Steam jet chilling plants
The environment-friendly alternative amongst chilling plants
Kälteanlagen-EN-141119.indd 2 19.11.2014 09:54:41
Steam jet chilling plants
Körting steam jet chilling plants
can be ideally utilised whenever large
chilling capacities have to be easily
realised. Preferably, unused exhaust,
residual or excess steam is available.
Körting steam jet chilling plants
provide:
• 	an environment-friendly operation by 	
	 means of water as refrigerant
• 	high operational safety
• 	minimum maintenance
• 	an easy assembly, as well as a good 	
	 handling since the plants basically 	
	 do not require rotating and moving 	
	components
Kälteanlagen-EN-141119.indd 3 19.11.2014 09:54:50
28 MW steam jet chilling plant in Egypt,
cooling of 1 600 m3
/h from 35 °C to 20 °C
24 MW steam jet chilling plant Petro China/Sichuan refinery,
cooling of 2 300 m3
/h from 29 °C to 20 °C
About 1.4 MW steam jet chilling plant in Stendal,
cooling of about 72 m3
/h from 25 °C to 8 °C
Usually, conventional steam jet chilling plants
are equipped with electrically driven mechanical
compressors. Such plants show obvious dis-
advantages as they generate additional energy
costs, increased maintenance of rotating com-
ponents and therefore higher investments for
safe operation.
Steam jet chilling plants by Körting provide an
environment-friendly alternative at reasonable
costs compared with traditional chilling plants.
If sufficient motive steam is available, the ad-
vantages of the Körting plants are convincing.
Körting chilling plants are particularly efficient
when processes provide excess or residual
steam. This means high efficiency for the entire
process, and, at the same time, good chilling
performance at high availability and low need of
maintenance.
The required cooling water volume is larger than
with mechanical compression chilling circuits,
but it is comparable to absorption plants.
Applications
Kälteanlagen-EN-141119.indd 4 19.11.2014 09:54:54
chilled water inlet
chilled water outlet
cooling water inlet
cooling water outlet
venting
condenserevaporator steam jet vacuum ejector
motive steam
2 up to 15 bar abs. (sat.)
14 °C
8 °C
32 °C
42 °C
Schematic diagram: steam jet chilling plant
Körting steam jet chilling plants take advantage
of the principle of flash evaporation. The liquid
to be chilled is being passed through a flash
evaporator. The pressure in the evaporator is
below the steam pressure of the liquid.
As a result of the flash evaporation process,
part of the liquid evaporates (flash steam);
evaporation heat is deducted from the heat
capacity of the liquid. This causes the liquid to
cool down to the boiling point of the respective
evaporation pressure (vacuum).
The application is only limited by the freezing
point of the liquid to be cooled.
The resulting flash steam will be sucked
off by a Körting steam jet vacuum ejector,
then compressed and finally condensed in a
downstream condenser. The respective pres-
sure level is defined by the temperature of the
used cooling medium.
This condenser has to be vented until atmos-
pheric pressure is reached. For this process
Körting steam jet vacuum ejectors or liquid ring
pumps have proven to be ideal.
Function
Kälteanlagen-EN-141119.indd 5 19.11.2014 09:54:57
Körting steam jet vacuum ejector
Advantages
•	 basically no rotating and moving components
•	 simple and good handling, even with large volume flows and chilling performances
•	 environment-friendly as no special refrigerants are required (water serves as refrigerant)
•	 summertime peak load can be covered by the difference in demand of heating steam 	
	 between summer and winter
•	 high operational safety
•	 low maintenance
•	 simple set-up and easy handling
•	 long service life
•	 corrosive media can be dealt with flexibility (use of various successfully tested materials 	
	 from plant building)
•	 electrical energy feed is not necessary (except for transporting chilled water and cooling 	
	 water)
•	 Körting has many years of experience in the development, design, manufacturing, com-	
	 missioning and maintenance of steam jet chilling plants
Options
Direct contact condensers are common in use
(mixing condensers). Evaporated cooling liquids,
cooling water and motive steam are mixed
during operation (see figure on the left).
By means of surface condensers this kind of
mixing can be avoided. Multi-stage evaporators
and condensers reduce the steam and cooling
water consumption.
Kälteanlagen-EN-141119.indd 6 19.11.2014 09:54:59
Requirements
As with all technical processes the following applies:
Sometimes less is more – the optimum design saves
costs!
Increased requirements demand high performance.
Alongside the plant size and the actual cooling performance
Körting considers the following for individual design in order
to reach high energy efficiency:
• 	The lower the required chilled water temperature has to 	
		 be, the more motive steam is needed.
• 	The required motive steam flow decreases with an in-		
		 creasing motive steam pressure.
• 	Multi-stage steam jet chilling plants reduce operational 		
		 costs and the demand for steam/cooling water con-		
		 siderably. This means that higher investment costs pay 		
		 off quickly.
•	 The higher the cooling water temperature at the con-		
		 denser inlet, the more motive steam is required.
•	 The more cooling water is available, which means, the 		
		 less the cooling water heats up, the lower the required 		
		 motive steam flow.
•	 In contrast to the countercurrent operation a cocurrent 		
		 operation requires slightly more motive steam at a similar 	
		 cooling water flow. However, it permits the space-saving 	
		 1-tower design.
What else has to be taken into account:
•	 How long runs the plant? During the whole year or during 	
		 a certain season only?
•	 Are there any variations regarding the cooling water inlet 	
		 temperature (why, when and how strong)?
•	 Are refrigerants and cooling fluids allowed to mix?
•	 Are there any requirements regarding corrosion?
•	 Which build up concept is the most favourable one?
•	 Shall the build up be horizontal or vertical?
•	 Does a steel construction already exist? Which load can 	
		 it bear? Is a steel construction required at all?
Kälteanlagen-EN-141119.indd 7 19.11.2014 09:55:01
1-stage
2-stage
3-stage
Motive steam requirement [t/h]
Motivesteampressure[barabs.]
12
10
8
6
4
2
0
10 15 20 25 30
Motive steam requirement in relation to number of plant stages
(7 MW cooling performance, cooling water heat up from 25 °C to 30 °C,
chilled water cool down from 12 °C to 6 °C)
25 °C up to 30 °C
27,5 °C up to 32,5 °C
30 °C up to 35 °C
25 °C up to 35 °C
Motive steam requirement [t/h]
Motivesteampressure[barabs.]
12
10
8
6
4
2
0
10 15 20 25 30 35
Motive steam requirement in relation to cooling water heat up
using the example of a 3-stage plant
(7 MW cooling performance, chilled water cool down from 12 °C to 6 °C)
Motive steam requirement [t/h]
Motivesteampressure[barabs.]
12
10
8
6
4
2
0
8 10 12 14 16 18 20 22 24
12 °C to 6 °C
16 °C to 10 °C
Motive steam requirement in relation to chilled water cool down
using the example of a 3-stage steam jet chilling plant
(7 MW cooling performance, cooling water heat up from 25°C to 30 °C
Kälteanlagen-EN-141119.indd 8 19.11.2014 09:55:06
direct condensation
with venting stages
1-tower design, 3-stage
cooling water inlet
venting
group
evaporator
motive steam
cooler/
condenser
chilled water
return
cooling
water outlet
chilled water
feed line
Designs
There are different designs of steam jet chilling plants:
•	 free- and self-supporting constructions with own steel construction (no separate steel
	 construction)
•	 constructions fitted in existing steel constructions
•	 tower design
•	 bridge design
•	 cocurrent or countercurrent operation
•	 direct condensation (with Körting mixing condensers)
•	 indirect condensation (with Körting surface condensers)
Kälteanlagen-EN-141119.indd 9 19.11.2014 09:55:08
Bridge design with separate steel construction,
option of a 2-tower design, 4-stage, cocurrent plant
Bridge design, self-supporting (without separate steel construction),
2-tower design, 3-stage, countercurrent plant
indirect condensation
with venting stages
motive steam
chilled water
return
cooler/condenser
stage 2
cooler/condenser
stage 1
chilled water
feed line
cooling water
inlet
cooling water
outlet
seal tank
seal tank
evaporator
to atmosphere
venting group
stage 1
stage 2
condensate
condensate
condensate
Kälteanlagen-EN-141119.indd 10 19.11.2014 09:55:10
A realised project
Successful operation of a Körting multi-stage
steam jet chilling plant in China
The self-supporting construction without
secondary steel construction as well
as the bridge design of the steam jet
vacuum ejectors are just some of the
individual characteristics of this unique
plant.
With a maximum constructional height
of almost 44 m and a maximum plant
diameter of about 6 m, this chilling plant
is almost as tall as a Saturn One rocket.
Körting Hannover AG has planned,
manufactured and commissioned this
steam jet chilling plant in cooperation with
their Chinese end costumer, Petro China/
Sichuan refinery.
Daring to build this plant and taking the
effort of everyone involved was worth it.
After almost one year in operation the
plant owner is highly satisfied with this
newly developed design of this steam jet
chilling plant and its performance.
Despite its size this steam jet chilling
plant with steam jet vacuum ejectors in
bridge design of up to 20 m in length
allows an installation without secondary
steel construction. Eventually, this saves
costs and required space.
The evaporator tower and a downstream
condenser in combination with the
Körting steam jet vacuum ejectors are
the core of the plant. The cooled water
is needed to cool down various petro-
chemical processes in the newly erected
Sichuan refinery.
After the steam jet chilling plant in Egypt
(28 MW) delivered by Körting as well, the
new plant is the second largest in the
world.
Kälteanlagen-EN-141119.indd 11 19.11.2014 09:55:12
Technical data:
cooling performance	 24 MW
chilled water flow	 2 300 t/h
cooling	 29 °C to 20 °C
Kälteanlagen-EN-141119.indd 12 19.11.2014 09:55:15
260-Kälteanlagen-EN-141119Körting Hannover AG
Badenstedter Straße 56
30453 Hannover
Germany
Tel.: +49 511 2129-259
Fax: +49 511 2129-223
st@koerting.de
www.koerting.de
Kälteanlagen-EN-141119.indd 1 19.11.2014 09:54:38

More Related Content

What's hot

ice plant factory report
ice plant factory reportice plant factory report
ice plant factory reportkifayat ullah
 
Kettle reboilers
Kettle reboilersKettle reboilers
Kettle reboilersAtif Khan
 
Design of thermosyphon reboiler
Design of thermosyphon reboilerDesign of thermosyphon reboiler
Design of thermosyphon reboilerHarshad Vaghela
 
1 reboilers types
1 reboilers types1 reboilers types
1 reboilers typeslesvit
 
Thermal Engineering - II
Thermal Engineering - IIThermal Engineering - II
Thermal Engineering - IIGOBINATHS18
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boilerAshvani Shukla
 
Cooling towers in thermal power plants
Cooling towers in thermal power plantsCooling towers in thermal power plants
Cooling towers in thermal power plantsManohar Tatwawadi
 
Thermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementThermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementAnkur Gaikwad
 
Niagara WSAC application solutions brochure - final - 0815
Niagara WSAC application solutions brochure - final - 0815Niagara WSAC application solutions brochure - final - 0815
Niagara WSAC application solutions brochure - final - 0815Joseph Merzlak
 
Construction of 500 MW Steam Boiler
Construction of 500 MW Steam BoilerConstruction of 500 MW Steam Boiler
Construction of 500 MW Steam BoilerVaibhav Paydelwar
 
Heat recovery steam generator
Heat recovery steam generatorHeat recovery steam generator
Heat recovery steam generatorJuno Joy
 
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantWater steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantHareesh VS
 
Boiler, Steam Trapes, Insulation and Steam Distribution System
Boiler, Steam Trapes,  Insulation and Steam Distribution SystemBoiler, Steam Trapes,  Insulation and Steam Distribution System
Boiler, Steam Trapes, Insulation and Steam Distribution SystemWasiullah Khan
 

What's hot (20)

High Pressure Boilers
High Pressure BoilersHigh Pressure Boilers
High Pressure Boilers
 
ice plant factory report
ice plant factory reportice plant factory report
ice plant factory report
 
Kettle reboilers
Kettle reboilersKettle reboilers
Kettle reboilers
 
Design of thermosyphon reboiler
Design of thermosyphon reboilerDesign of thermosyphon reboiler
Design of thermosyphon reboiler
 
1 reboilers types
1 reboilers types1 reboilers types
1 reboilers types
 
Superhtr
SuperhtrSuperhtr
Superhtr
 
Cooling tower
Cooling towerCooling tower
Cooling tower
 
Thermal Engineering - II
Thermal Engineering - IIThermal Engineering - II
Thermal Engineering - II
 
660 mw supercritical boiler
660 mw supercritical boiler660 mw supercritical boiler
660 mw supercritical boiler
 
Ice plant 1
Ice plant 1Ice plant 1
Ice plant 1
 
Boiler Superheater Design Modification
Boiler Superheater Design ModificationBoiler Superheater Design Modification
Boiler Superheater Design Modification
 
Cooling towers in thermal power plants
Cooling towers in thermal power plantsCooling towers in thermal power plants
Cooling towers in thermal power plants
 
Thermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency ImprovementThermal Power Plant Boiler Efficiency Improvement
Thermal Power Plant Boiler Efficiency Improvement
 
Niagara WSAC application solutions brochure - final - 0815
Niagara WSAC application solutions brochure - final - 0815Niagara WSAC application solutions brochure - final - 0815
Niagara WSAC application solutions brochure - final - 0815
 
Construction of 500 MW Steam Boiler
Construction of 500 MW Steam BoilerConstruction of 500 MW Steam Boiler
Construction of 500 MW Steam Boiler
 
Hot Water Vapour Absorption Chiller
Hot Water Vapour Absorption ChillerHot Water Vapour Absorption Chiller
Hot Water Vapour Absorption Chiller
 
Steam generator part 3
Steam generator part 3Steam generator part 3
Steam generator part 3
 
Heat recovery steam generator
Heat recovery steam generatorHeat recovery steam generator
Heat recovery steam generator
 
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power PlantWater steam Circuit in Supercritical Boiler for 660MW Power Plant
Water steam Circuit in Supercritical Boiler for 660MW Power Plant
 
Boiler, Steam Trapes, Insulation and Steam Distribution System
Boiler, Steam Trapes,  Insulation and Steam Distribution SystemBoiler, Steam Trapes,  Insulation and Steam Distribution System
Boiler, Steam Trapes, Insulation and Steam Distribution System
 

Similar to Chiller Plant-EN - Catalogue

Effects of Changing Different Components in a Compression Refrigeration System
Effects of Changing Different Components in a Compression Refrigeration SystemEffects of Changing Different Components in a Compression Refrigeration System
Effects of Changing Different Components in a Compression Refrigeration SystemHashim Hasnain Hadi
 
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...Juma Yousef J. Saleh جمعة يوسف جمعة صالح
 
Chilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptChilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptEstevanhuertas
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system pptvikramdangi
 
Applied Thermal Engineering
Applied Thermal EngineeringApplied Thermal Engineering
Applied Thermal EngineeringNitin Shekapure
 
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power Plant
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power PlantStudy on Induced Draft Cooling Tower Performance Analysis in Captive Power Plant
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power PlantIRJET Journal
 
A Brief Introduction to Boilers
A Brief Introduction to BoilersA Brief Introduction to Boilers
A Brief Introduction to BoilersSATYAKAM MOHAPATRA
 
Energy Conservation Opportunities in Cooling Tower.pdf
Energy Conservation Opportunities in Cooling Tower.pdfEnergy Conservation Opportunities in Cooling Tower.pdf
Energy Conservation Opportunities in Cooling Tower.pdfNITIN ASNANI
 
B op eqsyschillers
B op eqsyschillersB op eqsyschillers
B op eqsyschillersAnup Kumar
 
Air source heat pump Brochure-BLUEWAY
Air source heat pump Brochure-BLUEWAYAir source heat pump Brochure-BLUEWAY
Air source heat pump Brochure-BLUEWAYRoger Luo
 
Design and Fabrication of Vapour Absorption Refrigeration System [Libr-H20]
Design and Fabrication of Vapour Absorption Refrigeration  System [Libr-H20]Design and Fabrication of Vapour Absorption Refrigeration  System [Libr-H20]
Design and Fabrication of Vapour Absorption Refrigeration System [Libr-H20]IJMER
 
Final report on spent solution in hydro
Final report on spent solution in hydroFinal report on spent solution in hydro
Final report on spent solution in hydroprateekj765
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsSHIVAJI CHOUDHURY
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...IRJET Journal
 
BLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureBLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureRoger Luo
 
Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08Er Ramgarhia
 
BS5 - Lecture 2 HVAC Systems
BS5 - Lecture 2 HVAC SystemsBS5 - Lecture 2 HVAC Systems
BS5 - Lecture 2 HVAC SystemsSiddharth Khanna
 

Similar to Chiller Plant-EN - Catalogue (20)

Effects of Changing Different Components in a Compression Refrigeration System
Effects of Changing Different Components in a Compression Refrigeration SystemEffects of Changing Different Components in a Compression Refrigeration System
Effects of Changing Different Components in a Compression Refrigeration System
 
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...
Module (s 203) fundamentals of cooling tower أساسيات ومبدأ عمل أبراج التبريد-...
 
training report
training reporttraining report
training report
 
STEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEMSTEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEM
 
Chilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.pptChilled Water Systems Total Cost of Ownership.ppt
Chilled Water Systems Total Cost of Ownership.ppt
 
Cooling applications of solar system ppt
Cooling applications of solar system pptCooling applications of solar system ppt
Cooling applications of solar system ppt
 
Applied Thermal Engineering
Applied Thermal EngineeringApplied Thermal Engineering
Applied Thermal Engineering
 
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power Plant
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power PlantStudy on Induced Draft Cooling Tower Performance Analysis in Captive Power Plant
Study on Induced Draft Cooling Tower Performance Analysis in Captive Power Plant
 
A Brief Introduction to Boilers
A Brief Introduction to BoilersA Brief Introduction to Boilers
A Brief Introduction to Boilers
 
Energy Conservation Opportunities in Cooling Tower.pdf
Energy Conservation Opportunities in Cooling Tower.pdfEnergy Conservation Opportunities in Cooling Tower.pdf
Energy Conservation Opportunities in Cooling Tower.pdf
 
B op eqsyschillers
B op eqsyschillersB op eqsyschillers
B op eqsyschillers
 
Air source heat pump Brochure-BLUEWAY
Air source heat pump Brochure-BLUEWAYAir source heat pump Brochure-BLUEWAY
Air source heat pump Brochure-BLUEWAY
 
Design and Fabrication of Vapour Absorption Refrigeration System [Libr-H20]
Design and Fabrication of Vapour Absorption Refrigeration  System [Libr-H20]Design and Fabrication of Vapour Absorption Refrigeration  System [Libr-H20]
Design and Fabrication of Vapour Absorption Refrigeration System [Libr-H20]
 
Final report on spent solution in hydro
Final report on spent solution in hydroFinal report on spent solution in hydro
Final report on spent solution in hydro
 
Steam Condensers
Steam CondensersSteam Condensers
Steam Condensers
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
"Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject..."Replacement of vapor compression system of domestic refrigerator by an eject...
"Replacement of vapor compression system of domestic refrigerator by an eject...
 
BLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller BrochureBLUEWAY Air cooled water chiller Brochure
BLUEWAY Air cooled water chiller Brochure
 
Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08Adiabatic cooling tower v3 08.08
Adiabatic cooling tower v3 08.08
 
BS5 - Lecture 2 HVAC Systems
BS5 - Lecture 2 HVAC SystemsBS5 - Lecture 2 HVAC Systems
BS5 - Lecture 2 HVAC Systems
 

More from Tomas Eriksson

Venturi Scrubber - Dedusting
Venturi Scrubber - DedustingVenturi Scrubber - Dedusting
Venturi Scrubber - DedustingTomas Eriksson
 
Multistage-steam-jet-vacuum-ejectors
Multistage-steam-jet-vacuum-ejectorsMultistage-steam-jet-vacuum-ejectors
Multistage-steam-jet-vacuum-ejectorsTomas Eriksson
 
Alkaline Cloosed Loop vacuum systems
Alkaline Cloosed Loop vacuum systemsAlkaline Cloosed Loop vacuum systems
Alkaline Cloosed Loop vacuum systemsTomas Eriksson
 
Ice Condensation vacuum systems
Ice Condensation vacuum systemsIce Condensation vacuum systems
Ice Condensation vacuum systemsTomas Eriksson
 
Textile - Caustic Recovery-email
Textile - Caustic Recovery-emailTextile - Caustic Recovery-email
Textile - Caustic Recovery-emailTomas Eriksson
 
Water and Waste Water Treatment - EN - 140716 - webreduced
Water and Waste Water Treatment - EN - 140716 - webreducedWater and Waste Water Treatment - EN - 140716 - webreduced
Water and Waste Water Treatment - EN - 140716 - webreducedTomas Eriksson
 
Tank Mixing Systems - EN - webreduced
Tank Mixing Systems - EN - webreducedTank Mixing Systems - EN - webreduced
Tank Mixing Systems - EN - webreducedTomas Eriksson
 
Koerting - Institutional
Koerting - InstitutionalKoerting - Institutional
Koerting - InstitutionalTomas Eriksson
 

More from Tomas Eriksson (9)

Venturi Scrubber - Dedusting
Venturi Scrubber - DedustingVenturi Scrubber - Dedusting
Venturi Scrubber - Dedusting
 
Multistage-steam-jet-vacuum-ejectors
Multistage-steam-jet-vacuum-ejectorsMultistage-steam-jet-vacuum-ejectors
Multistage-steam-jet-vacuum-ejectors
 
Alkaline Cloosed Loop vacuum systems
Alkaline Cloosed Loop vacuum systemsAlkaline Cloosed Loop vacuum systems
Alkaline Cloosed Loop vacuum systems
 
Ice Condensation vacuum systems
Ice Condensation vacuum systemsIce Condensation vacuum systems
Ice Condensation vacuum systems
 
Shipbuilding-web
Shipbuilding-webShipbuilding-web
Shipbuilding-web
 
Textile - Caustic Recovery-email
Textile - Caustic Recovery-emailTextile - Caustic Recovery-email
Textile - Caustic Recovery-email
 
Water and Waste Water Treatment - EN - 140716 - webreduced
Water and Waste Water Treatment - EN - 140716 - webreducedWater and Waste Water Treatment - EN - 140716 - webreduced
Water and Waste Water Treatment - EN - 140716 - webreduced
 
Tank Mixing Systems - EN - webreduced
Tank Mixing Systems - EN - webreducedTank Mixing Systems - EN - webreduced
Tank Mixing Systems - EN - webreduced
 
Koerting - Institutional
Koerting - InstitutionalKoerting - Institutional
Koerting - Institutional
 

Chiller Plant-EN - Catalogue

  • 1. 260-Kälteanlagen-EN-141119 Körting Steam jet chilling plants The environment-friendly alternative amongst chilling plants Kälteanlagen-EN-141119.indd 2 19.11.2014 09:54:41
  • 2. Steam jet chilling plants Körting steam jet chilling plants can be ideally utilised whenever large chilling capacities have to be easily realised. Preferably, unused exhaust, residual or excess steam is available. Körting steam jet chilling plants provide: • an environment-friendly operation by means of water as refrigerant • high operational safety • minimum maintenance • an easy assembly, as well as a good handling since the plants basically do not require rotating and moving components Kälteanlagen-EN-141119.indd 3 19.11.2014 09:54:50
  • 3. 28 MW steam jet chilling plant in Egypt, cooling of 1 600 m3 /h from 35 °C to 20 °C 24 MW steam jet chilling plant Petro China/Sichuan refinery, cooling of 2 300 m3 /h from 29 °C to 20 °C About 1.4 MW steam jet chilling plant in Stendal, cooling of about 72 m3 /h from 25 °C to 8 °C Usually, conventional steam jet chilling plants are equipped with electrically driven mechanical compressors. Such plants show obvious dis- advantages as they generate additional energy costs, increased maintenance of rotating com- ponents and therefore higher investments for safe operation. Steam jet chilling plants by Körting provide an environment-friendly alternative at reasonable costs compared with traditional chilling plants. If sufficient motive steam is available, the ad- vantages of the Körting plants are convincing. Körting chilling plants are particularly efficient when processes provide excess or residual steam. This means high efficiency for the entire process, and, at the same time, good chilling performance at high availability and low need of maintenance. The required cooling water volume is larger than with mechanical compression chilling circuits, but it is comparable to absorption plants. Applications Kälteanlagen-EN-141119.indd 4 19.11.2014 09:54:54
  • 4. chilled water inlet chilled water outlet cooling water inlet cooling water outlet venting condenserevaporator steam jet vacuum ejector motive steam 2 up to 15 bar abs. (sat.) 14 °C 8 °C 32 °C 42 °C Schematic diagram: steam jet chilling plant Körting steam jet chilling plants take advantage of the principle of flash evaporation. The liquid to be chilled is being passed through a flash evaporator. The pressure in the evaporator is below the steam pressure of the liquid. As a result of the flash evaporation process, part of the liquid evaporates (flash steam); evaporation heat is deducted from the heat capacity of the liquid. This causes the liquid to cool down to the boiling point of the respective evaporation pressure (vacuum). The application is only limited by the freezing point of the liquid to be cooled. The resulting flash steam will be sucked off by a Körting steam jet vacuum ejector, then compressed and finally condensed in a downstream condenser. The respective pres- sure level is defined by the temperature of the used cooling medium. This condenser has to be vented until atmos- pheric pressure is reached. For this process Körting steam jet vacuum ejectors or liquid ring pumps have proven to be ideal. Function Kälteanlagen-EN-141119.indd 5 19.11.2014 09:54:57
  • 5. Körting steam jet vacuum ejector Advantages • basically no rotating and moving components • simple and good handling, even with large volume flows and chilling performances • environment-friendly as no special refrigerants are required (water serves as refrigerant) • summertime peak load can be covered by the difference in demand of heating steam between summer and winter • high operational safety • low maintenance • simple set-up and easy handling • long service life • corrosive media can be dealt with flexibility (use of various successfully tested materials from plant building) • electrical energy feed is not necessary (except for transporting chilled water and cooling water) • Körting has many years of experience in the development, design, manufacturing, com- missioning and maintenance of steam jet chilling plants Options Direct contact condensers are common in use (mixing condensers). Evaporated cooling liquids, cooling water and motive steam are mixed during operation (see figure on the left). By means of surface condensers this kind of mixing can be avoided. Multi-stage evaporators and condensers reduce the steam and cooling water consumption. Kälteanlagen-EN-141119.indd 6 19.11.2014 09:54:59
  • 6. Requirements As with all technical processes the following applies: Sometimes less is more – the optimum design saves costs! Increased requirements demand high performance. Alongside the plant size and the actual cooling performance Körting considers the following for individual design in order to reach high energy efficiency: • The lower the required chilled water temperature has to be, the more motive steam is needed. • The required motive steam flow decreases with an in- creasing motive steam pressure. • Multi-stage steam jet chilling plants reduce operational costs and the demand for steam/cooling water con- siderably. This means that higher investment costs pay off quickly. • The higher the cooling water temperature at the con- denser inlet, the more motive steam is required. • The more cooling water is available, which means, the less the cooling water heats up, the lower the required motive steam flow. • In contrast to the countercurrent operation a cocurrent operation requires slightly more motive steam at a similar cooling water flow. However, it permits the space-saving 1-tower design. What else has to be taken into account: • How long runs the plant? During the whole year or during a certain season only? • Are there any variations regarding the cooling water inlet temperature (why, when and how strong)? • Are refrigerants and cooling fluids allowed to mix? • Are there any requirements regarding corrosion? • Which build up concept is the most favourable one? • Shall the build up be horizontal or vertical? • Does a steel construction already exist? Which load can it bear? Is a steel construction required at all? Kälteanlagen-EN-141119.indd 7 19.11.2014 09:55:01
  • 7. 1-stage 2-stage 3-stage Motive steam requirement [t/h] Motivesteampressure[barabs.] 12 10 8 6 4 2 0 10 15 20 25 30 Motive steam requirement in relation to number of plant stages (7 MW cooling performance, cooling water heat up from 25 °C to 30 °C, chilled water cool down from 12 °C to 6 °C) 25 °C up to 30 °C 27,5 °C up to 32,5 °C 30 °C up to 35 °C 25 °C up to 35 °C Motive steam requirement [t/h] Motivesteampressure[barabs.] 12 10 8 6 4 2 0 10 15 20 25 30 35 Motive steam requirement in relation to cooling water heat up using the example of a 3-stage plant (7 MW cooling performance, chilled water cool down from 12 °C to 6 °C) Motive steam requirement [t/h] Motivesteampressure[barabs.] 12 10 8 6 4 2 0 8 10 12 14 16 18 20 22 24 12 °C to 6 °C 16 °C to 10 °C Motive steam requirement in relation to chilled water cool down using the example of a 3-stage steam jet chilling plant (7 MW cooling performance, cooling water heat up from 25°C to 30 °C Kälteanlagen-EN-141119.indd 8 19.11.2014 09:55:06
  • 8. direct condensation with venting stages 1-tower design, 3-stage cooling water inlet venting group evaporator motive steam cooler/ condenser chilled water return cooling water outlet chilled water feed line Designs There are different designs of steam jet chilling plants: • free- and self-supporting constructions with own steel construction (no separate steel construction) • constructions fitted in existing steel constructions • tower design • bridge design • cocurrent or countercurrent operation • direct condensation (with Körting mixing condensers) • indirect condensation (with Körting surface condensers) Kälteanlagen-EN-141119.indd 9 19.11.2014 09:55:08
  • 9. Bridge design with separate steel construction, option of a 2-tower design, 4-stage, cocurrent plant Bridge design, self-supporting (without separate steel construction), 2-tower design, 3-stage, countercurrent plant indirect condensation with venting stages motive steam chilled water return cooler/condenser stage 2 cooler/condenser stage 1 chilled water feed line cooling water inlet cooling water outlet seal tank seal tank evaporator to atmosphere venting group stage 1 stage 2 condensate condensate condensate Kälteanlagen-EN-141119.indd 10 19.11.2014 09:55:10
  • 10. A realised project Successful operation of a Körting multi-stage steam jet chilling plant in China The self-supporting construction without secondary steel construction as well as the bridge design of the steam jet vacuum ejectors are just some of the individual characteristics of this unique plant. With a maximum constructional height of almost 44 m and a maximum plant diameter of about 6 m, this chilling plant is almost as tall as a Saturn One rocket. Körting Hannover AG has planned, manufactured and commissioned this steam jet chilling plant in cooperation with their Chinese end costumer, Petro China/ Sichuan refinery. Daring to build this plant and taking the effort of everyone involved was worth it. After almost one year in operation the plant owner is highly satisfied with this newly developed design of this steam jet chilling plant and its performance. Despite its size this steam jet chilling plant with steam jet vacuum ejectors in bridge design of up to 20 m in length allows an installation without secondary steel construction. Eventually, this saves costs and required space. The evaporator tower and a downstream condenser in combination with the Körting steam jet vacuum ejectors are the core of the plant. The cooled water is needed to cool down various petro- chemical processes in the newly erected Sichuan refinery. After the steam jet chilling plant in Egypt (28 MW) delivered by Körting as well, the new plant is the second largest in the world. Kälteanlagen-EN-141119.indd 11 19.11.2014 09:55:12
  • 11. Technical data: cooling performance 24 MW chilled water flow 2 300 t/h cooling 29 °C to 20 °C Kälteanlagen-EN-141119.indd 12 19.11.2014 09:55:15
  • 12. 260-Kälteanlagen-EN-141119Körting Hannover AG Badenstedter Straße 56 30453 Hannover Germany Tel.: +49 511 2129-259 Fax: +49 511 2129-223 st@koerting.de www.koerting.de Kälteanlagen-EN-141119.indd 1 19.11.2014 09:54:38