  1. 1. SAUDI ARAMCO INDUSTRIAL LIGHTING USING DIALUX 4.11 Indoor, Emergency, Outdoor & Security Lighting Applications based on SAES-P-123 Engr. Michael T. Santiago | REE.AILP.MIES DIALux Accredited Trainer, ID 2013029 Supervisor, Lighting Applications Design Department Day Two – Outdoor & Security Lighting 4th day of March, 2014 SNC Lavalin Fayez Engineering Office Auto Moto Complex, Al-Khobar, KSA
  2. 2. Saudi Aramco, a fully integrated, global petroleum and chemicals enterprise, is the state-owned oil company of the Kingdom of Saudi Arabia. Through our 80-year history we have become a world leader in hydrocarbons exploration, production, refining, distribution, shipping and marketing, and the world’s top exporter of crude oil and natural gas liquids (NGLs). COURSE DEFINITION: A two day seminar & hands-on training for engineering design employees of SNC-Lavalin Fayez Engineering for the application of SAES-P- 123 (Saudi Aramco Engineering Standards) in indoor, emergency, outdoor & security lighting of Saudi Aramco Industrial Projects with the use of DIALux 4.11 as the lighting calculation software. SOURCE: http://www.aramco.com.sa INTRODUCTION SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  3. 3. A. THEORETICAL  Basic Lighting Terminologies  Fundamental Formulas  Manual Calculation & DIALux Verification  SAES Recommended Practices B. PRACTICAL  Outdoor Lighting Calculation in DIALux  Security Lighting Calculation in DIALux  Print-output & CAD LAyouts INTRODUCTION SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  4. 4. 1. To refresh participants with the design recommendations according to SAES P-123, IESNA and NFPA 70 2. To apply the design recommendations using SLC Products in future Saudi ARAMCO Substation Projects 3. To build a strong foundation where participant can design, calculate and estimate lighting for any given task, room or area in a ARAMCO substation project. OBJECTIVES SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  5. 5. 1. Adherence to Standards ~ NFPA ~ IESNA ~ OTHER SAUDI REGIONS 2. All Indoor Lighting will be calculated without effect of obstructions/objects but if future projects will provide a detailed furniture/equipment/cable tray/HVAC ducts layout, they should be included in the planning and calculation 3. DIALux, a leading lighting planning / calculating / rendering software from Germany will be used for evaluation and print output CONSIDERATIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  6. 6. (BIDDING) – SLC Gives Technical Offer – {We start here} (PRICING) – Requests to Verify Quantity - {Procurement} (REVISION) – Changes due to updated CAD layouts – {Design} {AS-BUILT} - Changes due to actual equipment, cable tray, HVAC ducting installations – {Site} {COMMISSIONING} – Possible issues arising after materials are supplied or lux levels are tested {Site} We would appreciate a request containing all relevant, detailed and updated information so we can minimize design rebounds. IMPORTANCE SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  7. 7. 1. GOALS OF A GOOD DESIGN a. surveillance inspection b. equipment inspection c. overall safety & performance status during nomal and emergency operation GENERAL INFO ON YARD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  8. 8. 2. PARTS OF YARD LIGHTING GENERAL INFO ON YARD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications Shaded / Unshaded Parking Workers Villa
  9. 9. 2. PARTS OF YARD LIGHTING GENERAL INFO ON YARD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications Interior / Residential Roads Interior / Residential Roads
  10. 10. 2. PARTS OF YARD LIGHTING GENERAL INFO ON YARD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications Platforms Building Elements
  11. 11. 2. PARTS OF YARD LIGHTING a. Perimeter Fence b. Gate Houses / Check Points c. Company Signboard d. Exterior Doors e. Main Entrances f. Roads g. Area Lighting (transformer bays, capacitor banks, etc.) GENERAL INFO ON YARD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  12. 12. BEAM LUMEN METHOD FOR FLOODLIGHTS FORMULAS TO BE USED SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  13. 13. POINT-BY-POINT METHOD FOR FLOODLIGHTS FORMULAS TO BE USED SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  14. 14. Image Source: Zumtobel, The Lighting Handbook Image Source: http://sustainabilityworkshop.autodesk.com/buildings/measuring-light-levels LIGHTING TERMS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  15. 15. SAMPLE: A point source luminaire is placed at a parapet of 3m height. It is aimed to the ground 4.5m away. When measured by a lux meter, it shows 10 lux. How much is the luminaire’s candela power? Frmla: Given: adj =3m opp=4.5m E = 10 lux Solution: get Ɵ, so tan Ɵ = 3/4.5 = 33.69 Ɵ = 56.31° then, d = 3 ² + 4.5 ² d = 5.408 m E x d ² 10 lm/m² x (5.408m) ² then, I = = cos Ɵ cos 56.31 ° Therefore : I = 527.249 cd MANUAL CALCULATION: FORMULA SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  16. 16. Eave = Average Illuminance (E) in lux Φ = Initial Flux in lumens CU = Coefficient of Utilization, Street Side MF = Maintenance Factor or LLF WR = Width of Roadway in meters PS = Pole Spacing in meters Therefore to get Pole Spacing: SAMPLE PROBLEM: 7435-250W MH Lamp with 19,000 lumens 7m Road width, 6m Pole Height Maintenance Factor as 70% What is the ideal Pole Spacing to achieve average illuminance of 20 lux? To get CU, Road Width / Pole Height = 7m / 6m = 1.6 Therefore, Street Side CU is 0.4 MANUAL CALCULATION: ROAD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  17. 17. MANUAL CALCULATION: ROAD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications DIALux Verified Calculation
  18. 18. MANUAL CALCULATION: ROAD LIGHTING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications DIALux Verified Calculation
  19. 19. LAMPS TO BE USED SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications SAES –P-123 Article 5.8.2 & 5.8.3 MINIMUM ACCEPTABLE EFFICACY CRI CCT HPS 87 lm/W -- -- LED < 50W 120 lm/W 90 or better 4000K & up LED > 50W 1240 lm/W 90 or better 4000K & up MH > 400W 58 lm/W -- -- Fluorescent 82.55 lm/W 82 3500k & up Incandescent 16 lm/W -- -- a. High Pressure Sodium, tubular clear ~ 250W (27500 lum) - OSRAM NAV-T 250 (28000 lum) ~ 400W (50000 lum) – GE LU-400/40 (51000 lum) ~1000W (140000 lum) – GE LU-1000/40 (140000 lum) ~100W (9500 lum), 127Vac – GE LU-100/ECO Connected to Indoor LP
  20. 20. MINIMUM LUX LEVELS PER AREA SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications a. Overall Area – maintained Min of 20 lux on ground b. Transformer Bay - 100 lux Min c. Building Entrance – 50 lux average d. Gate Houses – 300 lux Min e. Trenches – 100 lux Min f. Roadways – 15 lux g. Parking – 10 lux
  21. 21. 4. FIXTURES PER AREA ~DC Emergency – Lighting is not Required ~AC Normal a. Main Entrances (3m or Top of Door/Gate) - To the Substation - Gate Post - Outdoor Transformer Bay - Station Service for Transformers ~V2FW / 5-100, 100W HPS-T, 127 Vac MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  22. 22. 4. FIXTURES PER AREA ~DC Emergency – Lighting is not Required ~AC Normal b. All other Exterior Doors - 60W incandescent lamp, 127 Vac ~ 8513W/11-60x c. Road Lighting ~ tubular clear HPS lamp 7435/5-250 7435/5-250 MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  23. 23. 4. FIXTURES PER AREA ~DC Emergency – Lighting is not Required ~AC Normal d. Fence Lighting - Assymetrical Floodlight ~ A6TG/5-400 e. Large Area Lighting - NEMA 6x5 Floodlight ~ PF1K/5-400 ~ PF1K/5-1000 MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  24. 24. 4. FIXTURES PER AREA ~DC Emergency – Lighting is not Required ~AC Normal d. Bay Area - Small Floodlight ~ FL42/5-250 ~ FL42/5-400 MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  25. 25. INDUSTRIAL LIGHTING USING DIALUX – DAY 2 - OUTDOOR AREA LIGHTING 1. POSSIBLE MOUNTING A. Generally, Poles need to be as high as 10 meters B. Floodlights aimed close to an angle of 54.7 to Vertical
  26. 26. INDUSTRIAL LIGHTING USING DIALUX – DAY 2 - OUTDOOR AREA LIGHTING 1. POSSIBLE MOUNTING c. Transmission Tower/Gantry on both sides d. Building Parapet e. Localized, wall-bracketed around transformer f. For signboards, use of 2 x 250W fixtures, preferably A6TG/3-250, 250W clear tubular Metal Halide Very Good example is Qassim Project
  27. 27. PERIMETER LIGHTING 1. Adherence to SSD/13 a. Use of 400w Assymetrical Floodlight b. 3 m high Pole, 10 m spacing, c. 10 m inside fence MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  28. 28. ROAD LIGHTING 1. ROAD LIGHTING SCEMES MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications
  29. 29. ROAD LIGHTING MOUNTING SUGGESTIONS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications TYPICAL POLE SETBACKDesign Speed Pole Setback 50 kmh 0.8 m 80 kmh 1.0 m 100 kmh 1.5 m 120 kmh 1.5 m BS EN 5489-1:2003 Section 5.2.1.2 Pole Heights Pole Arm Length Arm Tilts 6.0 m 0.5 m 5°, 10°, 15° 8.0 m 1.0 m 5°, 10°, 15° 10.0 m 1.5 m 5°, 10°, 15° ≥ 12.0 m 2.0 m 5°, 10°, 15° *Common Practice RECOMMENDATIONS*
  30. 30. HELPFUL LINKS SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications For DIALux support: http://dxboard.dialux.com/ For Lighting Fundamentals: http://www.ies.org/lighting/ For Lighting Applications: http://www.licht.de/en/lighting-for-professionals/lighting-design/lighting-design- in-practice/ For Design Tips:http://www.ieslightlogic.org/ For free 3DS models: http://archive3d.net/ For free 3D Textures: http://archivetextures.net/ For Free DIALux M3D models: https://sites.google.com/site/dialux3d/home For Free Indoor M3D Models: https://sites.google.com/site/ezzatbaroudi/dialux-evo-m3d-furniture-free- download
  31. 31. CLOSING SAUDI ARAMCO INDUSTRIAL LIGHTING | Day Two – Outdoor & Security Applications THANK YOU FOR VALUED ATTENTION! Please submit your Evaluation of the Training As well Day One & Day Two Exercises Michael T. Santiago | REE.AILP.MIES LAD Supervisor Lighting Applications Design (LAD) Department Saudi Lighting Company http://www.saudilighting.com Riyadh, Saudi Arabia Tel: +966-11-4741515 Ext 113 Fax: +966-11-4743698 Cell: +966-56 262-3490 Email: michael@saudilighting.com

×