Edf R&D Dennetiere Hvdc Emtp

  1. 1. EMTP-RV user group meeting, Dubrovnik HVDC models in EMTP-RV Sébastien Dennetière, EDF R&D, April 30th 2009
  2. 2. Presentation layout  Why do we develop HVDC models ?  Description of a detailed HVDC model in EMTP-RV  Simulation results  Description of an average HVDC-VSC model in EMTP-RV  Simulation results  Next developments 2 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  3. 3. Why do we develop HVDC models ?  Growing interest in HVDC links in transmission system  Avoid overhead lines construction  Flexibility  HVDC links models are required :  Determination of the best HVDC solution in a specific case  Training of power system engineers  4 Models :  Detailed models for transient studies: generic & specific  Average models for system studies : generic & specific 3 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  4. 4. Detailed HVDC model  Main characteristics :  Generic standard HVDC (Bipolar 12 pulses)  Rated power : 1200 MVA  DC voltage : +/- 500 kV  DC cable 1400 mm², 70 km  AC Filters : 11th, 15th, 23rd/25th ; DC Filters : 6th & 12th  Reactive power compensation : filters + capacitor bank  Smoothing reactor : 370 mH  AC Short Circuit Power : 6000 MVA  Control system :  Current controller on rectifier side  Gamma controller or current controller on rectifier side  Developed by : University of Ontario Institute of Technology , Ecole Polytechnique de Montreal and EDF R&D 4 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  5. 5. Detailed HVDC model L2  AC network : R1 + + 1.5 85mH +  SCP = 6000 MVA 400kVRMSLL /_50 ?v  AC filters:  Each filter and capacitor bank generate ¼ of reactive power consumed by converters  Filters parameters are calculated from analytical expressions included into scripts ligne PQ_capa_bank PQ_HP PQ_11 PQ_13 PQ PQ PQ PQ + + + #C_24p# #R_11#,#L_11#,#C_11# #R_13#,#L_13#,#C_13# Capacitor bank + #L_24p# + harmonic 11th harmonic 13th HP filter #R_24p# + #C_bank# 5 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  6. 6. Detailed HVDC model  Converters transformers : ratio_rec_Y  Sn = 300 MVA / transformer YY1 1 2 B6P_1 6-pulse bridge 3-phase + 368/205.45 gamma_min_star_bd aux  Tap changer firing_rec_star gates -  Xlf = 12.5% ratio_rec_D B6P_3 YgD_2 1 2 6-pulse bridge 3-phase +  Converters : 368/205.45 gamma_min_delta_bd aux firing_rec_delta gates -  12 pulses ratio_rec_D Rectifier  RC snubbers YgD_1 B6P_4 6-pulse bridge 1 2 3-phase + 368/205.45 gamma_min_delta_minus_bd aux firing_rec_delta gates - ratio_rec_Y B6P_5 YY9 1 2 6-pulse bridge 3-phase + 368/205.45 gamma_min_star_minus_bd aux firing_rec_star gates - 6 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  7. 7. Detailed HVDC model  DC Cables :  Paper insulated +/- 500 kV, 1400 mm²  CP model  DC filters : RLC branches ( 6th et 12th )  Smoothing reactance : 370 mH RL4 cable_plus RL3 + 500 kv + 1400 mm² Cu 0.139,370mH 0.139,370mH DC filter DC filter DC filter DC filter 600 Hz 300 Hz 600 Hz 300 Hz 7 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  8. 8. Detailed HVDC model  Rectifier / inverter control system firing_rec_star DEV7 Rectifier_inverter_control 1 1 a g1 b VKSood g2 2 2 gamma_min_delta_bd dp 3 3 c g3 Regulation gamma_min_star_bd gamma_min_delta_minus_bd gamma_min_star_minus_bd sp dn sn out delay width g4 g5 blocking g6 4 5 6 4 5 6 id_rec idc iref iref2 single firing of iref1 io 6-pulse bridge 0.0002 scope Pulse generators v_rec_c f(u) scope v_rec_b firing_rec_delta scope DEV12 v_rec_a Fm8 a g1 1 1 1 VKSood 2 2 f(u) b g2 2 c g3 3 3 v_pri_rec_a 4 4 DEV6 Fm9 delay g4 1 f(u) width g5 5 5 5.3e-6 2 6 6 v_pri_a Fm11 blocking g6 v_pri_rec_b V_sync_a 1 Fm10 v_pri_b single firing of V_sync_b 2 f(u) 1 v_pri_c f(u) 6-pulse bridge 5.3e-6 V_sync_c 3 2 v_pri_rec_c delta_freq V.K.Sood Star/Delta DQO_PLL_50Hz 3PH AC Line 5.3e-6 transformation voltages at Rectifier DEV9 v_pri_a v_pri_b v_pri_c delta_freq V_sync_a V_sync_b V_sync_c 1 2 3 Fm12 f(u) Pulse generation Synchronization DQO_PLL_50Hz V.K.Sood DEV10 1Fm13 v_pri_a V_sync_a 2 f(u) v_pri_b V_sync_b 3 v_pri_c V_sync_c delta_freq V.K.Sood DQO_PLL_50Hz Synchronising System C9 tap_changer_rec 205.45 c ratio_rec_Y 365 v2 v1 ratio_Y ratio_D ratio_rec_D Transformer tap changer c C10 8 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  9. 9. Detailed HVDC model  Rectifier control system from page 1 Initialization idc sg10 step Step Initialisation Div1 PI current Gain15 amplitude 1pu 1 width 4000ms 1000 f(s) controller 180 time shift 200 ms Current Scaling iref iref sg9 0.8111 deg_pu_delay sum12 1.2 Gain17 0.81111 + rc rv Int4 sum13 1 1 ramp 2 SUM + + 1 - + 10 !h + + 1 120 + + !h deg_pu_delay_lim Current order to be sent 0.2 lim8 0.0278 0.0278 lim7 Kp=1.65 Ramp Initialisation to inverter (page 3) Gain16 Ki=2.75 alpha_delay in seconds amplitude 1pu via telecoms 0.7 divide by 120 elec. degs width 150 ms Alpha rectifier limits: time shift 50 ms alpha_min=5 degs =0.0278 alpha_max=145 degs=0.81111 sg3 err_idrec scope step step_change_Io Iref iref scope Step change in Iorder amplitude -0.1 pu width 200 ms time shift 501 ms Step change in Iorder 9 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  10. 10. Detailed HVDC model  Inverter control system Fm5 dp 1 0.2 sp 2 !h MIN f(s) 1 dn 3 !h Users may select at the inverter either sn 4 0.05 lim6 1. Inverter Gamma control, or 2. Inverter Current control. This is normally biased off sg4 scope with the current margin setting gamma_min step gamma_step PI Gamma Step Gamma test amplitude 0.05 controller width 300 ms time shift 1400 ms 0.944 sum3 Step change in C12 c + + + !h - + + !h Gain6 10 rc rv Int1 !h + sum5 + 1 0.944 scope Gain1 180 scope sum4 + !h inv_gamma_controller alpha_inv_degs Gamma order ref Gamma 0.10 gamma_ref scope Gain5 0.711 Kp=0.75 0.711 lim4 beta_delay in seconds 1 V = 180 degs Ki=35.0 0.2 inv gamma divide by 120 electrical degs 0.1 = 18 degs MIN_SELECT Div2 1 MIN !h 1 2 120 inv current Alpha inverter limits: alpha-min-inv =110 degs = 0.611 pu alpha-max-inv =170 degs = 0.944 pu 0.95 sum1 Div3 Gain4 0.925 rc rv Int3 sum2 idc 1 idc 1000 f(s) !h + + 14 !h + + 1 scope io - !h + !h inv_current_controller 0.711 lim1 current 0.611 scaling Kp=4.0 Gain3 Ki=12.0 1.8 sum8 sum6 0.95 + + + + 1 scope - - Io_inv 0.1 lim3 C9 Step Io test at rec sg6 c 0.1 PI current amplitude 0.1 pu width 270 ms step margin 0.1 pu simulates telecoms delay for margin setting controller time shift 470 ms 10 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  11. 11. Detailed HVDC model EMTP-RV design v(t) vd_rec_filtered v_pri_rec_a scope V_pri_rec_a v_pri_rec_b f(s) scope vd_rec_filtered V_pri_inv_a v(t) scope v_pri_inv_a v_pri_rec_c p3 v_pri_inv_b v_pri_inv_c vd_inv 400 kV AC system vd_rec scope scope id_rec +VM ?v ratio_rec_Y vd_rec id_rec ratio_inv_Y 400 kV AC system B6P_1 B6P_2 L2 YY1 RL4 v(t) i(t) cable_plus RL3 R1 + PQ_AC_rec 1 2 6-pulse bridge p1 500 kv 6-pulse bridge YY2 L1 + PQ + + 1400 mm² Cu + - 2 1 PQ_AC_inv 1.5 85mH 3-phase 0.139,370mH 0.139,370mH + + R2 3-phase PQ 1.5 + 85mH 400kVRMSLL /_50 368/205.45 gamma_min_star_bd aux + ?v aux gamma_min_star 410/205.45 400kVRMSLL /_0 firing_rec_star DC filter DC filter DC filter DC filter PQ_pole1_rec gates - + gates firing_inv_star PQ 600 Hz 300 Hz 600 Hz 300 Hz PQ_pole1_inv PQ ratio_rec_D ratio_inv_D PQ_filter_rec B6P_3 YgD_2 B6P_6 PQ PQ_filter_inv 6-pulse bridge YgD_3 1 2 + + Pole - 6-pulse bridge 2 1 PQ 3-phase 3-phase Rectifier AC Filters 368/205.45 gamma_min_delta_bd aux aux gamma_min_delta 420/205.45 Inverter AC Filters + 10M AC filters firing_rec_delta gates - harmonics + gates firing_inv_delta AC filters R11 11, 13, 24+ harmonics and 11, 13, 24+ Capacitor bank and filters_rec ratio_rec_D Capacitor bank Rectifier filters_inv B6P_4 ratio_inv_D B6P_7 YgD_1 Filters sizing 6-pulse bridge YgD_4 1 2 6-pulse bridge 3-phase + - 2 1 3-phase + 368/205.45 gamma_min_delta_minus_bd aux aux gamma_min_delta_minus 10M 420/205.45 Filters sizing firing_rec_delta PQ_pole2_inv PQ_pole2_rec gates - - Pole + gates firing_inv_delta R19 PQ PQ ratio_rec_Y ratio_inv_Y B6P_5 B6P_8 YY9 YY4 6-pulse bridge 1 2 + - 6-pulse bridge 2 1 3-phase 600 Hz 300 Hz 3-phase 600 Hz 300 Hz Inverter AC aux DC filter DC filter aux 368/205.45 gamma_min_star_minus_bd DC filter DC filter gamma_min_star_minus 410/205.45 system Rectifier AC system RL1 cable_minus RL2 firing_rec_star 500 kv firing_inv_star gates - + 1400 mm² Cu + + gates 0.139,370mH 0.139,370mH 11 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  12. 12. Detailed HVDC model Simulation results PLOT PLOT y y time (s) time (s) Step change in Iorder Step change in Gamma order Simulation options : Δt = 25µs, tmax = 2s, CPU time = 30s 12 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  13. 13. Detailed HVDC model Voltage sag AC voltage rectifier side PLOT AC voltage inverter side PLOT y y time (s) time (s) DC Current PLOT DC Voltage PLOT y y time (s) time (s) 13 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  14. 14. Detailed HVDC model, next developments  Available on demand  Implementation of the Voltage Dependent Current Limit Unit :  Static characteristic adapts Iref as a function of DC voltage  Dynamic characteristic adapts Iref as a function of DC voltage according to the fast down time and slow up time  Modeling of protection systems (overvoltage, overcurrent, commutation failures)  Implementation of start up algorithm  Integration of control systems designed by manufacturers (DLL connection) to obtain specific HVDC models 14 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  15. 15. Average HVDC VSC model  Main Characteristics :  Rated power : 1200 MVA  DC voltage : +/- 320 kV  DC cable 2500 mm² XLPE insulation, 70 km  Converters transformers  AC & DC filters  Capacitor bank : 20 µF  AC short circuit power : 6000 MVA  Control system :  Active power regulation  DC voltage regulation  Reactive power regulation  Developed by EDF R&D 15 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  16. 16. Average HVDC VSC model YY1 DC link YY2 AC_network2 LF + TD 1 2 2 1 + + + + LF + TD AC_network1 400/450 400/450 GND GND GND GND HVDC_VSC_Link F fault 3-phase fault during 200 ms Q2_mes scope scope P2_mes Q1_mes P1_mes scope scope Load-flow Load-flow Initialization Initialization P2_mes Q2_mes Q1_mes P1_mes P Q k_HVDC Q P m_HVDC + + V1 powerMeter2 powerMeter1 phase_2   phase_1 V_mag V2_mag V_mag V1_mag XLPE_cable_1 + CP 7.00000E+01 + + 60uF 60uF !v !v + + + + Vdc1_mes Vdc2_mes Idc1_mes cI2 V V cI1 Idc2_mes 0.50/100 - - 0.50/100 + + 60uF 60uF !v 7.00000E+01 !v + CP XLPE_cable_2 16 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  17. 17. Average HVDC VSC model PLOT PLOT y y time (s) time (s) Active power step change DC voltage step change Simulation options : Δt = 50µs, tmax = 3s, CPU time = 4.2s 17 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière
  18. 18. HVDC VSC model – Next developments  Reactive power controller has to be improved  Contribution to CIGRE WG B4.38 (Simulation of HVDC and FACTS)  Implementation of manufacturer controllers models using DLL connection to obtain specific HVDC models  Available on demand 18 April 28th 2009, EMTP-RV UGM Dubrovnik, Sébastien Dennetière

×