SED2 Drive Applications
Simple Applications INPUTS OUTPUTS ACTION 0-10 V On Fault Reset Relay 1 -> Fault Relay 2 -> Run
Standard I/O 0-10 V 2-10 V 0-20 mA 4-20 mA Programmable functions Form C contacts Programmable functions 30VDC, 5A 240VAC,...
Application -  Air Temperature Control , Cooling Digital Input Analog Input Digital Input <ul><li>Function Description </l...
Solution: PID Controller Direct Sensor Connection <ul><li>Ni 1000 Temperature Sensor </li></ul><ul><li>Drive Based PID w/ ...
Ni 1000 I/O SED2 Ni 1000 Analog input Digital input 1 Safety Input
Application - Water Pressure Control <ul><li>Function Description </li></ul><ul><li>Constant pressure (P) </li></ul><ul><l...
Solution :  Built-In Pump Cascading <ul><li>This function allows for control of up to two additional, cascaded pumps. With...
Pump Staging I/O SED2 2 x analog input 6 x digital input 2 x digital output 0-10 volt Pressure Transmitter 1 On Command 1 ...
Application – Temp. Control + Belt Monitoring <ul><li>Function Description </li></ul><ul><li>Exhaust fan  – </li></ul><ul>...
Solution: V-Belt Monitoring <ul><li>The SED2 ensures  reliable V-belt monitoring  without the expense of an external senso...
Application – Temp. Control + Duct Pressure Control <ul><li>Function Description </li></ul><ul><li>Exhaust fan =  Like air...
Solution: Duct Pressure Control <ul><li>0 – 10 Volt standard output signal </li></ul><ul><li>1% Accuracy over full scale <...
Static Pressure Control  I/O 2 x analog input 6 x digital input SED2 0-10 volt Pressure transmitter 1 On Command 1 Safety ...
Bundled Package The SED2 is equipped with TEC application 2722 Which includes 99 subpoints for monitoring and control (See...
Control Board
Control Terminals * Can also be configured as NI1000 inputs.  Digital Inputs Terminals Parameter Default  1 5 P0701=1 ON r...
Mounting & Installation Considerations <ul><li>Type of environment  </li></ul><ul><li>-  What is the location like?  Does ...
Enclosure Ratings - Drive & Drive W/Bypass <ul><li>IP 20 </li></ul><ul><ul><li>No NEMA equivalent, needs to be mounted in ...
Mounting & Installation Considerations <ul><li>Line Reactor Installation </li></ul><ul><li>Not recommended to reduce Harmo...
Mounting & Installation Considerations <ul><li>Load Reactor Installation </li></ul><ul><li>Long wire leads from drive to m...
Mounting & Installation Considerations <ul><li>Line and Load Reactor Installation </li></ul><ul><li>Always use Siemens Bui...
Siemens SED2 VFD Advantages <ul><li>Low harmonics design </li></ul><ul><li>Small enclosure size </li></ul><ul><li>Many sta...
Upcoming SlideShare
Loading in...5
×

2 Sed2 Drive Applications

490

Published on

2 - SED2 Drive Applications

0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total Views
490
On Slideshare
0
From Embeds
0
Number of Embeds
0
Actions
Shares
0
Downloads
0
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide

Transcript of "2 Sed2 Drive Applications"

  1. 1. SED2 Drive Applications
  2. 2. Simple Applications INPUTS OUTPUTS ACTION 0-10 V On Fault Reset Relay 1 -> Fault Relay 2 -> Run
  3. 3. Standard I/O 0-10 V 2-10 V 0-20 mA 4-20 mA Programmable functions Form C contacts Programmable functions 30VDC, 5A 240VAC, 2A 2 x analog outputs 2 x digital outputs RS-485 P1 N2 USS LonWorks (opt.) Modbus (opt.) 0-10 V 2-10 V 0-20 mA 4-20 mA Ni 1000 2 x analog inputs 6 x digital inputs 1 x motor PTC Insulated Programmable functions PNP or NPN (sink/source) SED2
  4. 4. Application - Air Temperature Control , Cooling Digital Input Analog Input Digital Input <ul><li>Function Description </li></ul><ul><li>Exhaust fan – </li></ul><ul><li>Air flow monitoring (External, only alarm) </li></ul><ul><li>- Room temperature control, cooling </li></ul><ul><li>Sensor Ni 1000 </li></ul><ul><li>-Set point +2 5 °C </li></ul><ul><li>-Thermostat for switch on/off </li></ul>T SP=2 5 °C 100 % 0 %
  5. 5. Solution: PID Controller Direct Sensor Connection <ul><li>Ni 1000 Temperature Sensor </li></ul><ul><li>Drive Based PID w/ Hibernation Mode </li></ul>Ni 1000 Sensor
  6. 6. Ni 1000 I/O SED2 Ni 1000 Analog input Digital input 1 Safety Input
  7. 7. Application - Water Pressure Control <ul><li>Function Description </li></ul><ul><li>Constant pressure (P) </li></ul><ul><li>Pump Logic Controller </li></ul><ul><li>(B&G Buster package) </li></ul><ul><li>P1, P2 and P3 on-off with motor </li></ul><ul><li>starters </li></ul>P3 P1 P2 100 % P SP=2.5 bar 0 % P1 P1 P1 P2 P3
  8. 8. Solution : Built-In Pump Cascading <ul><li>This function allows for control of up to two additional, cascaded pumps. With the two relay output contacts, the SED2 performs the cascading logic without additional controllers or I/O cards. </li></ul><ul><li>-No separate controller required </li></ul><ul><li>-Energy savings with SED2 </li></ul>Pressure demand Cascade P 100% 2. 3. 1.
  9. 9. Pump Staging I/O SED2 2 x analog input 6 x digital input 2 x digital output 0-10 volt Pressure Transmitter 1 On Command 1 safety input 2 nd stage pump 3 rd stage pump
  10. 10. Application – Temp. Control + Belt Monitoring <ul><li>Function Description </li></ul><ul><li>Exhaust fan – </li></ul><ul><li>Air flow monitoring (External, only alarm) </li></ul><ul><li>- Room temperature control, cooling </li></ul><ul><li>Sensor Ni 1000 </li></ul><ul><li>-Set point +2 5 °C </li></ul><ul><li>-Thermostat for switch on/off </li></ul><ul><li>Belt monitoring </li></ul>T SP=25°C 100 % 0 %
  11. 11. Solution: V-Belt Monitoring <ul><li>The SED2 ensures reliable V-belt monitoring without the expense of an external sensor. Both speed and torque are compared to a user-defined tolerance band. If the parameters do not match, the drive trips in the event of V-belt failure. </li></ul><ul><li>Also, the SED2 is able to monitor a pulse sequence from the sensor detecting rotation of the fan shaft. </li></ul>Speed Torque
  12. 12. Application – Temp. Control + Duct Pressure Control <ul><li>Function Description </li></ul><ul><li>Exhaust fan = Like air temperature control example </li></ul><ul><li>- Air flow monitoring (External, only alarm) </li></ul><ul><li>-Static pressure control </li></ul><ul><li>0-10v, 1-4inch wg </li></ul><ul><li>-Set point 2.5 inch </li></ul><ul><li>-Thermostat for switch on/off </li></ul>IWG SP=2.5 100 % 0 %
  13. 13. Solution: Duct Pressure Control <ul><li>0 – 10 Volt standard output signal </li></ul><ul><li>1% Accuracy over full scale </li></ul><ul><li>Available in uni-directional ½”, 1”, 2” and 5” wc </li></ul><ul><li>Available in bi-directional ¼” wc . </li></ul>Speed Reduction Pressure
  14. 14. Static Pressure Control I/O 2 x analog input 6 x digital input SED2 0-10 volt Pressure transmitter 1 On Command 1 Safety Static Pressure Switch
  15. 15. Bundled Package The SED2 is equipped with TEC application 2722 Which includes 99 subpoints for monitoring and control (See Attached Document for TEC Schedule)
  16. 16. Control Board
  17. 17. Control Terminals * Can also be configured as NI1000 inputs. Digital Inputs Terminals Parameter Default 1 5 P0701=1 ON right 2 6 P0702=12 Reverse 3 7 P07a03=9 Fault Acknowledge  4 8 P0704=15 Fixed Frequency 5 16 P0705=15 Fixed Frequency 6 17 P0706=15 Fixed Frequency Digital Outputs Terminals Parameter Default Operation 1 18,19,20 P0731 Drive fault 2 23,24,25 P0732 Drive running Analog Inputs * Terminals Parameter Default Operation 1 3,4 P0756(0) 0-10V dc 2 10,11 P0756(1) 0-10V dc Analog Outputs Terminals Parameter Default Operation 1 12,13 P0771(0) Frequency 2 26,27 P0771(1) Frequency
  18. 18. Mounting & Installation Considerations <ul><li>Type of environment </li></ul><ul><li>- What is the location like? Does it fall within the drives operating ranges for altitude & temperature </li></ul><ul><li>Type of power </li></ul><ul><li>- Line and load reactors reduce voltage. If voltage is already low, using them could have an effect on performance. </li></ul><ul><li>- Does the power system supply at least 1% impedance? </li></ul><ul><li>Type of motor </li></ul><ul><li>- Is it VFD rated? </li></ul><ul><li>- Distance from the drive? </li></ul><ul><li>- HP of the motors? </li></ul><ul><li>- Age of the motor? </li></ul>
  19. 19. Enclosure Ratings - Drive & Drive W/Bypass <ul><li>IP 20 </li></ul><ul><ul><li>No NEMA equivalent, needs to be mounted in another enclosure </li></ul></ul><ul><ul><li>Generally used in US for OEM applications </li></ul></ul><ul><ul><li>Our standard unit as it comes from the factory </li></ul></ul><ul><li>IP 21 </li></ul><ul><ul><li>NEMA 1, protects operator from electrical hazard and protects the equipment from falling material </li></ul></ul><ul><ul><li>Our standard unit when fitted with gland plate and dust cover </li></ul></ul><ul><li>IP 54 </li></ul><ul><ul><li>No direct US equivalent, but exceeds NEMA 12 </li></ul></ul><ul><ul><li>NEMA 3R </li></ul></ul><ul><ul><li>Water tight, limited need in drive applications </li></ul></ul>
  20. 20. Mounting & Installation Considerations <ul><li>Line Reactor Installation </li></ul><ul><li>Not recommended to reduce Harmonics </li></ul><ul><li>Can be ordered with or without an enclosure </li></ul><ul><li>Installed to protect the drive from: </li></ul><ul><ul><li>Power spikes or sags caused from transfer to generator </li></ul></ul><ul><ul><li>Poor heavy switch load on the same load center </li></ul></ul>
  21. 21. Mounting & Installation Considerations <ul><li>Load Reactor Installation </li></ul><ul><li>Long wire leads from drive to motor </li></ul><ul><ul><li>As wire length from drive to motor increases, the voltage spike increases </li></ul></ul><ul><ul><li>Can be ordered with or without an enclosure </li></ul></ul><ul><ul><li>Installed to protect the motor from: </li></ul></ul><ul><ul><li>Spikes caused from the drive switching frequencies or IGBT </li></ul></ul>
  22. 22. Mounting & Installation Considerations <ul><li>Line and Load Reactor Installation </li></ul><ul><li>Always use Siemens Building Technologies specified reactor </li></ul><ul><li>For retro-fit applications </li></ul><ul><ul><li>REMOVE AND REPLACE EXISTING REACTORS WITH SBT SPECIFIED REACTORS </li></ul></ul>
  23. 23. Siemens SED2 VFD Advantages <ul><li>Low harmonics design </li></ul><ul><li>Small enclosure size </li></ul><ul><li>Many standard features </li></ul><ul><li>Reduces operating cost </li></ul><ul><li>Low power losses/high efficiency </li></ul><ul><li>Minimal effect on customer power </li></ul><ul><li>Wide power range – from ½ to 125 HP </li></ul>