Wind load on pv system
Upcoming SlideShare
Loading in...5
×

Like this? Share it with your network

Share

Wind load on pv system

  • 446 views
Uploaded on

Design example of wind loading on ground photovoltaic system

Design example of wind loading on ground photovoltaic system

  • Full Name Full Name Comment goes here.
    Are you sure you want to
    Your message goes here
    Be the first to comment
    Be the first to like this
No Downloads

Views

Total Views
446
On Slideshare
441
From Embeds
5
Number of Embeds
2

Actions

Shares
Downloads
28
Comments
0
Likes
0

Embeds 5

https://www.linkedin.com 3
http://www.linkedin.com 2

Report content

Flagged as inappropriate Flag as inappropriate
Flag as inappropriate

Select your reason for flagging this presentation as inappropriate.

Cancel
    No notes for slide

Transcript

  • 1. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. WIND LOAD ON SURFACES (WALLS) EC-1-4 Assumptions: Assume that structural factor cscd is equal to 1 (EN1991-1-4,cl.6.0).1. Assume that lack of correlation of wind pressure between the windward and leeward side is2. taken equal to 1 (EN1991-1-4,cl.7.2.2(3)). Building data Type of structure: PHOTOVOLTAIC SYSTEM Total length of strucutre: d 5800mm:= Width of structure: b 2690mm:= Height of structure: h 3400mm:= Spacing frame to frame: ss 2900mm:= No of frames: No_frames 3:= Basic values 110
  • 2. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. Fundamental basic wind velocity (CYS NA EN1991-1-4,fig.1): vb.o 30m s 1- := Season factor (EN1991-1-4, NA 2.4/cl.4.2(2)): cseason 1.0:= Directional factor (EN1991-1-4, NA 2.4/cl.4.2(2)): cdir 1.0:= Basic wind velocity (EN1991-1-4,cl.4.2(2)): vb cdir cseason vb.o 30 m s 1- =:= 1.25kg m 3- := Density of air: Reference mean velocity pressure (EN1991-1-4,cl.4.5(1)): qb vb 2 2  562.5 N m 2- =:= Orography Orography factor (EN1991-1-4,cl.4.3.3(2): co 1.0:= Obstruction height (EN1991-1-4,Annex A.5): have 15m:= Distance to the nearest adjacement building (EN1991-1-4,Annex A.5): x 500m:= Displacement height (EN1991-1-4,Annex A.5): hdis min 0.8 have 0.6h,( ) x 2 haveif min 1.2 have 0.2 x- 0.6 h,( ) 2 have x< 6 have<if 0 x 6 haveif 0 m=:= 210
  • 3. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. Terrain category (EN1991-1-4,table 4.1): Terrain_category "I":= Roughness length,z0 (EN1991-1-4,table 4.1): zo 0.003m Terrain_category "0"=if 0.01m Terrain_category "I"=if 0.05m Terrain_category "II"=if 0.3m Terrain_category "III"=if 1.0m Terrain_category "IV"=if 10 mm=:= Roughness length,zmin (EN1991-1-4,table 4.1): zmin 1m Terrain_category "0"=if 1m Terrain_category "I"=if 2m Terrain_category "II"=if 5m Terrain_category "III"=if 10m Terrain_category "IV"=if 1 10 3  mm=:= Peak wind velocity pressure Reference height (EN1991-4,figure 7.4) ze h 3.4 m=:= Maximum height (EN1991-1-4,cl.4.3.2(1)): zmax 200m:= Factor, z0,II (EN1991-4,table 4.1) z0.II 50mm:= 310
  • 4. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. Terrain factor (EN1991-1-4,cl.4.3.2(1)): kr 0.19 zo z0.II       0.07  0.17=:= Roughness factor (EN1991-1-4,cl.4.3.2(1)): cr kr ln zmin zo        0.782=:= Mean wind velocity (EN1991-1-4,cl.4.3.1(1)): vm cr co vb 23.453 m s 1- =:= Turbulence factor EN1991-1-4,cl.4.4(1)): kI 1.0:= Turbulence intensity EN1991-1-4,cl.4.4(1)): Iv kI co ln zmin zo        0.217=:= Peak velocity pressure EN1991-1-4,cl.4.5(1)):: qp 1 7 Iv+( ) 0.5  vm 2  0.866 kN m 2- =:= Structural factor cscd Assume structural factor is 1 (for buildings with a height less than 15m) (EN1991-1-4,cl.6.2(1)): cs.d 1:= Wind pressure coefficients for canopy roof structure (EN1991-1-4,cl.7.3) There is no blockage beneath the canopy, however the values of cp.net and cf have been taken using the ϕ=0 for minimum values and ϕ=all for maximum values. The overall force coefficient represent the resulting force. The net pressure coefficient represents the maximum local pressure for all wind directions and have been used in the design of roofing elements and fixing. 410
  • 5. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. Table 1: cf values for monopitch canopies (EN1991-1-4,Table 7.6) Wind pressures for modules 30deg Wind suction φ=0 (max.) - Upward acting wind action External pressure coefficient for zone A (EN1991-1-4,Table 7.6): cp.net.A.up.30 3.0-:= Wind pressure for zone A (EN1991-1-4,Eq.5.1) we.A.up.30 qp cp.net.A.up.30 2.599- kN m 2- =:= 510
  • 6. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. External pressure coefficient for zone B (EN1991-1-4,Table 7.6): cp.net.B.up.30 3.8-:= Wind pressure for zone B (EN1991-1-4,Eq.5.1) we.B.up.30 qp cp.net.B.up.30 3.292- kN m 2- =:= Wind suction φ=0 (max.) - Downward acting wind action External pressure coefficient for zone A (EN1991-1-4,Table 7.6): cp.net.A.do.30 2.2:= Wind pressure for zone A (EN1991-1-4,Eq.5.1) we.A.do.30 qp cp.net.A.do.30 1.906 kN m 2- =:= External pressure coefficient for zone B (EN1991-1-4,Table 7.6): cp.net.B.do.30 3.2:= Wind pressure for zone B (EN1991-1-4,Eq.5.1) we.B.do.30 qp cp.net.B.do.30 2.772 kN m 2- =:= Figure 2: Location of the centre of force for monopitch canopies (EN1991-1-4,Figure 7.16) Effective area between two supports Aref.mid b ss 7.801 m 2 =:= Effective area of edges supports Aref.edg Aref.mid 2 3.9 m 2 =:= 610
  • 7. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. Wind loads for modules 30deg Overall factor coefficient for upward acting wind action (EN1991-1-4,Table 7.6): cf.up.30 1.8-:= Overall factor coefficient for upward acting wind action (EN1991-1-4,Table 7.6): cf.do.30 1.2:= Downward acting wind force at edge frame (EN1991-1-4,Eq.5.3) Fw.ed.do.30 cs.d cf.do.30 qp Aref.edg 4.055 kN=:= Downward acting wind force at middle frame (EN1991-1-4,Eq.5.3) Fw.mid.do.30 cs.d cf.do.30 qp Aref.mid 8.11 kN=:= Upward acting wind force at edge frame (EN1991-1-4,Eq.5.3) Fw.ed.up.30 cs.d cf.up.30 qp Aref.edg 6.082- kN=:= Upward acting wind force at middle frame (EN1991-1-4,Eq.5.3) Fw.mid.up.30 cs.d cf.up.30 qp Aref.mid 12.164- kN=:= No. 4 Load cases for wind force on structure for inclination of 30deg (edge members) b 4 0.672 m= Fw.ed.do.30 4.055 kN= Fw.ed.do.30 4.055 kN= b 4 0.672 m= Fw.ed.up.30 6.082- kN= Fw.ed.up.30 6.082- kN= b 4 0.672 m= b 4 0.672 m= 710
  • 8. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. No. 4 Load cases for wind force on structure for inclination of 30deg (middle members) b 4 0.672 m= Fw.mid.do.30 8.11 kN= Fw.mid.do.30 8.11 kN= b 4 0.672 m= Fw.mid.up.30 12.164- kN= Fw.mid.up.30 12.164- kN= b 4 0.672 m= b 4 0.672 m= Frictional force on structure (EN1991-1-4,cl.7.5) Frictional force should be considered to the roof canopy structures - see EN1991-1-4,cl.7.3.(7) Surface type (EN1991-1-4,Table 7.10): Surface_type "Very rough":= Frictional coefficient (EN1991-1-4,Table 7.10): cfr 0.01 Surface_type "Smooth"=if 0.02 Surface_type "Rough"=if 0.04 Surface_type "Very rough"=if 0.04=:= Reference area: Afr 2 ss b 15.602 m 2 =:= Frictional force per frame (EN1991-1-4,Eq.5.7): Ffr cfr qp Afr ss  0.186 kN m 1- =:= 810
  • 9. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. 910
  • 10. WIND LOAD CALCULATION BASE ON EN1991-4PV SYSTEM REV.A Calculated by:V.N. Reviewed by: V.N. 1010