How Row-based Data Center
Cooling Works
Revision 0
White Paper 208
Row-based data center cooling is normally regarded as
a “cold air supply” architecture that uses row-based
coolers. However, row-based cooling is actually a “hot
air capture” architecture that neutralizes hot air from IT
equipment before it has a chance to mix with the
surrounding air in the room. This paper discusses
common misconceptions about row-based cooling,
explains how row-based cooling removes hot air, and
describes key design attributes that maximize the
effectiveness of this approach.
Executive summary
by Schneider Electric White Papers are now part of the Schneider Electric
white paper library produced by Schneider Electric’s Data Center Science Center
DCSC@Schneider-Electric.com
by Paul Lin and Victor Avelar
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 2
Close-coupled cooling, row-oriented architecture, and in-row cooling are some common
names used to describe row-based cooling in data centers. Throughout this paper the term
row cooler1
will be used to describe this architecture. In addition, the term “pod” will be used
to describe how row coolers are typically deployed (see side bar for definition).
Although row-based cooling technology has been around for about 10 years, there is still
confusion surrounding how this type of cooling works. Specifically there are three common
misconceptions about how it works and how it is deployed:
• Misconception 1: Row coolers require turning vanes: It is commonly believed that
row coolers require turning vanes to direct cold air to the front of the racks. In fact,
some data center designers, operators, and manufactures design turning vanes at the
outlet of row-based cooling equipment to try to blow cold air directly into the racks.
• Misconception 2: Row coolers are needed in every row: It is commonly believed
that every row in the data center requires row cooler(s). It is counter intuitive to think
that you can cool an entire pod if all row coolers are in one row and none in the oppos-
ing row.
• Misconception 3: Row coolers can’t cool loads outside of their pod: It is common-
ly believed that row coolers can only cool the loads inside the pod they are located in.
Similarly, it is often thought that extra row-based cooling capacity in one pod cannot
help cool another pod.
This paper uses scientific evidence and the core principle of hot air capture to explain why
these are misconceptions. The paper then describes three key row-based cooling design
attributes that maximize hot air capture. For more information on fundamentals of row-based
cooling, see White Paper 130, Choosing between Room, Row, and Rack-based Cooling for
Data Centers.
The goal of any data center cooling system is to remove the heat added to the air by the IT
equipment. A metric for measuring the effectiveness of how hot IT exhaust air is captured by
cooling equipment (or how cold air is supplied to IT inlets) is called the capture index2
.
Capture index is based solely on the airflow patterns associated with the supply of cold air to,
or the removal of hot air from a rack. The capture index is typically a rack-by-rack metric and
has values between zero and 100%; higher values generally imply good cooling performance
and scalability of a cooling architecture.
The hot air capture index is the fraction of hot air exhausted by IT equipment that is captured
directly by the row coolers within the same pod as the IT equipment. This is the principle
metric that quantifies the effectiveness of row-based cooling. This is illustrated in Figure 1
where 78% of the hot IT exhaust air is captured by the cooler. Figure 2 shows a CFD
simulation result of temperature contour of a data center with row coolers.
1
Note that the principles in this paper are described with the assumption that the row coolers are floor-
mounted as opposed to ceiling-mounted.
2
J.W. VanGilder, S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric,
Published in ASHRAE Transactions 2007, Volume 113, Part 1.
Introduction
The principle
of hot air
capture
What is a data center
“pod”?
A data center pod is a cluster of
IT cabinets combined with
power and cooling infrastructure
that is deployed as a unit.
Rooms are planned in advance
for a number of pods, but the
pods may be separately
deployed or upgraded over
time. Pods typically assembled
on-site in a room to a standard
design, but may be partially or
extensively pre-manufactured.
In its most common form, a pod
is a pair of rows of cabinets
sharing a hot aisle.
Pod-based design is a
recommended best-practice for
larger data centers.
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 3
Source: J.W. VanGilder, S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric
A useful application of hot air capture index is optimizing the placement of racks and cooling
units in a pod. The design goal is to ensure that all exhaust air is captured by the cooling
units so that there is no net heating of the room. In this case, rack-by-rack capture indices
explicitly show how much of each rack’s airflow is captured so that the appropriate design
changes may be implemented until an acceptable solution is found. The hot air capture index
design target should generally be at least 90%, which means the pod layout is effective. The
following design practices can help attain or exceed this value.
• Use blanking panels and brush strips – IT exhaust air can escape the hot aisle
through open unused “U” positions in IT racks and through open areas around cable
penetrations at the top and bottom of the rack. Installing blanking panels in open “U”
positions and brush strips around cable penetrations is very effective at increasing the
hot air capture index. For more information on airflow management with blanking pan-
els, see White Paper 44, Improving Rack Cooling Performance Using Airflow Manage-
ment Blanking Panels.
• Optimize row cooler placement – Row coolers should be placed in between IT racks
and generally not at the end of a row in order to maximize hot air capture. For uniform
rack loading, the coolers should be distributed evenly along the length of the hot aisle.
For non-uniform rack loading, coolers should be clustered closer to the higher loads.
• Use side air distribution units – Many types of switches and routers employ side-to-
side airflow. This airflow configuration is generally incompatible with typical front-to-
back airflow of IT enclosures. Side air distribution units allow switch and router enclo-
sures to be placed side by side and still maintain proper airflow thereby consuming less
Figure 2
CFD simulation illustrating
hot air capture (center aisle
represents hot aisle, and
blue objects represents row
coolers)
Figure 1
Illustration of hot air capture
index
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 4
floor space. See White Paper 50, Cooling Solutions for Rack Equipment with Side-to-
Side Airflow.
• Avoid fan trays – Fan trays or roof fans employed in racks can actually degrade air
management as the induced airflow patterns are incompatible with the front-to-back IT
airflow.
• Use deeper IT racks – Over the last 10 years, IT equipment has trended toward deep-
er form factors. Using shallow-depth racks (i.e. 900mm / 35in) with this IT equipment
can constrict the movement of hot exhaust air out from the back of the rack. Deeper
racks allow more room for cabling which decreases resistance to airflow.
• Use air containment – The further row coolers are from IT racks, the more difficult it is
to prevent IT exhaust air from recirculating back into IT equipment inlets. Containing
the hot aisle with row coolers can improve cooling system efficiency, especially at den-
sities below 3kW/rack. For more information on airflow management and containment
please read these two white papers: White Paper 135, Impact of Hot and Cold Aisle
Containment on Data Center Temperature and Efficiency; White Paper 153, Imple-
menting Hot and Cold Air Containment in Existing Data Centers.
The three misconceptions mentioned in the introduction are indicative of a lack of under-
standing in how row coolers contribute to the concept of hot air capture. This section will first
describe three key design attributes of row coolers, which will then be used as the basis for
debunking each misconception.
Design attributes of row coolers
Row coolers capture hot IT exhaust air and neutralize it before it has a chance to mix with the
surrounding air in the room or recirculate to the front of the IT rack. Capturing 100% of hot
air can improve energy efficiency and eliminate hot spots. There are three key design
attributes that help row coolers capture and neutralize hot air:
• Back-to-front airflow
• Rack-based footprint
• Variable cooling capacity devices
Back-to-front airflow
Row coolers are designed with back-to-front airflow using small fans distributed across the
height of the cooler. Since the rear of the row cooler is in the hot aisle, the fans are able to
collect the hot IT exhaust air directly and uniformly (top to bottom) from the hot aisle as
shown in Figure 3. It has been shown, based on computational fluid dynamic (CFD) analysis
and performance testing, that the hot air capture index is generally highest for IT racks
closest to the row cooler. Conversely, the hot air capture index decreases for IT racks further
away from the row cooler. This relationship brings about the benefit of the second design
attribute, rack-based footprint.
Debunking the
misconceptions
Figure 3
Row cooler showing verti-
cally-aligned fans and back-
to-front airflow
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 5
Rack-based footprint
Row coolers are designed with a footprint similar to an IT rack (full or half rack width). This
design attribute allows you to distribute row coolers throughout a pod of IT racks. The
maximum distance between any row cooler and IT equipment exhaust is normally within 3
meters (10 feet). The implication of this distributed cooling layout is that the hot air capture
index is improved for the entire pod. When the hot exhaust air of one IT rack is beyond the
“reach” of a distant row cooler, a closer row cooler will capture the majority of the hot exhaust
air in that part of the pod.
If all of the hot exhaust air in a pod is captured by distributed coolers in that pod (i.e. 100%
hot air capture), then by definition there can be no hot spots at the intakes of IT equipment.
Figure 4 shows an example layout of distributed row coolers. The quantity and locations of
row coolers are determined according to rack densities and the extent of containment.
Variable cooling capacity devices
Row coolers are designed with EC fans which can adjust fan speed to change airflow and
output cooling capacity. Traditional CRAHs typically only control airflow to maintain raised
floor static pressure, and is not related to the IT load. This design attribute allows row
coolers to balance the cooling capacity with the heat load by sensing the inlet temperature of
nearby racks or the IT room.
Correcting misconception 1: Row coolers require turning vanes
If one doesn’t understand the premise of hot air capture, it’s easy to conclude that turning
vanes are required to blow cold air in the direction of the IT equipment. However, both
design attributes described above show that turning vanes are not required. If 100% of
the hot IT exhaust air is captured and cooled, (before it has a chance to mix with surrounding
air in the room), the remaining space in the room becomes a cold air supply plenum3
.
Therefore, it doesn’t matter where the cold air (from the row cooler) goes; it just matters that
the hot air (from the IT equipment) is being captured and neutralized.
Turning vanes are used by some manufacturers to direct
cold air into the adjacent racks, which indicates they
don’t understand hot air capture. The use of turning
vanes not only increases the capital cost and increases
the width of the cold aisle, but also results in airflow
issues. The airflow leaving the turning vanes is at a
higher velocity, and perpendicular to, the airflow of the
adjacent IT rack. The high velocity jet flow creates
regions of low pressure in front of the IT rack, interfering
with rack airflow. (This is known as Bernoulli’s principle,
3
Even if the initial room air temperature is higher than the row cooler supply air temperature, over time,
the room reaches steady state and will be approximately the same temperature as the row cooler
supply air. This assumes relatively tight room construction with minimal infiltration.
Figure 4
Illustration of row coolers
distributed across a row of
racks
CRAC
CRAC
CRAC
Rack Rack Rack Rack
REAR
FRONT
WALL or ROW to help form “hot aisle”
Hot aisle
CFD simulation of airflow
leaving the turning vanes
(Air velocity vectors show)
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 6
the same principle that allows wings to lift an airplane.) Unlike the gentle and fairly uniform
“sucking” of hot IT exhaust in the hot aisle, the strong jets blanketing the rack inlets creates
highly variable conditions from rack to rack. (Jet flow is characterized by localized pressure
and velocity changes.) Note that turning vanes also have a significant pressure drop
requiring more fan power.
Correcting misconception 2: Row coolers are needed in every row
Many believe that row coolers can only cool the racks which are located in the same row as
the coolers. Both design attributes described above show that, with a high hot air capture
index, it doesn’t matter if all the row coolers are on one side of a two-row pod (or any
placement combination).
CFD modeling and actual installations show it is possible for row coolers in a single row to
cool racks in both rows as illustrated in Figure 5. The percentage values on each rack
represent the hot air capture index. Note in the figure, all the IT inlets are exposed to the
blue color which is neutralized air, and the red color variation in the middle is the hot aisle.
Correcting misconception 3: Row coolers can’t cool loads outside
their pod
This misconception has been communicated in other ways including:
• Row coolers are for spot cooling pods only
• Row coolers can’t cool racks in another pod
• Row coolers can’t cool a large room
• Row coolers can’t cool tape storage units on the perimeter of my data center
• N+1 cooling redundancy with row cooling means that you need a redundant cooling
unit in every pod
An important fact to understand about this misconception is that the hot air capture index
measures the percentage of a rack’s hot exhaust air that is captured directly by row cooler(s)
in the same pod as the rack. By definition, if 100% of a rack’s hot air were to make its way
back to a row cooler far outside its pod, its hot air capture index would be 0%.
Therefore, the most predictable way to cool stand-alone ancillary IT gear, such as storage
arrays, is to place a row cooler next to the gear, assuring a high hot air capture index. In
essence, this creates a miniature pod with up to 100% hot air capture. This is analogous to
placing a perforated tile in front of the stand-alone gear, in a raised floor cooling architecture.
Figure 5
Example CFD analysis with
all row coolers in one row
3D view looking at the top of
the racks
Average 5kW/rack with no
cooling redundancy or
containment
99% 98% 95% 93% 99% 100% 100% 93% 91% 95% 98%
100% 100% 99% 100% 100% 99% 98% 100% 96%C C C C C
Hot Aisle
Supply air direction of row coolers
C
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 7
The main difference is that a perforated tile operates on the premise of cold air capture which
in this case is limited by how much airflow (and kW cooling capacity) is provided as dis-
cussed in WP121, Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center.
What if the stand-alone IT gear doesn’t have a row cooler (i.e. in its pod)? How would this
gear be cooled in a row-based cooling architecture? The answer is tied to the “rack-based
footprint” and “variable cooling capacity devices” design attributes of row coolers. The rack-
based footprint allows coolers to be distributed across the entire data center which creates a
close-coupled cooling effect with all heat loads. The variable cooling capacity devices over-
supply cold air to the cold aisle after sensing an increased room temperature. Containing the
hot aisle with row coolers can also improve hot air capture, especially at densities below
3kW/rack. Will containment have a negative impact on cooling stand-alone IT gear? The
easiest way to illustrate this is by comparing two identical data center layouts each with 65
racks, 235kW of IT load, two stand-alone IT devices, with and without containment.
Figure 6A shows the results of a CFD analysis with 14 row coolers distributed evenly
throughout the data center. The density for the 20 wide racks is 5kW/rack and the 43 narrow
racks are 3kW/rack. The two ancillary racks in the upper right-hand corner represent stand-
alone IT gear. The hot air capture index value (with the unit of percentage) is shown on each
rack. Both the 5kW stand-alone and 1kW stand-alone devices have an average inlet air
temperature of 22˚C (71.6˚F). Figure 6B shows the results of a CFD analysis of the same
data center except with hot aisle containment to illustrate its effect on hot air capture and inlet
air temperatures of the stand-alone IT devices. Most of the racks have 100% hot air capture
index. Both stand-alone IT devices have an average inlet air temperature of 21˚C (69.8˚F).
Figure 6A
Example CFD analysis with
distributed row coolers
3D view looking at the top of
the racks
235kW total load
65 total racks
Wide racks = 5kW/rack
Narrow racks = 3 kW/rack
No cooling redundancy or
containment
5kW stand-
alone device
1kW stand-
alone device
Figure 6B
Example CFD analysis with
centralized row coolers
3D view looking at the top of
the racks
235kW total load
65 total racks
Wide racks = 5kW/rack
Narrow racks = 3 kW/rack
No cooling redundancy but
with containment
5kW stand-
alone device
1kW stand-
alone device
99 100 99 98
99
100 100 100 100 100 100 100 100
100 100 100 100 100 100 100 100 100 100 100
59 65 89 100 76 76 94 85 97 100 100 100 97
66 68 73 79 67 63 97 92 81 90 97 100
99 100 100 98 97 82 80
9193971001009999
C C
CCC
C C
C C C
C C
100 100 100 100 100 100 100 100 100 100 100 100C C C C
C100 100 100 100 100 100 100 100 100 100 100 100
99 99 99 100 100 100 100 100 100 100 99 99 99
99 99 99 99 100 100 100 100 100 100100 100 100
100 100 100 100 100 100 100
100 100 100 100 100 100 100
C C
C C
C C
C C
C C
C
Hot Aisle
Hot Aisle Hot Aisle
Hot Aisle
Hot Aisle Hot Aisle
0 0
0 0
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 8
The figures above help to visualize the effect of row coolers on hot air capture index values
and cooling stand-alone IT device. As row coolers are variable capacity devices that are
capable of over-supplying cold air to the cold aisle. When the system is in balance, the
supply temperature from the cooler is equal to the IT inlet temperature. When ancillary
equipment (i.e. stand-alone devices) is initially added outside of the pod, the temperature of
the overall room environment increases due to air mixing. Nearby row-based cooling units
sense this increase and respond by increasing cooling capacity thereby neutralizing the hot
air. This increased cooling capacity is achieved by increased air flow (row coolers increase
fan speed) and or lower supply air temperature (row cooler increase chilled water valve flow).
These adjustments occur initially but remain unchanged once the data center reaches steady
state.
The steps describing how the row-based coolers “pick up the ancillary load” are the same
even when containment is used. In either case we expect the ancillary equipment to operate
at higher temperatures than the row-based racks, because it is not directly coupled to row
coolers in their own pod. The further away stand-alone IT gear is from row coolers, the
higher their inlet air temperature will be. Should you be concerned about the elevated
ancillary equipment temperature? Often times IT equipment can tolerate ASHRAE’s recom-
mended maximum temperature of 27˚C (80.6˚F). If this is not acceptable, it may be appropri-
ate to place row cooler close to the ancillary equipment rack. For more information on
cooling loads outside of a pod, see White Paper 139, Cooling Entire Data Centers Using Only
Row Cooling and White Paper 134, Deploying High-Density Pods in a Low-Density Data
Center.
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 9
Row-based cooling was designed with a focus on capturing hot exhaust air from IT equip-
ment in a pod. The higher the hot air capture index values, the less hot air recirculation that
occurs, which decreases temperature variations across racks (such as hot spots). It doesn’t
matter where the cold air goes; it matters where the hot air comes from. Row-based cooling
units can also help to cool ancillary equipment or racks outside of their pod but hot air
capture index is not used as a performance metric in this case. Instead row coolers use a
close-coupled cooling process described in this paper. Understanding these principles helps
to explain the three misconceptions described in this paper and provides a foundation for
effective deployment of row-based cooling.
Conclusion
Paul Lin is a Senior Research Analyst at Schneider Electric's Data Center Science Center.
He is responsible for data center design and operation research, and consults with clients on
risk assessment and design practices to optimize the availability and efficiency of their data
center environment. Before joining Schneider Electric, Paul worked as the R&D Project
Leader in LG Electronics for several years. He is now designated as a “Data Center Certified
Associate”, an internationally recognized validation of the knowledge and skills required for a
data center professional. He is also a registered HVAC professional engineer. Paul holds a
master’s degree in mechanical engineering from Jilin University with a background in HVAC
and Thermodynamic Engineering.
Victor Avelar is the Director of Schneider Electric’s Data Center Science Center. He is
responsible for data center design and operations research, and consults with clients on risk
assessment and design practices to optimize the availability and efficiency of their data
center environments. Victor holds a bachelor’s degree in mechanical engineering from
Rensselaer Polytechnic Institute and an MBA from Babson College. He is a member of
AFCOM and the American Society for Quality.
About the author
How Row-based Data Center Cooling Works
Schneider Electric – Data Center Science Center Rev 0 10
Choosing between Room, Row, and Rack-based Cooling for Data Centers
White Paper 130
Improving Rack Cooling Performance Using Airflow Management Blanking Panel
White Paper 44
Cooling Solutions for Rack Equipment with Side-to-Side Airflow
White Paper 50
Impact of Hot and Cold Aisle Containment on Data Center Temperature and
Efficiency
White Paper 135
Implementing Hot and Cold Aisle Containment in Existing Data Centers
White Paper 153
Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center
White Paper 121
Cooling Entire Data Centers Using Only Row Cooling
White Paper 139
Deploying High-Density Pods in a Low-Density Data Center
White Paper 134
Browse all
white papers
whitepapers.apc.com
tools.apc.com
Browse all
TradeOff Tools™
©2014SchneiderElectric.Allrightsreserved.
For feedback and comments about the content of this white paper:
Data Center Science Center
dcsc@schneider-electric.com
If you are a customer and have questions specific to your data center project:
Contact your Schneider Electric representative at
www.apc.com/support/contact/index.cfm
Contact us
Resources

More Related Content

What's hot

Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroommarlisaclark
 
Lowering operating costs through cooling system design
Lowering operating costs through cooling system designLowering operating costs through cooling system design
Lowering operating costs through cooling system designAFCOM
 
Impact Of High Density Colo Hot Aisles on IT Personnel Work Conditions
Impact Of High Density Colo Hot Aisles on IT Personnel Work ConditionsImpact Of High Density Colo Hot Aisles on IT Personnel Work Conditions
Impact Of High Density Colo Hot Aisles on IT Personnel Work ConditionsScott_Blake
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
Tia 942 Data Center Standards
Tia 942 Data Center StandardsTia 942 Data Center Standards
Tia 942 Data Center StandardsSri Chalasani
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slideLivin Jose
 
Datacenter101
Datacenter101Datacenter101
Datacenter101tarundua
 
Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub IRJET Journal
 
Net Ops Data Center Architecture Diagram 06
Net Ops Data Center Architecture Diagram 06Net Ops Data Center Architecture Diagram 06
Net Ops Data Center Architecture Diagram 06jeffqw
 
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...Schneider Electric
 
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT EnvironmentsWP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT Environmentszain kirmani
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationScicomm
 
Data center power availability provisioning
Data center power availability provisioningData center power availability provisioning
Data center power availability provisioningLivin Jose
 
Project Report On Data Center Management
Project Report On Data Center ManagementProject Report On Data Center Management
Project Report On Data Center ManagementDipak Bora
 

What's hot (20)

Data Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroomData Center Cooling Design - Datacenter-serverroom
Data Center Cooling Design - Datacenter-serverroom
 
Lowering operating costs through cooling system design
Lowering operating costs through cooling system designLowering operating costs through cooling system design
Lowering operating costs through cooling system design
 
Impact Of High Density Colo Hot Aisles on IT Personnel Work Conditions
Impact Of High Density Colo Hot Aisles on IT Personnel Work ConditionsImpact Of High Density Colo Hot Aisles on IT Personnel Work Conditions
Impact Of High Density Colo Hot Aisles on IT Personnel Work Conditions
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Tia 942 Data Center Standards
Tia 942 Data Center StandardsTia 942 Data Center Standards
Tia 942 Data Center Standards
 
Data center cooling infrastructure slide
Data center cooling infrastructure slideData center cooling infrastructure slide
Data center cooling infrastructure slide
 
project report on DATACENTER
project report on DATACENTERproject report on DATACENTER
project report on DATACENTER
 
Datacenter101
Datacenter101Datacenter101
Datacenter101
 
Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub
 
Data center m&e
Data center  m&eData center  m&e
Data center m&e
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 
Net Ops Data Center Architecture Diagram 06
Net Ops Data Center Architecture Diagram 06Net Ops Data Center Architecture Diagram 06
Net Ops Data Center Architecture Diagram 06
 
Ashrae thermal guidelines svlg 2015 (1)
Ashrae thermal guidelines  svlg 2015 (1)Ashrae thermal guidelines  svlg 2015 (1)
Ashrae thermal guidelines svlg 2015 (1)
 
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...
Virtualization and Cloud Computing: Optimized Power, Cooling, and Management ...
 
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT EnvironmentsWP-59 The Different Types of Air Conditioning Equipment for IT Environments
WP-59 The Different Types of Air Conditioning Equipment for IT Environments
 
Dcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentationDcd 2012 liquid cooling presentation
Dcd 2012 liquid cooling presentation
 
Data center power availability provisioning
Data center power availability provisioningData center power availability provisioning
Data center power availability provisioning
 
RESNET: HVAC Presentation
RESNET: HVAC PresentationRESNET: HVAC Presentation
RESNET: HVAC Presentation
 
Project Report On Data Center Management
Project Report On Data Center ManagementProject Report On Data Center Management
Project Report On Data Center Management
 

Similar to Row based cooling whitepaper

Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosureerdinc klima
 
white_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwhite_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwberring
 
Energy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemEnergy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemTantish QS, UTM
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling reportommuruga ps
 
IT cooling for Data Center
IT cooling for Data Center IT cooling for Data Center
IT cooling for Data Center Henry Soong
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Raptor Power Systems
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreUpsite Technologies
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environmentmixalisg
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case studySona Rawat
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centresColt UK
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutionspeperoca
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingUpsite Technologies
 

Similar to Row based cooling whitepaper (20)

Datacenters
DatacentersDatacenters
Datacenters
 
Final paper
Final paperFinal paper
Final paper
 
Selecting air conditioners for enclosure
Selecting air conditioners for enclosureSelecting air conditioners for enclosure
Selecting air conditioners for enclosure
 
white_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwhite_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdf
 
Tcc cooling
Tcc coolingTcc cooling
Tcc cooling
 
Green computing
Green computingGreen computing
Green computing
 
Energy Efficient Air Conditioning System
Energy Efficient Air Conditioning SystemEnergy Efficient Air Conditioning System
Energy Efficient Air Conditioning System
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling report
 
IT cooling for Data Center
IT cooling for Data Center IT cooling for Data Center
IT cooling for Data Center
 
Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers Thermal Management of Edge Data Centers
Thermal Management of Edge Data Centers
 
What's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & MoreWhat's Next in Cooling: Capacity, Containment, & More
What's Next in Cooling: Capacity, Containment, & More
 
25985 (1).pdf
25985 (1).pdf25985 (1).pdf
25985 (1).pdf
 
Data center cooling
Data center coolingData center cooling
Data center cooling
 
HVAC for Data Centers
HVAC for Data CentersHVAC for Data Centers
HVAC for Data Centers
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environment
 
Air Conditioning case study
Air Conditioning case studyAir Conditioning case study
Air Conditioning case study
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
 
Project on HVACR
Project on HVACRProject on HVACR
Project on HVACR
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutions
 
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center CoolingCooling Optimization 101: A Beginner's Guide to Data Center Cooling
Cooling Optimization 101: A Beginner's Guide to Data Center Cooling
 

More from Schneider Electric

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsSchneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsSchneider Electric
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service ProvidersSchneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingSchneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSchneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingSchneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingSchneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesSchneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTSchneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingSchneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingSchneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingSchneider Electric
 

More from Schneider Electric (20)

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 

Row based cooling whitepaper

  • 1. How Row-based Data Center Cooling Works Revision 0 White Paper 208 Row-based data center cooling is normally regarded as a “cold air supply” architecture that uses row-based coolers. However, row-based cooling is actually a “hot air capture” architecture that neutralizes hot air from IT equipment before it has a chance to mix with the surrounding air in the room. This paper discusses common misconceptions about row-based cooling, explains how row-based cooling removes hot air, and describes key design attributes that maximize the effectiveness of this approach. Executive summary by Schneider Electric White Papers are now part of the Schneider Electric white paper library produced by Schneider Electric’s Data Center Science Center DCSC@Schneider-Electric.com by Paul Lin and Victor Avelar
  • 2. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 2 Close-coupled cooling, row-oriented architecture, and in-row cooling are some common names used to describe row-based cooling in data centers. Throughout this paper the term row cooler1 will be used to describe this architecture. In addition, the term “pod” will be used to describe how row coolers are typically deployed (see side bar for definition). Although row-based cooling technology has been around for about 10 years, there is still confusion surrounding how this type of cooling works. Specifically there are three common misconceptions about how it works and how it is deployed: • Misconception 1: Row coolers require turning vanes: It is commonly believed that row coolers require turning vanes to direct cold air to the front of the racks. In fact, some data center designers, operators, and manufactures design turning vanes at the outlet of row-based cooling equipment to try to blow cold air directly into the racks. • Misconception 2: Row coolers are needed in every row: It is commonly believed that every row in the data center requires row cooler(s). It is counter intuitive to think that you can cool an entire pod if all row coolers are in one row and none in the oppos- ing row. • Misconception 3: Row coolers can’t cool loads outside of their pod: It is common- ly believed that row coolers can only cool the loads inside the pod they are located in. Similarly, it is often thought that extra row-based cooling capacity in one pod cannot help cool another pod. This paper uses scientific evidence and the core principle of hot air capture to explain why these are misconceptions. The paper then describes three key row-based cooling design attributes that maximize hot air capture. For more information on fundamentals of row-based cooling, see White Paper 130, Choosing between Room, Row, and Rack-based Cooling for Data Centers. The goal of any data center cooling system is to remove the heat added to the air by the IT equipment. A metric for measuring the effectiveness of how hot IT exhaust air is captured by cooling equipment (or how cold air is supplied to IT inlets) is called the capture index2 . Capture index is based solely on the airflow patterns associated with the supply of cold air to, or the removal of hot air from a rack. The capture index is typically a rack-by-rack metric and has values between zero and 100%; higher values generally imply good cooling performance and scalability of a cooling architecture. The hot air capture index is the fraction of hot air exhausted by IT equipment that is captured directly by the row coolers within the same pod as the IT equipment. This is the principle metric that quantifies the effectiveness of row-based cooling. This is illustrated in Figure 1 where 78% of the hot IT exhaust air is captured by the cooler. Figure 2 shows a CFD simulation result of temperature contour of a data center with row coolers. 1 Note that the principles in this paper are described with the assumption that the row coolers are floor- mounted as opposed to ceiling-mounted. 2 J.W. VanGilder, S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric, Published in ASHRAE Transactions 2007, Volume 113, Part 1. Introduction The principle of hot air capture What is a data center “pod”? A data center pod is a cluster of IT cabinets combined with power and cooling infrastructure that is deployed as a unit. Rooms are planned in advance for a number of pods, but the pods may be separately deployed or upgraded over time. Pods typically assembled on-site in a room to a standard design, but may be partially or extensively pre-manufactured. In its most common form, a pod is a pair of rows of cabinets sharing a hot aisle. Pod-based design is a recommended best-practice for larger data centers.
  • 3. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 3 Source: J.W. VanGilder, S.K. Shrivastava, Capture Index: An Airflow-Based Rack Cooling Performance Metric A useful application of hot air capture index is optimizing the placement of racks and cooling units in a pod. The design goal is to ensure that all exhaust air is captured by the cooling units so that there is no net heating of the room. In this case, rack-by-rack capture indices explicitly show how much of each rack’s airflow is captured so that the appropriate design changes may be implemented until an acceptable solution is found. The hot air capture index design target should generally be at least 90%, which means the pod layout is effective. The following design practices can help attain or exceed this value. • Use blanking panels and brush strips – IT exhaust air can escape the hot aisle through open unused “U” positions in IT racks and through open areas around cable penetrations at the top and bottom of the rack. Installing blanking panels in open “U” positions and brush strips around cable penetrations is very effective at increasing the hot air capture index. For more information on airflow management with blanking pan- els, see White Paper 44, Improving Rack Cooling Performance Using Airflow Manage- ment Blanking Panels. • Optimize row cooler placement – Row coolers should be placed in between IT racks and generally not at the end of a row in order to maximize hot air capture. For uniform rack loading, the coolers should be distributed evenly along the length of the hot aisle. For non-uniform rack loading, coolers should be clustered closer to the higher loads. • Use side air distribution units – Many types of switches and routers employ side-to- side airflow. This airflow configuration is generally incompatible with typical front-to- back airflow of IT enclosures. Side air distribution units allow switch and router enclo- sures to be placed side by side and still maintain proper airflow thereby consuming less Figure 2 CFD simulation illustrating hot air capture (center aisle represents hot aisle, and blue objects represents row coolers) Figure 1 Illustration of hot air capture index
  • 4. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 4 floor space. See White Paper 50, Cooling Solutions for Rack Equipment with Side-to- Side Airflow. • Avoid fan trays – Fan trays or roof fans employed in racks can actually degrade air management as the induced airflow patterns are incompatible with the front-to-back IT airflow. • Use deeper IT racks – Over the last 10 years, IT equipment has trended toward deep- er form factors. Using shallow-depth racks (i.e. 900mm / 35in) with this IT equipment can constrict the movement of hot exhaust air out from the back of the rack. Deeper racks allow more room for cabling which decreases resistance to airflow. • Use air containment – The further row coolers are from IT racks, the more difficult it is to prevent IT exhaust air from recirculating back into IT equipment inlets. Containing the hot aisle with row coolers can improve cooling system efficiency, especially at den- sities below 3kW/rack. For more information on airflow management and containment please read these two white papers: White Paper 135, Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency; White Paper 153, Imple- menting Hot and Cold Air Containment in Existing Data Centers. The three misconceptions mentioned in the introduction are indicative of a lack of under- standing in how row coolers contribute to the concept of hot air capture. This section will first describe three key design attributes of row coolers, which will then be used as the basis for debunking each misconception. Design attributes of row coolers Row coolers capture hot IT exhaust air and neutralize it before it has a chance to mix with the surrounding air in the room or recirculate to the front of the IT rack. Capturing 100% of hot air can improve energy efficiency and eliminate hot spots. There are three key design attributes that help row coolers capture and neutralize hot air: • Back-to-front airflow • Rack-based footprint • Variable cooling capacity devices Back-to-front airflow Row coolers are designed with back-to-front airflow using small fans distributed across the height of the cooler. Since the rear of the row cooler is in the hot aisle, the fans are able to collect the hot IT exhaust air directly and uniformly (top to bottom) from the hot aisle as shown in Figure 3. It has been shown, based on computational fluid dynamic (CFD) analysis and performance testing, that the hot air capture index is generally highest for IT racks closest to the row cooler. Conversely, the hot air capture index decreases for IT racks further away from the row cooler. This relationship brings about the benefit of the second design attribute, rack-based footprint. Debunking the misconceptions Figure 3 Row cooler showing verti- cally-aligned fans and back- to-front airflow
  • 5. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 5 Rack-based footprint Row coolers are designed with a footprint similar to an IT rack (full or half rack width). This design attribute allows you to distribute row coolers throughout a pod of IT racks. The maximum distance between any row cooler and IT equipment exhaust is normally within 3 meters (10 feet). The implication of this distributed cooling layout is that the hot air capture index is improved for the entire pod. When the hot exhaust air of one IT rack is beyond the “reach” of a distant row cooler, a closer row cooler will capture the majority of the hot exhaust air in that part of the pod. If all of the hot exhaust air in a pod is captured by distributed coolers in that pod (i.e. 100% hot air capture), then by definition there can be no hot spots at the intakes of IT equipment. Figure 4 shows an example layout of distributed row coolers. The quantity and locations of row coolers are determined according to rack densities and the extent of containment. Variable cooling capacity devices Row coolers are designed with EC fans which can adjust fan speed to change airflow and output cooling capacity. Traditional CRAHs typically only control airflow to maintain raised floor static pressure, and is not related to the IT load. This design attribute allows row coolers to balance the cooling capacity with the heat load by sensing the inlet temperature of nearby racks or the IT room. Correcting misconception 1: Row coolers require turning vanes If one doesn’t understand the premise of hot air capture, it’s easy to conclude that turning vanes are required to blow cold air in the direction of the IT equipment. However, both design attributes described above show that turning vanes are not required. If 100% of the hot IT exhaust air is captured and cooled, (before it has a chance to mix with surrounding air in the room), the remaining space in the room becomes a cold air supply plenum3 . Therefore, it doesn’t matter where the cold air (from the row cooler) goes; it just matters that the hot air (from the IT equipment) is being captured and neutralized. Turning vanes are used by some manufacturers to direct cold air into the adjacent racks, which indicates they don’t understand hot air capture. The use of turning vanes not only increases the capital cost and increases the width of the cold aisle, but also results in airflow issues. The airflow leaving the turning vanes is at a higher velocity, and perpendicular to, the airflow of the adjacent IT rack. The high velocity jet flow creates regions of low pressure in front of the IT rack, interfering with rack airflow. (This is known as Bernoulli’s principle, 3 Even if the initial room air temperature is higher than the row cooler supply air temperature, over time, the room reaches steady state and will be approximately the same temperature as the row cooler supply air. This assumes relatively tight room construction with minimal infiltration. Figure 4 Illustration of row coolers distributed across a row of racks CRAC CRAC CRAC Rack Rack Rack Rack REAR FRONT WALL or ROW to help form “hot aisle” Hot aisle CFD simulation of airflow leaving the turning vanes (Air velocity vectors show)
  • 6. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 6 the same principle that allows wings to lift an airplane.) Unlike the gentle and fairly uniform “sucking” of hot IT exhaust in the hot aisle, the strong jets blanketing the rack inlets creates highly variable conditions from rack to rack. (Jet flow is characterized by localized pressure and velocity changes.) Note that turning vanes also have a significant pressure drop requiring more fan power. Correcting misconception 2: Row coolers are needed in every row Many believe that row coolers can only cool the racks which are located in the same row as the coolers. Both design attributes described above show that, with a high hot air capture index, it doesn’t matter if all the row coolers are on one side of a two-row pod (or any placement combination). CFD modeling and actual installations show it is possible for row coolers in a single row to cool racks in both rows as illustrated in Figure 5. The percentage values on each rack represent the hot air capture index. Note in the figure, all the IT inlets are exposed to the blue color which is neutralized air, and the red color variation in the middle is the hot aisle. Correcting misconception 3: Row coolers can’t cool loads outside their pod This misconception has been communicated in other ways including: • Row coolers are for spot cooling pods only • Row coolers can’t cool racks in another pod • Row coolers can’t cool a large room • Row coolers can’t cool tape storage units on the perimeter of my data center • N+1 cooling redundancy with row cooling means that you need a redundant cooling unit in every pod An important fact to understand about this misconception is that the hot air capture index measures the percentage of a rack’s hot exhaust air that is captured directly by row cooler(s) in the same pod as the rack. By definition, if 100% of a rack’s hot air were to make its way back to a row cooler far outside its pod, its hot air capture index would be 0%. Therefore, the most predictable way to cool stand-alone ancillary IT gear, such as storage arrays, is to place a row cooler next to the gear, assuring a high hot air capture index. In essence, this creates a miniature pod with up to 100% hot air capture. This is analogous to placing a perforated tile in front of the stand-alone gear, in a raised floor cooling architecture. Figure 5 Example CFD analysis with all row coolers in one row 3D view looking at the top of the racks Average 5kW/rack with no cooling redundancy or containment 99% 98% 95% 93% 99% 100% 100% 93% 91% 95% 98% 100% 100% 99% 100% 100% 99% 98% 100% 96%C C C C C Hot Aisle Supply air direction of row coolers C
  • 7. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 7 The main difference is that a perforated tile operates on the premise of cold air capture which in this case is limited by how much airflow (and kW cooling capacity) is provided as dis- cussed in WP121, Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center. What if the stand-alone IT gear doesn’t have a row cooler (i.e. in its pod)? How would this gear be cooled in a row-based cooling architecture? The answer is tied to the “rack-based footprint” and “variable cooling capacity devices” design attributes of row coolers. The rack- based footprint allows coolers to be distributed across the entire data center which creates a close-coupled cooling effect with all heat loads. The variable cooling capacity devices over- supply cold air to the cold aisle after sensing an increased room temperature. Containing the hot aisle with row coolers can also improve hot air capture, especially at densities below 3kW/rack. Will containment have a negative impact on cooling stand-alone IT gear? The easiest way to illustrate this is by comparing two identical data center layouts each with 65 racks, 235kW of IT load, two stand-alone IT devices, with and without containment. Figure 6A shows the results of a CFD analysis with 14 row coolers distributed evenly throughout the data center. The density for the 20 wide racks is 5kW/rack and the 43 narrow racks are 3kW/rack. The two ancillary racks in the upper right-hand corner represent stand- alone IT gear. The hot air capture index value (with the unit of percentage) is shown on each rack. Both the 5kW stand-alone and 1kW stand-alone devices have an average inlet air temperature of 22˚C (71.6˚F). Figure 6B shows the results of a CFD analysis of the same data center except with hot aisle containment to illustrate its effect on hot air capture and inlet air temperatures of the stand-alone IT devices. Most of the racks have 100% hot air capture index. Both stand-alone IT devices have an average inlet air temperature of 21˚C (69.8˚F). Figure 6A Example CFD analysis with distributed row coolers 3D view looking at the top of the racks 235kW total load 65 total racks Wide racks = 5kW/rack Narrow racks = 3 kW/rack No cooling redundancy or containment 5kW stand- alone device 1kW stand- alone device Figure 6B Example CFD analysis with centralized row coolers 3D view looking at the top of the racks 235kW total load 65 total racks Wide racks = 5kW/rack Narrow racks = 3 kW/rack No cooling redundancy but with containment 5kW stand- alone device 1kW stand- alone device 99 100 99 98 99 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 59 65 89 100 76 76 94 85 97 100 100 100 97 66 68 73 79 67 63 97 92 81 90 97 100 99 100 100 98 97 82 80 9193971001009999 C C CCC C C C C C C C 100 100 100 100 100 100 100 100 100 100 100 100C C C C C100 100 100 100 100 100 100 100 100 100 100 100 99 99 99 100 100 100 100 100 100 100 99 99 99 99 99 99 99 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 C C C C C C C C C C C Hot Aisle Hot Aisle Hot Aisle Hot Aisle Hot Aisle Hot Aisle 0 0 0 0
  • 8. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 8 The figures above help to visualize the effect of row coolers on hot air capture index values and cooling stand-alone IT device. As row coolers are variable capacity devices that are capable of over-supplying cold air to the cold aisle. When the system is in balance, the supply temperature from the cooler is equal to the IT inlet temperature. When ancillary equipment (i.e. stand-alone devices) is initially added outside of the pod, the temperature of the overall room environment increases due to air mixing. Nearby row-based cooling units sense this increase and respond by increasing cooling capacity thereby neutralizing the hot air. This increased cooling capacity is achieved by increased air flow (row coolers increase fan speed) and or lower supply air temperature (row cooler increase chilled water valve flow). These adjustments occur initially but remain unchanged once the data center reaches steady state. The steps describing how the row-based coolers “pick up the ancillary load” are the same even when containment is used. In either case we expect the ancillary equipment to operate at higher temperatures than the row-based racks, because it is not directly coupled to row coolers in their own pod. The further away stand-alone IT gear is from row coolers, the higher their inlet air temperature will be. Should you be concerned about the elevated ancillary equipment temperature? Often times IT equipment can tolerate ASHRAE’s recom- mended maximum temperature of 27˚C (80.6˚F). If this is not acceptable, it may be appropri- ate to place row cooler close to the ancillary equipment rack. For more information on cooling loads outside of a pod, see White Paper 139, Cooling Entire Data Centers Using Only Row Cooling and White Paper 134, Deploying High-Density Pods in a Low-Density Data Center.
  • 9. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 9 Row-based cooling was designed with a focus on capturing hot exhaust air from IT equip- ment in a pod. The higher the hot air capture index values, the less hot air recirculation that occurs, which decreases temperature variations across racks (such as hot spots). It doesn’t matter where the cold air goes; it matters where the hot air comes from. Row-based cooling units can also help to cool ancillary equipment or racks outside of their pod but hot air capture index is not used as a performance metric in this case. Instead row coolers use a close-coupled cooling process described in this paper. Understanding these principles helps to explain the three misconceptions described in this paper and provides a foundation for effective deployment of row-based cooling. Conclusion Paul Lin is a Senior Research Analyst at Schneider Electric's Data Center Science Center. He is responsible for data center design and operation research, and consults with clients on risk assessment and design practices to optimize the availability and efficiency of their data center environment. Before joining Schneider Electric, Paul worked as the R&D Project Leader in LG Electronics for several years. He is now designated as a “Data Center Certified Associate”, an internationally recognized validation of the knowledge and skills required for a data center professional. He is also a registered HVAC professional engineer. Paul holds a master’s degree in mechanical engineering from Jilin University with a background in HVAC and Thermodynamic Engineering. Victor Avelar is the Director of Schneider Electric’s Data Center Science Center. He is responsible for data center design and operations research, and consults with clients on risk assessment and design practices to optimize the availability and efficiency of their data center environments. Victor holds a bachelor’s degree in mechanical engineering from Rensselaer Polytechnic Institute and an MBA from Babson College. He is a member of AFCOM and the American Society for Quality. About the author
  • 10. How Row-based Data Center Cooling Works Schneider Electric – Data Center Science Center Rev 0 10 Choosing between Room, Row, and Rack-based Cooling for Data Centers White Paper 130 Improving Rack Cooling Performance Using Airflow Management Blanking Panel White Paper 44 Cooling Solutions for Rack Equipment with Side-to-Side Airflow White Paper 50 Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency White Paper 135 Implementing Hot and Cold Aisle Containment in Existing Data Centers White Paper 153 Airflow Uniformity Through Perforated Tiles in a Raised-Floor Data Center White Paper 121 Cooling Entire Data Centers Using Only Row Cooling White Paper 139 Deploying High-Density Pods in a Low-Density Data Center White Paper 134 Browse all white papers whitepapers.apc.com tools.apc.com Browse all TradeOff Tools™ ©2014SchneiderElectric.Allrightsreserved. For feedback and comments about the content of this white paper: Data Center Science Center dcsc@schneider-electric.com If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative at www.apc.com/support/contact/index.cfm Contact us Resources