancos 0.70 Talleres de fundición 0.70Bodegas 0.50 Fábricas de galletas 0.55Casinos 0.85 Fábricas de hielo 0.90Correos 0.30 Talleres de herrería 0.50Escuelas 0.70 Imprentas 0.60Garages 0.60 Fábricas de jabón 0.60Hospitales 0.40 Fáb. artículos de lámina 0.70Hoteles chicos 0.50 Talleres de niquelado 0.75Hoteles grandes 0.40 Madererías 0.65Iglesias 0.60 Talleres de marmolería 0.70Mercados 0.80 Talleres mecánicos 0.75Multifamiliares 0.25 Fábricas de muebles 0.65Oficinas 0.65 Fábricas de pan 0.55Restaurantes 0.65 Fábricas de papel 0.75Teatros 0.60 Periódicos 0.75Tiendas 0.65 Fábricas de pinturas 0.70Fábricas de acetileno 0.70 Industria química 0.50Industria automotriz 0.70 Refinerías 0.60Talleres de carpintería 0.65 Fábricas de refrescos 0.55Empacadoras de carne 0.80 Industria textil 0.65Fábricas de cartón 0.50 Fábricas de ropa 0.45Fábricas de cemento 0.65 Fábricas de zapatos 0.45
  19. 19. TABLA NO. 22TABLA 250-95 SECCIÓN TRANSVERSAL MÍNIMA DE LOS CONDUCTORES DE PUESTA A TIERRA PARA CANALIZACIONES Y EQUIPOS CAPACIDAD DEL DISPOSITIVO SECCIÓN TRANSVERSAL SECCIÓN TRANSVERSAL AUTOMÁTICO DE SOBRE COBRE ALUMINIO CORRIENTE ANTES DEL EQUIPO mm2 AWG mm2 AWG 15 2.082 14 3.307 12 20 3.307 12 5.260 10 30 5.260 10 8.367 8 40 5.260 10 8.367 8 60 5.260 10 8.367 8 100 8.367 8 13.300 6 200 13.300 6 21.150 4 300 21.150 4 33.620 2 400 27.670 3 42.410 1 500 33.620 2 53.480 1/0 600 42.410 1 67.430 2/0 800 53.480 1/0 85.010 3/0 1000 67.430 2/0 107.200 4/0

×