AUTOMATION OF BREAK GENERATOR
                       Presented by
          K.JANAKI
          K.L.SUSHMA PRIYA
          K.PRASAD
         B.SANTHAN BHARDWAJ
CONTENTS
1.Aim of the project
2.Description of expansion turbine
3.Description of ASP
4.GEFANUC PLC system
    a) advantages
   b)disadvantages
 5.Input output lists
     6.Conclusion
AIM OF THE PROJECT
To improve the performance of “EXPANSION TURBINE OF ASU
 - 1” and to provide necessary automation with latest Micro-
    Processor based PLC logic system to avoid spurious trips.
                     Existing system is relay logic system. It is
 always giving spurious trips and hampering production. With
   the newly implemented PLC based system, we are able to
  give continuous monitoring of all process parameters from
 CCP DESKTOP monitor, historical trends, improved accuracy,
    reliability and ensuring safe & continuous running of the
                        expansion turbine
DESCRIPTION OF EXPANSION
              TURBINE

  •A part of the air is taken at an intermediate point of the
  exchangers and sent to a Centrifugal Expansion turbine
 equipped with a Break Generator to provide the necessary
refrigeration to make-up the thermal losses of the cold box.
                   PROCESS PARAMETERS
           Air flow (max.)             : 37,500 Nm3/hr
           Inlet pressure                : 6.6 kg/cm2 abs
          Outlet pressure                : 1.45 kg/cm2 abs
           Inlet temperature                : (-) 135 ºC
          Outlet temperature                 : (-) 178 ºc
             Power                          : 550 KW
            Model                         : ETG 360 NS
           Constructor                     : ATLAS COPCO
TURBINE CHECK LIST

    1.Oil level shown on oil gauge glass.
     2.Thawing gas valves closed.
     3.Nozzle blades closed.
     4.Quick-close shutoff valve closed.
     5.Temperature of turbine bearings .If temperature of either
bearing is less than +15 deg. C, bearings must be warmed by
turning on lubricating oil supply. Turbine outlet valve must be
closed. If bearing temperature cannot be raised by circulating
lubricating oil, turbine must be heated with thawing gas.
 Oil filter clean and in circuit.
    6.Adjust the stroke of nozzle control valve.
TURBINE START UP PROCEDURE
        1.Turn on sealing gas supply.
        2. Switch on control power supply for instruments and
controls.
        3.Electrical auxiliary oil Pump starts automatically.
Turn on cooling water supply for oil cooler.
      4.Open turbine outlet valve.
      5.Open turbine inlet valve.
      6.Open quick-close shutoff valve.
7. Open up nozzle valve until operating speed level is
           attained and generator cuts automatically.
       8.Keep check on bearings temperatures, gap pressure
  and satisfactory running of complete unit during start-up.
      9.Switch off auxiliary oil pump by switch “oil pump off”.
      10. After generator has cut in, load turbine by opening up
nozzle blades as far as required for given operating conditions.
     11.During start-up briefly open drain and instrument lines
              to vent them, re-closing afterwards.
DESCRIPTION OF ASP
                       Air Composition:-
               Air is mainly a mixture of two gases:
    Oxygen and Nitrogen in the following percentages.
              *1/5th Oxygen, namely 20.96%.
              *4/5th nitrogen, namely 78.11%.
    Air also contains other components such as the five rare
gases, which are found in a constant percentage by volume.
                      Argon (Ar) – 0.93%
                      Neon (Ne) – 0.0015%
                     Helium (He) – 0.0005%
                     Krypton (Kr) – 0.0001%
                    Xenon (Xe) – 0.000008%
Some other components are also present in variable
               quantities such as:
              *Water vapor (H2O)
              *Carbon dioxide (CO2 about 0.03%)
              *Hydro carbons, Acetylene (C2H2)
                 *Ozone (O3)
SEPARATION OF AIR COMPONENTS

 Air components are separated by means of liquid distillation
                 columns, in distillation column.
   A thorough separation of air cannot be made by means of a
                   single rectification column:
        1. The first one is the high pressure column separating
the process air into liquid nitrogen and oxygen rich liquid (40%
                             oxygen).
       2. The second one is the low pressure column which is
   used for final separation into pure nitrogen and oxygen.
AIR PURIFICATION
           Air contains some water, carbon dioxide, hydrocarbons
  and oil if it is compressed by means of lubricated equipment.
            These components must be removed because water
and carbon dioxide when cooled to low temperatures may form
  a deposit in the pipe work and result in subsequent plugging.
 Acetylene and oil are also dangerous and may cause explosion
        when they come into contact with liquid oxygen.
           Heavier hydrocarbons are removed during cooling. It
  should be noted that hydrocarbons may be removed when in
                            liquid state.
PROCESS DESCRIPTION
              Air is sucked through air pulse filter which removes
  the dust particles, then it goes through the inlet guide vane and
                       compressed in four stages.
.         After first stage compression, the compressed air goes to
  the first water inlet cooler and then to the second stage suction.
  .          From second stage discharge it goes to second cooler
                    and then to third stage suction.
. From third stage discharge it goes to third inter cooler and then
                         to fourth stage suction
.From fourth state discharge it goes to after cooler.
Discharge pressure after first, second, third and fourth stages are
              0.75, 2.0, 3.8, 6.4 Kg/Cm2 respectively.
            Suction pipe gas temperature of first stage to fourth
stage is 40 to 45 deg c. Discharge gas temperature at fourth stage
                          is 90 to 105 deg c.
                To protect the machine from surges it has been
 provided with anti-surge valve (ASV).When there is a sudden
   increase of discharge pressure or decrease of discharge flow
 through the compressor, the machine goes to an unstable region
                             called surge.
INTRODUCTION TO PLC’S

           The break generator is equipped with pressure gauges,
   temp Indicators, pressure switches, speed measurement &
vibration measurement systems and safety devices. At present all
        safety interlocks are based on relay logic system.
              In this proposed automation project the relay logic
        system is converted into PLC based logic system.
PLC’S
            The Series 90-30 PLC’S are members of the GE
Fanuc Series 90™ family of Programmable Logic Controllers
                          (PLC’S).
               They are easy to install and configure, offer
advanced programming features, and are compatible with the
                    Series 90-70 PLC’S.
             Two Windows-based configuration/programming
  packages are available for Series 90-30 PLC’S. VersaPro
          software supports all Series 90-30 CPUs.
.              The software structure for the 341 and lower Series
    90-30 PLC’S uses an architecture that manages memory and
          execution priority in the 80188 microprocessor.
               The 35x and 36x series of Series 90-30 PLC’S use
                   an 80386EX microprocessor
            This operation supports both program execution and
       basic housekeeping tasks such as diagnostic routines,
           input/output scanners, and alarm processing.
       The system software also contains routines to communicate
                       with the programmer.
The Series 90-30 Genius Bus Controller (catalog number
 IC693BEM331) is used to interface a Genius I/O serial bus to a
 Series 90-30 PLC. The GBC receives and transmits control data
    of up to 128 bytes for up to 31 devices on the Genius bus.
                     A Genius bus may serve:
              Genius blocks, which provide interface to a broad
   range of discrete, analog, and special-purpose field devices.
    Genius blocks are self-contained modules with advanced
diagnostics capabilities and many software-configurable features.
Remote Drops, Series 90-70 I/O racks that are interfaced to
 the bus via Remote I/O Scanner Modules. Each remote drop can
include any mix of discrete and analog I/O modules, providing up
      to 128 bytes of input data and 128 bytes of output data.
           Hand-held Monitor, which can be used as a portable
  device or permanently mounted. A HHM provides a convenient
      operator interface for block setup, data monitoring, and
                             diagnostics.
         Multiple hosts, for communications using datagram’s and
                            Global Data.
ADVANTAGES:
By replacing the analog systems with latest microprocessor
        based Control systems the advantages are
               1.Spurious indications will be eliminated.
               2.Reliability will be ensured.
               3.Production delays will be avoided.
               4.Accuracy will be improved.
                5.Events will be monitored.
               6.Trip analysis becomes easier.
               7.Historical trends will be obtained.
               8.Maintenance cost will be reduced.
              9.Spurious indications will be eliminated.
              10.Reliability will be ensured.
11.Production delays will be avoided.
12.Accuracy will be improved.
13.Events will be monitored.
14.Trip analysis becomes easier.
15.Historical trends will be obtained.
16.Maintenance cost will be reduced.
DISADVANTAGES:
       1.All interlocks are used change over series contacts. So this is
     very difficult to trace out the abnormalities in the process.
          2.All the contacts are taking from the field switches.
      3.Control panel and field switches are mounted on the body of
equipment. So during running condition switches are malfunctioning
                            due to vibration.
                         4.Spares are too costly.
       5. Problem analysis and troubleshooting takes lot of time and
                       causing production delays.
      6.All interlocks are used change over series contacts. So this is
     very difficult to trace out the abnormalities in the process.
7.All the contacts are taking from the field switches.
 8.Control panel and field switches are mounted on the body
of equipment. So during running condition switches are
             malfunctioning due to vibration.
                 9.Spares are too costly.
 10.Problem analysis and troubleshooting takes lot of time
             and causing production delays.
INPUT-OUTPUT PORTS

                         32 Point Discrete Input Module
    Power Sources: The module receives power from the Field Processor to r
  run its own 5-volt logic. An external 24VDC supply is needed to power the
                                  input devices.
    LEDs: Individual LEDs (logic side), visible through the transparent portion
 of the module top, indicate the on/off status of each input. The PWR LED is
                on when field and backplane power is present.
    Host Interface: Intelligent processing for this module is performed by the
   Bus Interface Unit or elsewhere in the system. This includes configuring
 features such as input defaults and fault reporting. The module has 16 bits
(two bytes) of discrete input data. A Bus Interface Unit is required to provide
              this input data to the host and/or local processor.
Module Operation: A network of resistors and capacitors establishes
 input thresholds and provides input filtering. Opt isolators provide isolation
between the field inputs and the module's logic components. Data from all 16
                       inputs is placed into a data buffer.
                        32 Point Discrete Output Module
        Power Sources: Power for the module itself comes from the power
  supply in the Bus Interface Unit. An external source of DC power must be
                provided for the switches that power the loads.
         LEDs: Individual green LEDs (logic side) indicate the on/off status of
   each output. The green LEDs remain off when user power is not present,
 regardless of the state of the outputs. Individual yellow LEDs show the fault
  status of each output. The green PWR LED is on when field and backplane
                               power are present.
Host Interface: Intelligent processing for this module is performed
      by the Bus Interface Unit or elsewhere in the system. This includes
configuring features such as output default and fault reporting. The module
has 8 bits (one byte) of discrete output data. A Bus Interface Unit is required
        to obtain this output data from the host and/or local processor.
           Module Operation: After checking the Board ID, the Bus Interface
Unit sends output data to the module in serial format. During transmission,
 the module automatically loops this data back to the Bus Interface Unit for
  verification. Serial to parallel converters convert this data into the parallel
   format needed by the module. Opto-isolators isolate the module's logic
  components from field outputs. Power from the external power supply is
             used to drive the FETs that source current to the loads.
CONCLUSION

               After completion of the “AUTOMATION OF EXPANSION TURBINE
OF ASU – 1” the performance of the break generator is found to be improved.
    Now the operation people are easily able to run the machine without
spurious breakdowns. In that context Instrumentation is playing major role in
early alarming and minimizing the breakdown of the equipment and ensuring
              the safety of man / machine in very higher manner.
        As this modification has been found successful in improving the safety
 and minimizing the breakdowns, it is planned to implement the same to the
                                  other units.
         Hence it may be concluded that the modification is accurate, reliable,
                        trouble free and easily monitor.
THANK YOU
ANY QUARIES
     ?

More Related Content

What's hot

OBD2 Powertrain Code List (P3000- P3999)
OBD2 Powertrain Code List (P3000- P3999)OBD2 Powertrain Code List (P3000- P3999)
OBD2 Powertrain Code List (P3000- P3999)Tim Miller
 
Vertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZVertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZAndy Chen
 
OBD2 Powertrain Code List (P2500-P2599)
OBD2 Powertrain Code List (P2500-P2599)OBD2 Powertrain Code List (P2500-P2599)
OBD2 Powertrain Code List (P2500-P2599)Tim Miller
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedureAshvani Shukla
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingTahoor Alam Khan
 
Cfbc burner startup sequence
Cfbc burner startup sequenceCfbc burner startup sequence
Cfbc burner startup sequenceAshvani Shukla
 
Ford OBD2 Codes
Ford OBD2 CodesFord OBD2 Codes
Ford OBD2 CodesTim Miller
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Manohar Tatwawadi
 
OBD2 Powertrain Code List (P1000- P2099)
OBD2 Powertrain Code List (P1000- P2099)OBD2 Powertrain Code List (P1000- P2099)
OBD2 Powertrain Code List (P1000- P2099)Tim Miller
 
Subaru OBD2 Codes
Subaru OBD2 CodesSubaru OBD2 Codes
Subaru OBD2 CodesTim Miller
 
Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Ashvani Shukla
 
Innovations - Ability 11.02.14
Innovations - Ability 11.02.14Innovations - Ability 11.02.14
Innovations - Ability 11.02.14Overbury
 

What's hot (20)

Integrated control valve, sensors, actuator, and controller
Integrated control valve, sensors, actuator, and controllerIntegrated control valve, sensors, actuator, and controller
Integrated control valve, sensors, actuator, and controller
 
OBD2 Powertrain Code List (P3000- P3999)
OBD2 Powertrain Code List (P3000- P3999)OBD2 Powertrain Code List (P3000- P3999)
OBD2 Powertrain Code List (P3000- P3999)
 
Breathing Air Purifiers for Commercial and Industrial Use
Breathing Air Purifiers for Commercial and Industrial UseBreathing Air Purifiers for Commercial and Industrial Use
Breathing Air Purifiers for Commercial and Industrial Use
 
Vertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZVertical multistage fire pump catalogue-60HZ
Vertical multistage fire pump catalogue-60HZ
 
OBD2 Powertrain Code List (P2500-P2599)
OBD2 Powertrain Code List (P2500-P2599)OBD2 Powertrain Code List (P2500-P2599)
OBD2 Powertrain Code List (P2500-P2599)
 
Pulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedurePulverized coal fired boiler startup procedure
Pulverized coal fired boiler startup procedure
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & Working
 
Cfbc burner startup sequence
Cfbc burner startup sequenceCfbc burner startup sequence
Cfbc burner startup sequence
 
Ford OBD2 Codes
Ford OBD2 CodesFord OBD2 Codes
Ford OBD2 Codes
 
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
Starting & Recommended Interlocks for AH,ID,FD,PA Fans & BD Valves for 270 MW...
 
Hst ppt
Hst pptHst ppt
Hst ppt
 
Hydrostatic Pressure Liquid Level Transmitter
Hydrostatic Pressure Liquid Level TransmitterHydrostatic Pressure Liquid Level Transmitter
Hydrostatic Pressure Liquid Level Transmitter
 
OBD2 Powertrain Code List (P1000- P2099)
OBD2 Powertrain Code List (P1000- P2099)OBD2 Powertrain Code List (P1000- P2099)
OBD2 Powertrain Code List (P1000- P2099)
 
Subaru OBD2 Codes
Subaru OBD2 CodesSubaru OBD2 Codes
Subaru OBD2 Codes
 
Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1Furnace safegaurd supervisory system logic-1
Furnace safegaurd supervisory system logic-1
 
Innovations - Ability 11.02.14
Innovations - Ability 11.02.14Innovations - Ability 11.02.14
Innovations - Ability 11.02.14
 
Medical gas supply system
Medical gas supply systemMedical gas supply system
Medical gas supply system
 
04 ingestive-cleaning-es9-62-rev-l-pdf
04 ingestive-cleaning-es9-62-rev-l-pdf04 ingestive-cleaning-es9-62-rev-l-pdf
04 ingestive-cleaning-es9-62-rev-l-pdf
 
VW OBD2 Codes
VW OBD2 CodesVW OBD2 Codes
VW OBD2 Codes
 
Dv test rig
Dv test rigDv test rig
Dv test rig
 

Similar to Automation of break generator with PLC

Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6GlobeCore
 
TIDA-01070-Design-Guide
TIDA-01070-Design-GuideTIDA-01070-Design-Guide
TIDA-01070-Design-GuideBrian Dempsey
 
Technical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightTechnical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightAdicomp s.r.l
 
PresentationGGSSTP_Atul
PresentationGGSSTP_AtulPresentationGGSSTP_Atul
PresentationGGSSTP_AtulAtul Kataria
 
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas Daniel Donatelli
 
Uscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOUscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOColinGroup Craiova
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Beeteco
 
Compressor fundamentals
Compressor fundamentalsCompressor fundamentals
Compressor fundamentalsPrem Baboo
 
Esco Orbicult Laboratory Shakers
Esco Orbicult Laboratory ShakersEsco Orbicult Laboratory Shakers
Esco Orbicult Laboratory ShakersEsco Group
 
Perkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEPerkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEAdpower FZCO
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Marlon Torres
 
Globecore transformer oil purification plant with high vacuum cmm 6 d
Globecore transformer oil purification plant with high vacuum cmm  6 dGlobecore transformer oil purification plant with high vacuum cmm  6 d
Globecore transformer oil purification plant with high vacuum cmm 6 dGlobeCore
 
VORTEX ELECTROMAGNETIC FIELD SYSTEM
 VORTEX ELECTROMAGNETIC FIELD SYSTEM  VORTEX ELECTROMAGNETIC FIELD SYSTEM
VORTEX ELECTROMAGNETIC FIELD SYSTEM NadiiaHubar
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13-
 
Standard boiler 500 mwerection manual (boiler auxiliaries)
Standard boiler 500 mwerection manual (boiler auxiliaries)Standard boiler 500 mwerection manual (boiler auxiliaries)
Standard boiler 500 mwerection manual (boiler auxiliaries)Ashutosh Sachan
 
Perkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aePerkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aeAdpower FZCO
 
ATM-1000h - Power Module - Documentation V1.7
ATM-1000h - Power Module - Documentation V1.7ATM-1000h - Power Module - Documentation V1.7
ATM-1000h - Power Module - Documentation V1.7shaukat1607
 

Similar to Automation of break generator with PLC (20)

Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6Globe core oil purification plant SMM 0.6
Globe core oil purification plant SMM 0.6
 
Cosmodyne aspen 1000
Cosmodyne aspen 1000Cosmodyne aspen 1000
Cosmodyne aspen 1000
 
TIDA-01070-Design-Guide
TIDA-01070-Design-GuideTIDA-01070-Design-Guide
TIDA-01070-Design-Guide
 
Technical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) lightTechnical description bvg 2014 (upgrading) (en) light
Technical description bvg 2014 (upgrading) (en) light
 
PresentationGGSSTP_Atul
PresentationGGSSTP_AtulPresentationGGSSTP_Atul
PresentationGGSSTP_Atul
 
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas
Lpg Biogas Biomass Reformer Hydrogen Fuel cell power gas
 
Uscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATOUscatoare cu ciclu frigorifer CECCATO
Uscatoare cu ciclu frigorifer CECCATO
 
Hydraulic flushing rig ppt
Hydraulic flushing rig pptHydraulic flushing rig ppt
Hydraulic flushing rig ppt
 
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)
 
Compressor fundamentals
Compressor fundamentalsCompressor fundamentals
Compressor fundamentals
 
Esco Orbicult Laboratory Shakers
Esco Orbicult Laboratory ShakersEsco Orbicult Laboratory Shakers
Esco Orbicult Laboratory Shakers
 
Perkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAEPerkins UK Generator Specifications Dubai - UAE
Perkins UK Generator Specifications Dubai - UAE
 
Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones Hoja de datos lm 555 y configuraciones
Hoja de datos lm 555 y configuraciones
 
QX1401 VDL(H) spec.
QX1401 VDL(H) spec.QX1401 VDL(H) spec.
QX1401 VDL(H) spec.
 
Globecore transformer oil purification plant with high vacuum cmm 6 d
Globecore transformer oil purification plant with high vacuum cmm  6 dGlobecore transformer oil purification plant with high vacuum cmm  6 d
Globecore transformer oil purification plant with high vacuum cmm 6 d
 
VORTEX ELECTROMAGNETIC FIELD SYSTEM
 VORTEX ELECTROMAGNETIC FIELD SYSTEM  VORTEX ELECTROMAGNETIC FIELD SYSTEM
VORTEX ELECTROMAGNETIC FIELD SYSTEM
 
Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
 
Standard boiler 500 mwerection manual (boiler auxiliaries)
Standard boiler 500 mwerection manual (boiler auxiliaries)Standard boiler 500 mwerection manual (boiler auxiliaries)
Standard boiler 500 mwerection manual (boiler auxiliaries)
 
Perkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.aePerkins uk generators supplier Dubai – Adpower.ae
Perkins uk generators supplier Dubai – Adpower.ae
 
ATM-1000h - Power Module - Documentation V1.7
ATM-1000h - Power Module - Documentation V1.7ATM-1000h - Power Module - Documentation V1.7
ATM-1000h - Power Module - Documentation V1.7
 

Automation of break generator with PLC

  • 1. AUTOMATION OF BREAK GENERATOR Presented by K.JANAKI K.L.SUSHMA PRIYA K.PRASAD B.SANTHAN BHARDWAJ
  • 2. CONTENTS 1.Aim of the project 2.Description of expansion turbine 3.Description of ASP 4.GEFANUC PLC system a) advantages b)disadvantages 5.Input output lists 6.Conclusion
  • 3. AIM OF THE PROJECT To improve the performance of “EXPANSION TURBINE OF ASU - 1” and to provide necessary automation with latest Micro- Processor based PLC logic system to avoid spurious trips. Existing system is relay logic system. It is always giving spurious trips and hampering production. With the newly implemented PLC based system, we are able to give continuous monitoring of all process parameters from CCP DESKTOP monitor, historical trends, improved accuracy, reliability and ensuring safe & continuous running of the expansion turbine
  • 4. DESCRIPTION OF EXPANSION TURBINE •A part of the air is taken at an intermediate point of the exchangers and sent to a Centrifugal Expansion turbine equipped with a Break Generator to provide the necessary refrigeration to make-up the thermal losses of the cold box. PROCESS PARAMETERS Air flow (max.) : 37,500 Nm3/hr Inlet pressure : 6.6 kg/cm2 abs Outlet pressure : 1.45 kg/cm2 abs Inlet temperature : (-) 135 ºC Outlet temperature : (-) 178 ºc Power : 550 KW Model : ETG 360 NS Constructor : ATLAS COPCO
  • 5. TURBINE CHECK LIST 1.Oil level shown on oil gauge glass. 2.Thawing gas valves closed. 3.Nozzle blades closed. 4.Quick-close shutoff valve closed. 5.Temperature of turbine bearings .If temperature of either bearing is less than +15 deg. C, bearings must be warmed by turning on lubricating oil supply. Turbine outlet valve must be closed. If bearing temperature cannot be raised by circulating lubricating oil, turbine must be heated with thawing gas. Oil filter clean and in circuit. 6.Adjust the stroke of nozzle control valve.
  • 6. TURBINE START UP PROCEDURE 1.Turn on sealing gas supply. 2. Switch on control power supply for instruments and controls. 3.Electrical auxiliary oil Pump starts automatically. Turn on cooling water supply for oil cooler. 4.Open turbine outlet valve. 5.Open turbine inlet valve. 6.Open quick-close shutoff valve.
  • 7. 7. Open up nozzle valve until operating speed level is attained and generator cuts automatically. 8.Keep check on bearings temperatures, gap pressure and satisfactory running of complete unit during start-up. 9.Switch off auxiliary oil pump by switch “oil pump off”. 10. After generator has cut in, load turbine by opening up nozzle blades as far as required for given operating conditions. 11.During start-up briefly open drain and instrument lines to vent them, re-closing afterwards.
  • 8. DESCRIPTION OF ASP Air Composition:- Air is mainly a mixture of two gases: Oxygen and Nitrogen in the following percentages. *1/5th Oxygen, namely 20.96%. *4/5th nitrogen, namely 78.11%. Air also contains other components such as the five rare gases, which are found in a constant percentage by volume. Argon (Ar) – 0.93% Neon (Ne) – 0.0015% Helium (He) – 0.0005% Krypton (Kr) – 0.0001% Xenon (Xe) – 0.000008%
  • 9. Some other components are also present in variable quantities such as: *Water vapor (H2O) *Carbon dioxide (CO2 about 0.03%) *Hydro carbons, Acetylene (C2H2) *Ozone (O3)
  • 10. SEPARATION OF AIR COMPONENTS Air components are separated by means of liquid distillation columns, in distillation column. A thorough separation of air cannot be made by means of a single rectification column: 1. The first one is the high pressure column separating the process air into liquid nitrogen and oxygen rich liquid (40% oxygen). 2. The second one is the low pressure column which is used for final separation into pure nitrogen and oxygen.
  • 11. AIR PURIFICATION Air contains some water, carbon dioxide, hydrocarbons and oil if it is compressed by means of lubricated equipment. These components must be removed because water and carbon dioxide when cooled to low temperatures may form a deposit in the pipe work and result in subsequent plugging. Acetylene and oil are also dangerous and may cause explosion when they come into contact with liquid oxygen. Heavier hydrocarbons are removed during cooling. It should be noted that hydrocarbons may be removed when in liquid state.
  • 12. PROCESS DESCRIPTION Air is sucked through air pulse filter which removes the dust particles, then it goes through the inlet guide vane and compressed in four stages. . After first stage compression, the compressed air goes to the first water inlet cooler and then to the second stage suction. . From second stage discharge it goes to second cooler and then to third stage suction. . From third stage discharge it goes to third inter cooler and then to fourth stage suction
  • 13. .From fourth state discharge it goes to after cooler. Discharge pressure after first, second, third and fourth stages are 0.75, 2.0, 3.8, 6.4 Kg/Cm2 respectively. Suction pipe gas temperature of first stage to fourth stage is 40 to 45 deg c. Discharge gas temperature at fourth stage is 90 to 105 deg c. To protect the machine from surges it has been provided with anti-surge valve (ASV).When there is a sudden increase of discharge pressure or decrease of discharge flow through the compressor, the machine goes to an unstable region called surge.
  • 14. INTRODUCTION TO PLC’S The break generator is equipped with pressure gauges, temp Indicators, pressure switches, speed measurement & vibration measurement systems and safety devices. At present all safety interlocks are based on relay logic system. In this proposed automation project the relay logic system is converted into PLC based logic system.
  • 15. PLC’S The Series 90-30 PLC’S are members of the GE Fanuc Series 90™ family of Programmable Logic Controllers (PLC’S). They are easy to install and configure, offer advanced programming features, and are compatible with the Series 90-70 PLC’S. Two Windows-based configuration/programming packages are available for Series 90-30 PLC’S. VersaPro software supports all Series 90-30 CPUs.
  • 16. . The software structure for the 341 and lower Series 90-30 PLC’S uses an architecture that manages memory and execution priority in the 80188 microprocessor. The 35x and 36x series of Series 90-30 PLC’S use an 80386EX microprocessor This operation supports both program execution and basic housekeeping tasks such as diagnostic routines, input/output scanners, and alarm processing. The system software also contains routines to communicate with the programmer.
  • 17. The Series 90-30 Genius Bus Controller (catalog number IC693BEM331) is used to interface a Genius I/O serial bus to a Series 90-30 PLC. The GBC receives and transmits control data of up to 128 bytes for up to 31 devices on the Genius bus. A Genius bus may serve: Genius blocks, which provide interface to a broad range of discrete, analog, and special-purpose field devices. Genius blocks are self-contained modules with advanced diagnostics capabilities and many software-configurable features.
  • 18. Remote Drops, Series 90-70 I/O racks that are interfaced to the bus via Remote I/O Scanner Modules. Each remote drop can include any mix of discrete and analog I/O modules, providing up to 128 bytes of input data and 128 bytes of output data. Hand-held Monitor, which can be used as a portable device or permanently mounted. A HHM provides a convenient operator interface for block setup, data monitoring, and diagnostics. Multiple hosts, for communications using datagram’s and Global Data.
  • 19. ADVANTAGES: By replacing the analog systems with latest microprocessor based Control systems the advantages are 1.Spurious indications will be eliminated. 2.Reliability will be ensured. 3.Production delays will be avoided. 4.Accuracy will be improved. 5.Events will be monitored. 6.Trip analysis becomes easier. 7.Historical trends will be obtained. 8.Maintenance cost will be reduced. 9.Spurious indications will be eliminated. 10.Reliability will be ensured.
  • 20. 11.Production delays will be avoided. 12.Accuracy will be improved. 13.Events will be monitored. 14.Trip analysis becomes easier. 15.Historical trends will be obtained. 16.Maintenance cost will be reduced.
  • 21. DISADVANTAGES: 1.All interlocks are used change over series contacts. So this is very difficult to trace out the abnormalities in the process. 2.All the contacts are taking from the field switches. 3.Control panel and field switches are mounted on the body of equipment. So during running condition switches are malfunctioning due to vibration. 4.Spares are too costly. 5. Problem analysis and troubleshooting takes lot of time and causing production delays. 6.All interlocks are used change over series contacts. So this is very difficult to trace out the abnormalities in the process.
  • 22. 7.All the contacts are taking from the field switches. 8.Control panel and field switches are mounted on the body of equipment. So during running condition switches are malfunctioning due to vibration. 9.Spares are too costly. 10.Problem analysis and troubleshooting takes lot of time and causing production delays.
  • 23. INPUT-OUTPUT PORTS 32 Point Discrete Input Module Power Sources: The module receives power from the Field Processor to r run its own 5-volt logic. An external 24VDC supply is needed to power the input devices. LEDs: Individual LEDs (logic side), visible through the transparent portion of the module top, indicate the on/off status of each input. The PWR LED is on when field and backplane power is present. Host Interface: Intelligent processing for this module is performed by the Bus Interface Unit or elsewhere in the system. This includes configuring features such as input defaults and fault reporting. The module has 16 bits (two bytes) of discrete input data. A Bus Interface Unit is required to provide this input data to the host and/or local processor.
  • 24. Module Operation: A network of resistors and capacitors establishes input thresholds and provides input filtering. Opt isolators provide isolation between the field inputs and the module's logic components. Data from all 16 inputs is placed into a data buffer. 32 Point Discrete Output Module Power Sources: Power for the module itself comes from the power supply in the Bus Interface Unit. An external source of DC power must be provided for the switches that power the loads. LEDs: Individual green LEDs (logic side) indicate the on/off status of each output. The green LEDs remain off when user power is not present, regardless of the state of the outputs. Individual yellow LEDs show the fault status of each output. The green PWR LED is on when field and backplane power are present.
  • 25. Host Interface: Intelligent processing for this module is performed by the Bus Interface Unit or elsewhere in the system. This includes configuring features such as output default and fault reporting. The module has 8 bits (one byte) of discrete output data. A Bus Interface Unit is required to obtain this output data from the host and/or local processor. Module Operation: After checking the Board ID, the Bus Interface Unit sends output data to the module in serial format. During transmission, the module automatically loops this data back to the Bus Interface Unit for verification. Serial to parallel converters convert this data into the parallel format needed by the module. Opto-isolators isolate the module's logic components from field outputs. Power from the external power supply is used to drive the FETs that source current to the loads.
  • 26. CONCLUSION After completion of the “AUTOMATION OF EXPANSION TURBINE OF ASU – 1” the performance of the break generator is found to be improved. Now the operation people are easily able to run the machine without spurious breakdowns. In that context Instrumentation is playing major role in early alarming and minimizing the breakdown of the equipment and ensuring the safety of man / machine in very higher manner. As this modification has been found successful in improving the safety and minimizing the breakdowns, it is planned to implement the same to the other units. Hence it may be concluded that the modification is accurate, reliable, trouble free and easily monitor.