Transformer basic

  1. 1. Transformer Basic-B.
  2. 2. working principle A transformerworks on theFaraday,slawofelectromagnetic induction.A transformerconsists of alaminatedmagnetic
  3. 3. Transformerparts
  4. 4. Winding
  5. 5. Type of transformer Distribution Power. Control. Auto. Isolation. Instrument potential. Instrument current Indoor Outdoor Oil type Dry type Core type Shell type Natural cool Forced air/watercool
  6. 6. Distribution transformerPrimaryvoltageSecondaryvoltageCapacity(KVA)Construction Impedancerange3-11 380-440 25,40,63 Dry type 3-7%100,150,250 Dry type300,400,500 Oil/dry type630,750,1000 Oil type1250,1600 Oil type2000,2500 Oil type
  7. 7. Star delta connection
  8. 8. Star delta diagram
  9. 9. Star delta voltage current Line voltage on Primary side = √3 X Phase voltage onPrimary side. So Phase voltage on Primary side = Line voltage on Primaryside / √3 Transformation Ration (K) = Secondary Phase Voltage /Primary Phase Voltage Secondary Phase Voltage = K X Primary Phase Voltage. As Secondary  in delta connected: Line voltage on Secondary side = Phase voltage onSecondary side. Secondary Phase Voltage = K X Primary Phase Voltage.=K X (Line voltage on Primary side / √3)
  10. 10. Advantages of StarDelta Connection The Y-D connection has no problem with thirdharmonic components fewer numbers of turns are required The neutral available on the primary can beearthed to avoid distortion. Neutral point allows both types of loads(single phase or three phases) to be met Large unbalanced loads can be handledsatisfactory
  11. 11. Disadvantages of star delta The secondary voltage is not in phase with theprimary If secondary of this transformer should beparalleled with secondary of another transformerwithout phase shift, there would be a problemApplication: commonly employed for power supplytransformers. Y connection on the HV side reduces insulationcosts the neutral point on the HV side can begrounded.
  12. 12. Tap changerIt is a device fitted inthe transformer,which is used tovary the voltagetransformationratio. Off load tapchanger Onloadtapchanger(OLTC)
  13. 13. BUSHINGTransformer Bushingsare specially designedelectrical terminals fortaking out windingends (leads) throughthe openings providedon the top cover orwall of the oftransformer tank andconnecting to theincoming andoutgoing lines.
  14. 14. CT =CURRENTTRANSFORMERTypical specification fora 11kV CT System voltage:11 KV Insulation level voltage (ILV) :12/28/75 kV Ratio: 200/1 - 1 - 0.577 A Core 1: 1A, metering, 15VA/class 1, ISF<10 Core 2: 5A, protection, 15VA/5P10 Short time rating:20 kA for 1second
  15. 15. PT=POTENTIALTRANSFORMERTypical specification fora 11 kV VT System voltage: 11 KV Insulation level voltage (ILV) : 12 /28/75 kV Number of phases: Three Vector Group: Star / Star Ratio: 11 kV/ 110 V Burden: 100 VA Accuracy: Class 0.5 Voltage Factor: 1.2 continuous and1.5 for 30 seconds With provision forfuse
  16. 16. Condition ForParallel Operation OfTransformers Same voltage and Turns Ratio (both primary andsecondary voltage rating is same) Same Percentage Impedance and X/R ratio Identical Position of Tap changer Same KVA ratings Same Phase angle shift (vector group are same) Same Frequency rating Same Polarity Same Phase sequence
  18. 18. Impedance Levels Based kVA Minimum Impedance, %0 – 150 Manufacturer’s standard151 – 300 4301 – 600 5601 – 2,500 62,501 – 5,000 6.55,001 – 7,500 7.57,501 – 10,000 8.5Above 10,000 9.5
  19. 19. Oil and winding temperature indicationDescription Setting, degree CFan start 85Fan stop 75Pump start 90Pump stop 80Oil temperature alarm 85Oil temperature trip 95Winding temperaturealarm100Winding temperature trip 110
  20. 20. Transformer protection–  Overcurrent & Short circuit (51):The relay used is CDAG 51. Earth Fault (51N): The relay used is CAG 14. TransformerDifferential (87T): The relay used isDTH 31, 11/6.6KV transformers.  WTI (49WTX/49WAX): protected against increasein winding temperature. The relay used is VAA 34. OTI (49TX/49AX): protected against increase in oiltemperature. The relay used is VAA 34.  Buchholz (63TX/63AX): protected against internal.The relay used is VAA 34.