A SEMINAR ON               Submitted by:-               Rakesh Kumar Padhy               0901106221               Electric...
CONTENTSPower Factor: An IntroductionTypes of circuit  • Linear Circuit  • Non-linear CircuitImportance of power factor...
Power factor: An introductionIt is the ratio of real power flowing through the load to the apparent power in the circuit...
Types of CircuitThere are two types of circuits based on the type of current waveform  • Linear loads  • Non-linear loads...
Variation of PF in transmission            systemsGenerally due to inductive loads the power factor never remains unity i...
Disadvantages of low PFVoltage regulation becomes poorGreater amount of apparent power needed to get the same amount of ...
Power Factor Correction for linear               loadsVarious methods of power factor correction (PFC)are adopted to minim...
APFC unitIt’s an automatic system adjusting itself to control the power factor above a desired value by a bank of capacit...
Parts of the APFC unit1.Reactive power control relay Capable of measuring the   reactive and active power of   the networ...
The main functions of the reactive power control relay Automatic connection detection (Star or Delta) Automatic detectio...
2.Network connection pointsSince the power factor of the loads is to becompensated hence the connection of the APFC unit i...
3.Slow-blow switches Slow blow switches are always used because of the  following requirements  • To sustain the inrush a...
4.Inrush current contactors Used for damping the inrush current arising due  to  • Remaining capacitor voltage due to fas...
5.Capacitor BankThe capacitor bank is themain part of the APFCunits. Large capacitor banksare installed in the APFC’swhich...
6.Control Transformer Monitors the switchboard load  (or load to be corrected) Placed physically above  (towards the sup...
Maintenance of the APFC unitThe major maintenance checks involved for the APFCunit are In “out of maximum demand hours” (...
Conclusion Hence the APFC units correct the power  factor above a decided value by switching  the appropriate no of capac...
Automatic power factor correction unit
Upcoming SlideShare
Loading in...5
×

Automatic power factor correction unit

11,665

Published on

1 Comment
8 Likes
Statistics
Notes
No Downloads
Views
Total Views
11,665
On Slideshare
0
From Embeds
0
Number of Embeds
3
Actions
Shares
0
Downloads
760
Comments
1
Likes
8
Embeds 0
No embeds

No notes for slide

Automatic power factor correction unit

  1. 1. A SEMINAR ON Submitted by:- Rakesh Kumar Padhy 0901106221 Electrical engineering
  2. 2. CONTENTSPower Factor: An IntroductionTypes of circuit • Linear Circuit • Non-linear CircuitImportance of power factor in distribution systemsDisadvantages of low power factorPFC in linear loadsThe APFC (Automatic Power Factor Correction) unitParts of the APFC unitMaintenance of the APFC unitConclusion
  3. 3. Power factor: An introductionIt is the ratio of real power flowing through the load to the apparent power in the circuitIt is also defined as the cosine of the angle between the voltage and current phasesIt is a dimensionless no between 0 and 1Whether the current is leading or lagging the power factor is termed as leading or lagging PF correspondingly
  4. 4. Types of CircuitThere are two types of circuits based on the type of current waveform • Linear loads • Non-linear loadsThe type of loads which doesn’t change the current waveform shape are known as linear loadsThe loads on the others case which change the shape (distort) the current waveform are termed as non-linear loadsDistortion decreases average power transmitted to the load
  5. 5. Variation of PF in transmission systemsGenerally due to inductive loads the power factor never remains unity in realityA capacitive network gives reactive power and an inductive network takes the sameIn both the cases the power factor becomes less than 1 causing more current to be transferred for the same amount of real power
  6. 6. Disadvantages of low PFVoltage regulation becomes poorGreater amount of apparent power needed to get the same amount of real powerThe increase in reactive power increases the current flowing through the networkSize of the transformer, switch gears etc. increase thereby increasing the transmission cost
  7. 7. Power Factor Correction for linear loadsVarious methods of power factor correction (PFC)are adopted to minimize the apparent power as: Using capacitor banks in Automatic Power Factor Correction (APFC) units For high voltage rating the power electronic devices such as Static VAR compensator or STATCOM are used It’s also a good practice to use an unloaded synchronous motor
  8. 8. APFC unitIt’s an automatic system adjusting itself to control the power factor above a desired value by a bank of capacitors switched by means of contractorsContractors are controlled by a regulator that measures PF in the networkDepending upon the load PF the controller will adjust the PF by switching the necessary no of capacitors from the bank
  9. 9. Parts of the APFC unit1.Reactive power control relay Capable of measuring the reactive and active power of the network Works in conjunction with a capacitor bank Controls the programmed target PF by activating/deactivating the capacitors
  10. 10. The main functions of the reactive power control relay Automatic connection detection (Star or Delta) Automatic detection of capacitor stages Patented characteristics avoiding compensation of very low active power Reactive power requirement-switching delay time Alarm signals for • Failure to reach the target PF • Overcurrent in the capacitor • Defects at capacitor stages
  11. 11. 2.Network connection pointsSince the power factor of the loads is to becompensated hence the connection of the APFC unit isalways done in parallel with the supply connection.Generally Y- connection of the capacitor bank ispreferred because the transmission distribution ofthree phase distribution system above 132 kv is Yconnected always
  12. 12. 3.Slow-blow switches Slow blow switches are always used because of the following requirements • To sustain the inrush and starting current surges due to vehicular loads • It offers a time delay between overloading and fusing • They can withstand heavy currents (about ten times the rated)
  13. 13. 4.Inrush current contactors Used for damping the inrush current arising due to • Remaining capacitor voltage due to fast switching • Short circuit power of supply • Fault level of supply networks The contractors also protect the welding of the main contacts of the contactors Prevent the capacitors from high stress
  14. 14. 5.Capacitor BankThe capacitor bank is themain part of the APFCunits. Large capacitor banksare installed in the APFC’swhich switch in order tomeet the desired powerfactor requirement. Eachcapacitor is individuallyfused with appropriatelysized current limit fuse.
  15. 15. 6.Control Transformer Monitors the switchboard load (or load to be corrected) Placed physically above (towards the supply) the connections for the PFC system In case more than one transformers are fitted they are always connected in series as they work as CT
  16. 16. Maintenance of the APFC unitThe major maintenance checks involved for the APFCunit are In “out of maximum demand hours” (eg. Late nights or weekends) switch off the system after internal and external checks Remove contactor tops and inspect for contact wear, check capacitance of each capacitor Check (and adjust if necessary) all connections to contactors, capacitors, fuses etc. Re-energize system and check current (true RMS) and harmonics drawn by each capacitor step. Check voltage level and fuses
  17. 17. Conclusion Hence the APFC units correct the power factor above a decided value by switching the appropriate no of capacitors from the capacitor bank In non-linear loads we use inductors, filters, valley-fill circuit etc. to suppress harmonics as they cause the current wave form to be distorted
  1. A particular slide catching your eye?

    Clipping is a handy way to collect important slides you want to go back to later.

×