SCHOOLOFARCHITECTURE,BUILDING &DESIGN
CENTREOFARCHITECTURESTUDIESINSOUTHEASTASIA
(MASSA)
BACHELOROFSCIENCE(HONOURS)(ARCHITECTURE)
BUILDING SCIENCE2(BLD61303)
LEEJO YEE
LIM YEEQUN
LING HUISIM
LIEW QIAO LI
CHUNG WEIJING
CHANPINQI
0314880
0319121
0313855
0315671
0313789
0314676
TUTOR:MREDWINCHAN
PROJECT1:LIGHTING &ACOUSTIC
PERFORMANCEEVALUTION&DESIGN
DONUTESSS15
1 | P a g e
CONTENTS PAGE
1.0 INTRODUCTION
1.1 Aim and Objective
1.2 Site Information
1.2.1 Site Introduction
1.2.2 Site Selection Reasons
1.2.3 Technical Drawings
2.0 LIGHTING PERFORMANCE EVALUATION
2.1 Literature Review
2.1.1 Architectural Lighting
2.1.2 Daylight Factor
2.1.3 Lumen Method
2.2 Precedent Studies
2.2.1 Introduction
2.2.2 Daylighting
2.2.3 Artificial Lighting
2.2.4 Conclusion
2.3 Research Methodology
2.3.1 Light Measuring Equipment (Digital Lux Meter)
2.3.2 Data Collection Method
2.4 Case Study
2.4.1 Introduction
2.4.2 Zoning
2.5 Existing Lighting Conditions
2.5.1 Existing Light Fixture
2.5.2 Materials
2.6 Lighting Data Analysis
2.6.1 Daytime Lux Reading
2.6.1.1 Zone A
2.6.1.2 Zone B & C
2.6.2 Night Time Lux Reading
2.6.2.1 Zone A
2.6.2.2 Zone B & C
2.6.3 Observation and Discussion
2.7 Lighting Calculation Analysis
2.7.1 Daylight Factor Analysis
2.7.1.1 Zone A
2.7.1.2 Zone B
2.7.1.3 Zone C
2 | P a g e
2.7.2 Artificial Lighting Analysis
2.7.2.1 Zone A
2.7.2.2 Zone B
2.7.2.3 Zone C
2.8 Conclusion
3.0 ACOUSTIC PERFORMANCE EVALUATION
3.1 Literature Review
3.1.1 Architecture Acoustic
3.1.2 Sound Pressure Level (SPL)
3.1.3 Reverberation Time (RT)
3.1.4 Sound Reduction Index (SRI)
3.2 Precedent Studies
3.3 Research Methodology
3.3.1 Acoustic Measuring Equipment
3.3.1.1 Digital Sound Level Meter
3.3.1.2 Camera
3.3.1.3 Measuring Tape
3.3.2 Methodology
3.3.3 Data Collection Procedures
3.4 Case Study
3.5 Existing Noise Sources
3.5.1 External Noise
3.5.1.1 Site Context
3.5.1.2 Vehicles
3.5.2 Internal Noise
3.5.2.1 Human Activities
3.5.2.2 Speakers
3.5.2.3 Air Conditioners
3.5.2.4 Electrical Appliances
3.5.3 Location of the Noise Sources
3.6 Materials and Properties
3.6.1 Furniture Material
3.6.2 Wall Material
3.6.3 Ceiling Material
3.6.4 Floor Material
3.7 Acoustic Tabulation and Analysis
3.7.1 Sound Intensity Level (SIL)
3.7.1.1 Sound Meter Reading of Retail Area (Zone A)
3.7.1.1.1 Peak Period
3.7.1.1.2 Non-Peak Period
3.7.1.1.3 Analysis
3.7.1.2 Sound Meter Reading of Reading Area (Zone B&C)
3 | P a g e
3.7.1.2.1 Peak Period
3.7.1.2.2 Non-Peak Period
3.7.1.2.3 Analysis
3.7.2 Reverberation Time (RT)
3.7.2.1 Zone A-Retail (Peak)
3.7.2.2 Zone A-Retail Area ( Non-Peak)
3.7.2.3 Zone B & C- Reading Area (Peak)
3.7.2.4 Zone B & C- Reading Area ( Non-Peak )
3.7.2.5 Analysis
3.7.3 Sound Reduction Index (SRI)
3.7.3.1 Zone A- Retail Area
3.7.3.1.1 Wall A
3.7.3.1.2 Wall B
3.7.3.2 Zone B & C- Reading Zone
3.7.3.2.1 Wall C
3.7.3.2.2 Wall D
3.7.3.3 Analysis
4.0 BIBLIOGRAPHY
4 | P a g e
CHAPTER
This chapter discuss on the aim and objective of this case study. Besides, this chapter also includes the
introduction of site chosen and reason behind.
1I N T R O
5 | P a g e
1.0 INTRODUCTION
1.1 Aim and Objective
This Project mainly focus on the lighting and acoustic study of the case study, Donutes
SS15.
Lighting design essential element in architectural design and interior design. Via lighting,
solid volumes, colours, enclosed spaces and textures can only come to sight. Successive
building are building where standard required amount of lighting is achieved.
Acoustic design is an element which concerned with control of sound in spaces
especially enclosed spaces. The requirement varies in accordance to various functions. It is
crucial and essential to enhance the desired sound and to eliminate noise and undesired noise.
This project is mainly exploring students to the way of designing a good lighting system
and good acoustic system via a series of calculation. The objective of the lighting analysis is to
understand the daylighting and lighting besides acoustic characteristic and acoustic requirement
in the case study. Moreover, the study’s objective is to determine the characteristic and function
of the day lighting and artificial lighting and sound & acoustic within the intended space. Finally
is to critically report and analyse the space based on the data collected.
1.2 Site Information
1.2.1 Site Introduction
Donutes, a 24-hours operating bakery and café that is located in the brim of
SS15, Subang Jaya has emerged as the favourite gathering spot for local community,
especially youngsters. Originally from Taiwan, the bakery brand has expanded and
reached the shore of Malaysia in the year of 2013 when its first branch opened in Bandar
Puteri Puchong, followed by the second franchise in Damansara (2014) and the third
one in Subang Jaya (2015). We have chosen this café as our case study not only
because its experience in designing a good café atmosphere and also the high human
traffic in the building.
6 | P a g e
Figure 1.2.1: Exterior of Donutes Café
Figure 1.2.2: Outdoor smoking area
Figure 1.2.3: Interior of the café first floor – reading area
7 | P a g e
CHAPTER
Lighting or illumination is the deliberate use of light to achieve a practical or aesthetic effect. Lighting
includes the use of both artificial light sources like lamps and light fixtures, as well as natural
illumination by capturing daylight. Daylighting using windows, skylights, or light shelves is sometimes
used as the main source of light during daytime in buildings.
2L I G H T
8 | P a g e
2.1 Literature Review
2.1.1 Architecture Lighting
Importance of Light in Architecture
Light is the most important factor in the appreciation and understanding of
Architecture. The relationship between light and architecture is grounded in the principles
of physics; it is about energy and matter but in this particular case it also implies an
emotional effect on people. The word of space is directly connected to the way light
integrates with it. Light interact with us and environment by our vision, experience and
interpretation on elements. Based on architecture study, in any dimension we can analyze
such as space, material or colour, it is essentially dependent on the lighting situation that
involves both the object and the observer. The dynamic daylight and the controlled
artificial lighting are able to affect not only distinct physical measurable setting in a space,
but also to instigate and provoke different visual experiences and moods. In addition, light
can perceive different atmospheres in the same physical environment. It also integrates an
element of basic relevance for design of spaces which plays a significant role in the
discussion of quality in architecture.
Natural Daylighting & Artificial Electrical Lighting
Natural light has always been important for architects. In a way, architects sculpt
buildings in order that the light can play off their different surfaces. If done well, space and
light can evoke positive emotional responses in people. Although architects should always
strive towards achieving a building which can draw in as much natural daylight as
possible, it is almost impossible to go on without electrical lighting taking into consideration
in design especially that it need to function both day and night. Moreover, certain building
typologies and uses are not suitable for daylighting such as museums and galleries
because exposure to natural light could damage the artifacts. It is an important
understanding of limitations and opportunities in using natural daylighting as well as
artificial lighting and be able to apply it architecturally to achieve the best performing
building.
Balance between Science & Art
The balance of science & art will create a visually appropriate light scene
accordingly to the character and use of a space .Sciences of light production and luminaire
photometric are important as they are balanced with the artistic application of light as a
medium in our built environment. Electrical lighting systems and daylighting systems
should be integrated together while considering the impacts of it.
There are three fundamental aspects in architectural lighting design for the
illumination of building and spaces, including the aesthetic appeal, ergonomic aspect and
energy efficiency of illumination. Aesthetic appeal focuses on the importance of
illumination in retail environments. Ergonomic aspect is the measurement of how much
function the lighting produces. Energy efficiency covers the issue of light wastage due to
over illumination which could happen by unnecessary illumination of spaces or over
providing light sources for aesthetic purposes. Each of these aspects are important when
lighting works are carried out. It allows exploration on the attractiveness of the design by
either providing subtle or strong lighting sources which creates different emotions for the
users.
9 | P a g e
2.1.2 Daylight Factor
It is a ratio that represents the amount of illumination available indoors relative to the
illumination present outdoors at the same time under overcast skies. Daylight factor is usually used to
obtain the internal natural lighting levels as perceived on a plane or surface, in order to determine the
sufficiency of natural lighting for the users in a particular space to conduct their activities. It is also
simply known to be the ratio of internal light level to external light level, as shown below:
Daylight Factor, DF
Indoor Illuminance, Ei
Outdoor Illuminance, Eo
Where, Ei = Illuminance due to daylight at a point on the indoor working planes,
Eo = Simultaneous outdoor illuminance on a horizontal plane from an unobstructed hemisphere of
overcast sky.
Zone DF (%) Distribution
Very bright > 6 Large (including thermal and glare problem)
Bright 3 – 6 Good
Average 1 -3 Fair
Dark 0 – 1 Poor
Table 2.1 Daylight Factor and Distribution.
10 | P a g e
2.1.3 Lumen Method
Lumen method is used to determine the number of lamps that should be installed in a space.
This can be done by calculating the total illuminance of the space based on the number of fixtures and
determine whether or not that particular space has enough lighting fixtures.
The number of lamps can be calculated by the formula below:
Where, N = Number of lamps required
E = Illuminance level required (Lux)
A = Area at working plane height (m2)
F = Average luminous flux from each lamp (lm)
UF = Utilisation factor, an allowance for the light distribution of the luminaire and the room surfaces
MF = Maintenance factor, an allowance for reduced light output because of deterioration and dirt
Room Index, RI, is the ratio of room plan area to half wall area between the working and luminaire
planes.
Which can be calculated by:
Where, L = Length of room
W = Width of room
Hm = Mounting height, the vertical distance between the working plane and the luminaire
11 | P a g e
2.2 PRECEDENT STUDY
2.2.1 Introduction
Place: The Netherlands (Zwijndrecht)
Building type: Secondary school
Contact: Truus de Bruin-Hordijk (Faculty of Architecture, Technical University Delft, The Netherlands)
Measurements were done in two classrooms. Classroom A, which is facing North-West, is
experienced as dark by teachers. Another classroom B, which is facing South-East, is experienced
bright by teachers. The judgement of the lighting expert is negative for classroom A and is neutral for
classroom B. Both classrooms have grey walls and much furniture in it (Figure 2.2.1). Dimensions of
the classrooms are: 7.2 x 7.2 x 3 m3. These are normal standard dimensions for primary and
secondary classrooms in The Netherlands.
Figure 2.2.1 Classroom B (window side and corridor side)
12 | P a g e
2.2.2 Daylighting
The daylight factors were measured on 23 September 2008 by a (not complete) overcast sky.
Table 2.2.1 and 2.2.2 show the daylight situation of the classrooms with daylight factors measured on a
regular grid on table height (0.75 m). Table 2.2.3 shows the daylight factors in the middle on the
blackboard and the outer left and right part of the blackboard. Classroom A has a green chalk board,
whereas classroom B has a white board.
The table proved that the daylight factor is decreased below 0.5% on the corridor side of
classroom.
Black Board
Teacher desk 2.2 0.56 0.30
8.9 2.5 0.66 0.29
11.6 2.9 0.74 0.29
12.3 2.3 0.63 0.31
Table 2.2.1 The daylight factors (%) on student table height in classroom A.
White Board
Teacher desk 2.2 0.77 0.42
8.3 2.4 0.88 0.4
8.5 2.7 0.86 0.46
8.8 2.3 0.72 0.34
Table 2.2.2 The daylight factors (%) on student table height in classroom B.
Board type Left Middle Right
Black board 3 1 0.4
White board 2.4 0.82 0.38
Table 2.2.3 The daylight factors (%) on the boards in both classrooms.
Window Zone Corridor Zone
Window Zone Corridor Zone
13 | P a g e
Figures below show luminance pictures, taken with a luminance camera with a fish-eye lens,
from the back-side of the classrooms. It shows the situation for a sitting student with eye level on 1.2 m.
The figures show the daylight situation with and without electrical lighting.
Figure 2.2.4 Classroom A without electrical lighting
Figure 2.2.5 Classroom A with electrical lighting
Figure 2.2.6 Classroom B without electrical lighting
14 | P a g e
Figure 2.2.7 Classroom B with electrical lighting
2.2.3 Artificial Lighting
Both classrooms have six high-efficient surface-mounted luminaires with mirror reflector
(Philips TCS298), each luminaire with one Philips TL5 HO 49 W/830 lamp (Figure 2.2.8) with
electronic ballast. The illuminance on the work plane is 350 lx at full power. The school has
replaced the old lamps and luminaires some years ago. The lamps were placed in two rows of three
luminaires parallel to the window façade. The lamps were dimmable and have daylight sensors. There
were also presence detectors in these classrooms (Figure 2.2.9). There was also asymmetric board
lighting.
Figure 2.2.8 Philips TL5 Lamp Figure 2.2.9 New Lighting Installation
The luminance values in the windows of the classroom A are higher than in the windows of
classroom B, because of the presence of trees outside the classroom B. That can explain the difference
in the measured daylight factors, and so more energy savings are expected due to daylight sensors.
The luminance images illustrate how the automatic dimming of the electric lighting can
compensate an asymmetrical day-light distribution on the work plane (windows zone/corridor zone),
and on the blackboard.
15 | P a g e
2.2.4 Conclusion
In conclusion, natural light is important and can be affected by other side factor, for example
the condition outside the window. Natural light provide enough light to work but not causing discomfort
by the over exposed reflection on white surface like white painted wall and book. Direct light from the
windows may perceive as uncomfortable when having a high contrast ratios, without electrical lighting.
Therefore, most of the seat placed in the middle of class, due to the comfortable yet sufficient light. This
case study can apply into our site. Café by consider the people occupancy according to light condition,
furniture arrangement and artificial light placement.
2.3 RESEARCH METHODOLOGY
2.3.1 Light Measuring Equipment
a) Lux Meter
Lux meter also known as Light meter is used to measure the intensity of light illumination as
distinguished by the human eye. The value gained does not correspond to the object value of
energy radiated, as different wavelength within specific spectrum is perceived with varying
sensitivity by the eye. Therefore, lux meter reading is reading that are taken in consideration of
this variables.
Most Lux meter registers brightness with an integrated photodetector. The photodetector is
held perpendicular to the light source for optimal exposure. Readouts are presented via digital
PhotodetectorLCD
Display
16 | P a g e
LCD display. Most Lux meter has measurement in variable range. The model of lux meter used
in this case study is Lux LX-101.
2.3.2 Data Collection Method
Procedure
1) Ground floor plan and first floor plan is measured and drawn.
2) 3 zones of case study area is determined and plotted with grid lines.
3) Measurement is taken at 1.5m and 1.0m high at each intersection points at different time
(Daytime and Night time)
4) Procedure 3 is repeated.
1.5m
1.0m
Figure 2.3.2.1 Position height of lux meter during measurement
17 | P a g e
2.4 CASE STUDY
2.4.1 Introduction
Figure 2.4.1.1 Location of Donutes Cafe
Figure 2.4.1.2 Exterior view of Donutes Cafe
Donutes Café is one of the shops located at SS15, Subang Jaya. It is a 2-storey shop lot, with
an open roof concept. The café is a place where mostly student’s hangout after classes and office staff
relax after long hours of work. Peak hours of the café is usually during the night.
18 | P a g e
The building itself is situated along a busy main road and surrounded by several high rise
buildings, therefore noise pollution might occur at certain times. Part of the shop is designed with
curtain walling. This allows natural daylighting to enter the space, besides being illuminated with
artificial lightings. However it also produces glares into the shop during evening hours. The site has
very minimal sun shading besides the surrounding buildings.
This particular site was chosen as our case study due to its well known lighting design
strategies used in the building and variety type of lighting, which allow us to expose to new knowledge.
Figure 2.4.1.3 Interior Space during daytime
Figure 2.4.1.4 Interior space at night
19 | P a g e
2.4.2 Zoning
20 | P a g e
2.5 EXISTING LIGHTING CONDITIONS
LEGEND
AB
21 | P a g e
Figure 2.5.1 Ceiling Plan of Zone A (Colour referring to Light Specification List)
AB
22 | P a g e
LEGEND
23 | P a g e
Figure 2.5.2 Ceiling Plan of Zone B and C (Colour referring to Light Specification List)
AB
AB
24 | P a g e
Figure 2.5.3 Section A-A
Figure 2.5.4 Section B-B
25 | P a g e
2.5.1 Existing Lighting Fixture
Indication Image Light Type Philips Fluoresent Light
Lamp Luminous Flux (lm) 1250
Specification Extra-long life of 50,000
hours
Rated Colour Temperature 4100K
Colour Rendering Index 98
Luminaire Type Open Fluorescent Strip light
Wattage 8
Placement Hidden under ceiling or
cabinet ( Display bread )
Light Type Leadare LED Bulb
Lamp Luminous Flux (lm) 400 lm
Specification E27
Life time approx. 25.000
hours.
Rated Colour Temperature 5000K
Colour Rendering Index 82
Luminaire Type Built in LED lamps
Wattage 9
Placement Wall Lamp
Light Type LED Downlight
Lamp Luminous Flux (lm) 400 lm
Specification Life time approx. 35.000
hours.
Rated Colour Temperature 5000K
Colour Rendering Index 82
Luminaire Type Built in LED lamps Downlight
Wattage 40
Placement Ceiling Lamp
Light Type Fluid Pendent Light Bulb
Lamp Luminous Flux (lm) 800
Specification Life time approx.
4.000 hours
Rated Colour Temperature 2700K
Colour Rendering Index 100
Luminaire Type Decorative pendent Downward
Wattage 60
Placement Ceiling Lamp
Table 2.5.1.1 Light Specification
26 | P a g e
2.5.2 Materials
Figure 2.5.2.1 Materials on Section A-A
Figure 2.5.2.2 Materials on Section B-B
27 | P a g e
No. Location Materials Color Reflectance Surface
1. 1 Table Brown 25 Semi -Rough
2. 1 Laminated wood bookshelves Brown 25 Smooth
3. 2,1,3,4 Bread display stands
White 45 SmoothMarble
Wood
Laminated
Sheets
Brown 25 Smooth
Glass Transpar
ent
0 Smooth
Steel Silver 12 Smooth
Table 2.5.14 Furniture Material
28 | P a g e
No. Location Materials Color Reflectance Surface
1. 5 Concrete wall with Plaster finish Purple
Paint
6 Smooth
with
texture
2. 1 Wood Laminate Sheets Brown 25 Smooth
Table 2.5.15 Wall Material
29 | P a g e
3. 6 Exposed Concrete Grey 35 Smooth
4. 3 Glass Trans-
parent
0 Smooth
Table 2.5.16 Wall Material
30 | P a g e
5. 7 Mirror Reflective 88 Smooth
7. 8 Laminated Granite Sheets Dark Grey 40 Semi-
Rough
Table 2.5.17 Wall Material
31 | P a g e
No. Zone Materials Color Reflectance Surface
1. 9 Concrete Ceiling with Black paint finish Black 15 Rough
2. 2 Wood
Laminate Sheets
Wood 25 Smooth
Table 2.5.18 Ceiling Material
32 | P a g e
No. Zone Materials Color Reflectance Surface
1. 10 Porcelain Floor Tiles Light Grey 70 Semi
Smooth
2. 2 Laminated Wood Flooring Light Brown 25 Smooth
3. 6 Exposed Concrete Dark Grey 39.5 Smooth
Table 2.5.19 Floor Material
33 | P a g e
2.6 LIGHTING DATA ANALYIS
2.6.1 Daytime Lux Reading
2.6.1.1 Zone A
Diagram 2.6.1 Daytime data result on Zone A
.
Data at 1.5m Height
Data at 1.0m Height
*
34 | P a g e
Diagram 2.6.2. Daytime light contour on Zone A – 12pm
Diagram 2.6.3 Daytime light contour on Zone A – 4pm
The lux reading shown above shows the lux level during 4pm to 6pm interval. Partially, the
artificial lighting were switched on during our data collection, but all of them are placing low to light up
the floor. So, for the whole ground floor area, the main source of light during daytime is the sunlight.
Referring to Diagram 2.6.1, the reading for the inner space are lower as it is deep inside and it rarely
exposes to sunlight. The highest reading recorded is at the entrance area, where receive more sunlight
through the glass sliding door.
35 | P a g e
2.6.1.1 Zone B and C
Diagram 2.6.4 Daytime data result on Zone B and Zone C
Data at 1.5m Height
Data at 1.0m Height
*
Zone B
Zone C
36 | P a g e
Diagram 2.6.5 Daytime light contour on Zone B and Zone C
Within Zone B, a distinctively high reading is recorded along the glasses area, as the glasses
reflect the direct sunlight to the interior space. While the wall lights were switched on to light up the area
of gridline C2 to C5 and B8 to B10, because of the daylight is blocked by the partition and furniture.
Zone C is a semi-outdoor area where receives huge amount of sunlight as it is an open space
and yet surrounded with glasses.
37 | P a g e
2.6.2 Night Time Lux Reading
2.6.2.1 Zone A
Diagram 2.6.6 Night time data result on Zone A
The readings taken at 9pm at the night, which fully dependant on artificial lightings inside. The
higher lux readings are collected at the counter area (gridline C9-C11) as more artificial lightings are
installed to provide brightness for clear vision for people to order or paying. Overall, the luminance level
is above standard lux level, which is 200 lux (according to MS 1525).
Data at 1.5m Height
Data at 1.0m Height
*
38 | P a g e
Diagram 2.6.7 Night time light contour on Zone A
Diagram 2.6.8 Ceiling Plan of Zone A
According to Diagram 2.6.7, the area rendered with blue and purple area has lower luminance
level while red and orange area has higher luminance level. As shown in Diagram 2.6.8, more
downlights are installed around the counter and middle display area, which provide brighter
environment and thus exceed standard 200 lux. While moving towards the kitchen area, the luminance
level getting lower as that area is either walkway or corridor.
39 | P a g e
2.6.2.2 Zone B and C
Diagram 2.6.9 Night time data result on Zone B and C
The readings taken at 9pm at the night, which fully dependant on artificial lightings inside. At
certain areas, the readings are extremely low, which may drop to 2 or 3 lux. This is because this area is
main to be darker to create a more relaxing ambience. Overall, the luminance level is below the café
standard luminance level, which is 200 lux.
Data at 1.5m Height
Data at 1.0m Height
*
Zone B
Zone C
40 | P a g e
Diagram 2.6.10 Night time light contour on Zone B and C
41 | P a g e
Diagram 2.6.11 Ceiling plan of Zone B and C
According to Diagram 2.6.10, the area rendered with blue and purple area has lower luminance
level while red area has higher luminance level. As shown in Diagram 2.6.11, artificial lighting are all
placing near to the table to provide brightness to only targeted place. Most of the light are decorative
lighting and task lighting which did not provide general lighting to the whole area. Therefore, most of
the area are rendered in blue and purple colour which is considered very poorly lid.
42 | P a g e
2.6.3 Observation and Discussion
Observation 1
The readings of Zone A during daytime are lower than the readings collected during night time.
Discussion 1
The walkway outside Zone A has affected the daylighting as greatly reduce the coming in sunlight
because of the shaded. The artificial lighting is not bright compare to night time because ceiling
downlight are only turning on at night. During nigh time, the space looks brighter as the light reflecting
from ceiling and glasses. Hence, during daytime, the daylighting on Zone A is not sufficient.
Figure 2.6.1 Daytime on Zone A
Figure 2.6.2 Night time on Zone A
43 | P a g e
Observation 2
In opposite, the readings of Zone B and C during daytime are higher than the readings collected during
nigh time.
Discussion 2
By exclusively using full glass window on the west, Zone B and C receives much sunlight compare to
others. While during night time, decorative lightings and task lightings are used to focus on each table.
Also, because of the dark colour of wall and ceiling to create a relaxing ambiance, the whole area looks
dimmer.
Figure 2.6.3 Zone B (Grid D to G)
Figure 2.6.4 Night View on Zone B
Figure 2.6.5 Night view on Zone C
44 | P a g e
Observation 3
The readings collected at the inner space of Zone A, B and C are mostly under 200 lux, the standard
illumination level.
Discussion 3
The inner space area located far from the openings. The furniture and partitions are placing in layers
and blocking much of the sunlight. Thus, they receive inadequate sunlight during daytime. Poor
planning of placing artificial lightings was also darken down the area.
Figure 2.6.6 Daytime on Zone B
Figure 2.6.7 Daytime on Zone B
Grid A-CGrid D-G
45 | P a g e
Observation 4
Reading collected beside the glasses in Zone B are extremely high.
Discussion 4
That area is good for lighting but the direct sunlight is causing discomfort to the sofa area. Although the
shading panels are installed above and below the glasses, but when it comes to afternoon. Because of
the heat and glare, people occupancy on daytime is lower compare to night time.
Figure 2.6.4 Building West Facade
Figure 2.6.5 Strong contrast of luminance level in Zone B
46 | P a g e
2.7 LIGHTING CALCULATION ANALYSIS
2.7.1 Daylight Factor Analysis
2.7.1.1 Zone A (Retail Area)
Time Weather Luminance At
1m (1x)
Average (1x) Luminance at
1.5m (1x)
Average (1x)
4pm – 6pm Clear sky 28-77 62 lux 49 - 81 65.7 lux
Table 2.5.1 Lux Reading at Zone A
Average Lux Reading 4pm – 6pm
1m 62
1.5m 65.7
Average lux value 63.85 lux (64 lux)
Table 2.5.2 Average Lux Value at Zone A
Luminance Level Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1000 – 2000 lux Typical over cast day, midday
400 lux Sunrise or sunset on clear day (ambient illumination)
<200 lux Extreme of darkest storm clouds, midday
40 lux Fully overcast, sunset/sunrise
< 1 lux Extreme of darkest storm cloud, sunset/rise
Table 2.5.3 Daylight intensity at different condition
Date and Time 4pm – 6pm (26 April 2016)
Average lux value reading 64 lux
Daylight Factor Calculation Formula D =
Standard direct sunlight 20,000 lux
Calculation D=(64/20000) x 100%
= 0.32%
DF , % Distribution
>6 Very Bright With thermal and glare problem
3 – 6 Bright
1 - 3 Average
0 - 1 Dark
Table 2.5.4 Daylight Factor, DF
Daylight factor at Zone A, retail area is relatively low. The calculation shown is 0.32 and which
in the range of dark according to table provided in MS1525. This is due to the reason of the
cantilevered floor above, which covers up the five-foot walkway. The prevention of direct sun exposure
is purposely done to keep the indoor temperature low and thus keep the bread fresh.
(E external)
E internal x 100%
E external
(E internal)
47 | P a g e
2.7.1.2 Zone B (Reading Area)
Time Weather Luminance At
1m (1x)
Average (1x) Luminance at
1.5m (1x)
Average (1x)
4pm – 6pm Clear sky 10-19840 186.7 lux 2-1020 1170.36 lux
Table 2.5.5 Lux Reading at Zone B
Average Lux Reading 4pm – 6pm
1m 186.7
1.5m 1170.36
Average lux value 678.5 lux
Table 2.5.6 Average Lux Value at Zone B
Luminance Level Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1000 – 2000 lux Typical over cast day, midday
400 lux Sunrise or sunset on clear day (ambient illumination)
<200 lux Extreme of darkest storm clouds, midday
40 lux Fully overcast, sunset/sunrise
< 1 lux Extreme of darkest storm cloud, sunset/rise
Table 2.5.7 Daylight intensity at different condition
Date and Time 4pm – 6pm (26 April 2016)
Average lux value reading 678.5 lux
Daylight Factor Calculation Formula D =
Standard direct sunlight 20,000 lux
Calculation D=(678.5/20000) x 100%
= 2.89%
DF , % Distribution
>6 Very Bright With thermal and glare problem
3 – 6 Bright
1 - 3 Average
0 - 1 Dark
Table 2.5.8 Daylight Factor, DF
Daylight factor at zone B, reading area is considered high. The calculation shown is 2.89%,
which in the range of bright according to the table provided in MS 1525. The existence of glass around
the area had led high amount of lux to enter the interior space. This can save energy during daytime, as
only partial artificial lights are needed. However, the glare created is unpreventable as its location is at
the junction of turn in with existence of full wall of glass. Least shading device can be seen along the
glass window. The customers will also experience the high amount of glare during the noontime,
therefore shading device such as louvers is strongly recommended in this building.
(E external)
E internal x 100%
E external
(E internal)
48 | P a g e
2.7.1.3Zone C (Smoking Area)
Time Weather Luminance At
1m (1x)
Average (1x) Luminance at
1.5m (1x)
Average (1x)
4pm – 6pm Clear sky 90-370 232.16 lux 50-530 201.9 lux
Table 2.5.9 Lux Reading at Zone C
Average Lux Reading 4pm – 6pm
1m 232.16
1.5m 201.9
Average lux value 217 lux
Table 2.5.10 Average Lux Value at Zone C
Luminance Level Example
120,000 lux Brightest sunlight
110,000 lux Bright sunlight
20,000 lux Shade illuminated by entire clear blue sky, midday
1000 – 2000 lux Typical over cast day, midday
400 lux Sunrise or sunset on clear day (ambient illumination)
<200 lux Extreme of darkest storm clouds, midday
40 lux Fully overcast, sunset/sunrise
< 1 lux Extreme of darkest storm cloud, sunset/rise
Table 2.5.11 Daylight intensity at different condition
Date and Time 4pm – 6pm (26 April 2016)
Average lux value reading 217 lux
Daylight Factor Calculation Formula D =
Standard direct sunlight 20,000 lux
Calculation D=(217/20000) x 100%
=1.0%
DF , % Distribution
>6 Very Bright With thermal and glare problem
3 – 6 Bright
1 - 3 Average
0 - 1 Dark
Table 2.5.12 Daylight Factor, DF
Daylight factor at zone C, smoking area is moderate but relatively low compare to reading area.
The calculation shown is 1.0%, which is in the range of moderate according to the table provided
inMS1525. It is a partially open space which location is facing northwest, thus allows high amount of lux
to light up the place during daytime.
(E external)
E internal x 100%
E external
(E internal)
49 | P a g e
2.7.1 Zone A Lightings
Dimensions of Space
(L x W) (m)
(6.0 x 6.5) / (6.8 x 15)
Total Floor Area (m²) 107.8
Standard Illuminance
Required (lux)
200
Type of Lighting
Fixture
Fluorescent Light
(8W)
LED E27 Bulb (9W) LED Downlight (12W)
Number of Lighting
Fixture / N
10 6 28
Lumen of Lighting
Fixture / F (lm)
1250 700 900
Height of Luminaries
(m)
3.5 2.0 3.5
Height of Working
Plan (m)
1.3 1.3 1.3
Mounting Height / H
(m)
2.2 0.7 2.2
Reflection Factors (%) Ceiling : 30.0
Wall : 10.0
Ceiling : 22.5
Wall : 10.0
Ceiling : 50.0
Wall : 10.0
Room Index
𝑅𝐼 =
𝐿 𝑥 𝑊
𝐻 𝑥 (𝐿 + 𝑊)
= 6.0 x 6.5 / 2.2 x
(6.0 + 6.5)
= 1.4 ,
=6.8 x 15.0 / 2.2 x
(6.8 + 15.0)
=2.0
1.4 + 2.0 / 2.0
=1.7
=2.0
= 6.0 x 6.5 / 0.7 x
(6.0 + 6.5)
= 4.0 ,
=6.8 x 15.0 / 0.7 x
(6.8 + 15.0)
=6.7
4.0 + 6.7 / 2.0
=5.0
= 6.0 x 6.5 / 2.2 x
(6.0 + 6.5)
= 1.4 ,
=6.8 x 15.0 / 2.2 x
(6.8 + 15.0)
=2.1
1.4 + 2.1 / 2.0
=1.8
=2.0
Average
Utilisation Factor /
Refer Chart
0.29 0.72 0.78
Maintenance Factor 0.8 0.8 0.8
Average Illuminance
/lux
1.5m: 281.0 Average Illuminance: (281+ 211.4) / 2=246.7
1.0m: 211.4
Number of Light
Required
𝑁
=
𝐸 𝑥 𝐴
𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹
𝑁 =
200 𝑥 9.5m²
1250 𝑥 0.29 𝑥 0.8
= 6.5
= 7.0
𝑁 =
200 𝑥 12.3m²
700 𝑥 0.72 𝑥 0.8
= 6.0
𝑁 =
200 𝑥 86.05m²
900 𝑥 0.78 𝑥 0.8
= 30.6
= 31.0
Spacing requirement
for light fitting
S=
1.5 x Hm
(Diffuse Light)
1.0 x Hm
(Direct Light)
S=
1.5 x 2.2 = 3.3m
S=
1.0 x 0.7 = 0.7 m
S=
1.0 x 3.5 = 3.5 m
50 | P a g e
Total average lux in the retail area is 246.2 lux. The standard illuminance required for the room
with retail purpose is 200 lux. It is bright-lit room where its illuminance exceeds 46.2 lux.
As it is an area of bread display session of the bakery, it requires slightly higher illuminance to
emphasize the cleanliness and food attractiveness. The area did a good job in creating a well-lit room
for bread display as a variation of light fittings is seen throughout the area. However, it would be cost
consuming in maintaining the light fittings.
Instead of having 44 light bulbs of different type to achieve the required lux, suggestion of 38
LED down lights can be done in a cheaper way to light up the place.
51 | P a g e
2.7.2 Zone B Lightings
Dimensions of Space
(L x W) (m)
(10 x 13) / (8 x 4) / (6 x 2.5)
Total Floor Area (m²) 188.2
Standard Illumination
Required (lux)
200
Type of Lighting
Fixture
Fluorescent Light
(8W)
LED E27 Bulb (9W) LED Downlight (12W) Fluid Pendant Light
Bulb (60W)
Number of Lighting
Fixture / N
6 26 16 4
Lumen of Lighting
Fixture / F (lm)
1250 700 900 800
Height of Luminaries
(m)
3.0 2.0 3.0 2.3
Height of Working
Plan (m)
0.45 0.7 0.7 0.45
Mounting Height / H
(m)
2.55 1.3 2.3 1.85
Reflection Factors
(%)
Ceiling (Plywood)
: 25.0
Wall (Grey paint)
: 25.0
Ceiling (Grey paint)
: 25.0
Wall (Grey paint)
: 25.0
Ceiling (Plywood)
: 25.0
Wall (Glass)
: 0
Ceiling (White paint)
: 70.0
Wall (Glass)
: 0
Room Index
𝑅𝐼 =
𝐿 𝑥 𝑊
𝐻 𝑥 (𝐿 + 𝑊)
= 10.0 x 13.0 / 2.55 x
(10.0 + 13.0)
= 2.2 ,
=8.0 x 4.0 / 2.55 x
(8.0 + 4.0)
=1.0 ,
=6.0 x 2.5 / 2.55 x
(6.0 + 2.5)
=0.7 ,
= 2.2 + 1.0 + 0.7 / 3.0
= 3.9
=4.0
= 10.0 x 13.0 / 1.3 x
(10.0 + 13.0)
= 4.3 ,
=8.0 x 4.0 / 1.3 x
(8.0 + 4.0)
=2.0 ,
=6.0 x 2.5 / 1.3 x
(6.0 + 2.5)
=1.35 ,
= 4.3 + 2 + 1.35 / 3.0
= 2.55
=3.0
= 10.0 x 13.0 / 2.3 x
(10.0 + 13.0)
= 2.45 ,
=8.0 x 4.0 / 2.3 x
(8.0 + 4.0)
=1.15 ,
=6.0 x 2.5 / 2.3 x
(6.0 + 2.5)
=0.77 ,
= 2.45+1.15+0.77/3.0
= 1.5
=2.0
= 10.0 x 13.0 / 1.85 x
(10.0 + 13.0)
= 3.0 ,
=8.0 x 4.0 / 1.85 x
(8.0 + 4.0)
=1.4 ,
=6.0 x 2.5 / 1.85 x
(6.0 + 2.5)
=1.0 ,
= 3.0 + 1.4 + 1.0 / 3.0
= 1.8
=2.0Average
Utilisation Factor /
Refer Chart
0.60 0.15 0.39 0.67
Maintenance Factor 0.8 0.8 0.8 0.8
Average Illuminance /
Lux
1.5m: 49.7 Average Illuminance: (49.7 + 33) / 2= 41.35
1.0m: 33
Number of Light
Required
𝑁 =
𝐸 𝑥 𝐴
𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹
𝑁 =
200 𝑥 12.6m²
1250 𝑥 0.15 𝑥 0.8
= 16.8
= 17.0
𝑁 =
200 𝑥 72.8m²
700 𝑥 0.6 𝑥 0.8
= 43.0
𝑁 =
200 𝑥 74.2m²
900 𝑥 0.67 𝑥 0.8
= 30.7
= 31.0
𝑁 =
200 𝑥 74.2m²
800 𝑥 0.39 𝑥 0.8
= 22.9
= 23.0
Spacing requirement
for light fitting
S=
1.5 x Hm
(Diffuse Light)
1.0 x Hm
(Direct Light)
S=
1.5 x 2.55 = 3.8m
S=
1.0 x 0.7 = 0.7m
S=
1.0 x 2.3 = 2.3m
S=
1.5 x 1.85 = 2.7m
Data at 1.5m Height
Data at 1.0m Height
*
52 | P a g e
Total average lux in the reading area is 41.35lux where standard lux required is 200 lux. It is a
dimly lit up room which lacking 158.65lux.
In order to achieve the required lux, 17 of LED Leadfare Bulb E27 lights, 11 of indirect
fluorescent light E27, 23 more Fluid Pendant light bulb, and 31 more LED down light need to be added
into the area to achieve 200lux. Instead of having 82 type of light fittings, 77 of fluid pendant light can
used to achieve the standard illuminance and achieve the certain level of romantic and relaxing
ambient.
53 | P a g e
2.7.3 Zone C Lightings
Dimensions of Space (L x
W) (m)
(13.4 x 10.6) / (8.8 x 4.2) / (2.5 x 5.8)
Total Floor Area (m²) 92.8
Standard Illumination
Required (lux)
200
Type of Lighting Fixture LED Downlight (12W) Fluid Pendant Light Bulb (60W)
Number of Lighting
Fixture / N
7 5
Lumen of Lighting Fixture
/ F (lm)
800 900
Height of Luminaries (m) 2.3 4.0
Height of Working Plan
(m)
0.45 0.45
Mounting Height / H (m) 1.85 3.55
Reflection Factors (%) Ceiling (Black paint)
: 15.0
Wall (Glass)
: 0
Ceiling (Black paint)
: 15.0
Wall (Glass)
: 0
Room Index
𝑅𝐼 =
𝐿 𝑥 𝑊
𝐻 𝑥 (𝐿 + 𝑊)
= 13.4 x 10.6 / 3.55 x
(13.4 + 10.6)
= 2.0 ,
=8.8 x 4.2 / 3.55 x
(8.8 + 4.2)
=1.0 ,
=2.5 x 5.8 / 3.55 x
(2.5 + 5.8)
=1.0 ,
2.0 + 1.0 + 1.0 / 3.0
= 1.0
= 13.4 x 10.6 / 1.85 x
(13.4 + 10.6)
= 3.0 ,
=8.8 x 4.2 / 1.85 x
(8.8 + 4.2)
=2 ,
=2.5 x 5.8 / 1.85 x
(2.5 + 5.8)
=1.0 ,
3.0 + 2.0 + 1.0 / 3.0
= 3.0Average
Utilisation Factor / Refer
Chart
0.31 0.72
Maintenance Factor 0.8 0.8
Average Illuminance /
Lux
1.5m: 18.3 Average Illuminance: (18.3 + 12.58) / 2= 15.45
1.0m: 12.58
Number of Light Required
𝑁 =
𝐸 𝑥 𝐴
𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹
𝑁 =
200 𝑥 20.0m²
900 𝑥 0.72 𝑥 0.8
= 7.0
𝑁 =
200 𝑥 24.0m²
800 𝑥 0.31 𝑥 0.8
= 24.0
Spacing requirement for
light fitting
S=
1.5 x Hm
(Diffuse Light)
1.0 x Hm
(Direct Light)
S=
1.0x 1.85 = 1.85m
S=
1.5 x 3.5 = 5.25m
54 | P a g e
Total average lux in smoking area is 15.45 lux. The standard illuminance required for the room
is 200 lux. It is under insufficiency of light.
The difference between the required lux with the current reading is 184.55 lux. It needs another
24 Fluid light bulbs to achieve the standard lux. The low reading is gained due to the large number of
diffusing light around the area (Fluid Pendant Light). Low reflectance of the surrounding material also
affect to the low reading, the dark colour ceiling paint and glass window.
55 | P a g e
2.8 CONCLUSION
In conclusion, natural lighting in Donutes SS15 is relatively good based on the daylight factor
calculation, which range around average to moderate. The sufficiency of day lighting strongly
influenced by the openings provided. The strategic location at the corner lot had made Donutes SS15 a
successful place for natural lighting. However, based on the data collected, there’s a huge contrast in
daylight factor of the certain points although at the same floor area. This is caused by the existing
partition and furniture being separated in to an enclosed area to form a semi-private space.
Figure2.8.1Corner location of DonutesSS15
Figure2.8.2 Glass area along the edge of building (Reading Area)
56 | P a g e
The low daylight factor reading is due to the existing sunshade along the five-foot walkway. The
shaded area is then utilized to be a usable outdoor chatting area. However, this had blocked large
amount of natural light to be able to strike through the interior. Therefore, some artificial lights are
turned on during daytime to aid on the lighting effect, but overall appear dark inside except the bread
display area with display lights on.
Figure2.8.3 Glass area along the edge of building (Smoking Area)
Figure2.8.4 Partition blocking the sun exposure to inner space
Figure2.8.5 Contrast between lighting quality
57 | P a g e
Artificial lighting is relatively considered good and had achieved the standard of 200lux at the
ground floor retail area. Most of the artificial lights available in Donutes SS15 are located in low position
and low in power. Therefore, there’re number of them but resulted in moderate lighting effect which is
cost consuming and wasting energy.
Most of the light fittings are ambient based, not meant for general lighting to bring out the
ambience of a relaxing, eating and chatting area. Ordinary light fittings are not suitable for this building
as it serves as a relaxing hang out area. It cannot be placed a standard spacing of lights like in factory.
Therefore, the variation of light fittings is acceptable but only to be enhanced by improving the light bulb
luminous flux, and increase the number. The placement of the luminaires should be able to follow the
working planes, which are the table surface, allowing optional work to be carrying out in the comfortable
light.
Figure2.8.6 overhanging sunshade
Figure2.8.7 Well-litted ground floor (Bread Display Area)
58 | P a g e
Figure2.8.8 Dim lighted smoking area
CHAPTER
Sound is a mechanical wave which travels through a medium from one location to another. This motion
through a medium occurs as one particle of the medium interacts with its neighbouring particle,
transmitting the mechanical motion and corresponding energy to it.
3
S O U N D
55
3.0 ACOUSTIC PERFORMANCE EVALUATION
3.1 Literature Review
3.1.1 Architecture Acoustic
Architecture acoustic is the branch of physic study that deals with the production, control,
transmission, reception and effects of sound. The study of acoustics is important when
designing a desirable atmosphere with concern and control of sound in spaces. The aim
of the study is to preserve and enhanced desired sound in one space and on the other
hand reduce or eliminate sound that interrupt with our activities known as noise.
3.1.2 Sound Pressure Level (SPL)
It is a term most often used in measuring the magnitude of sound in decibels (dB). It is
a relative quantity in that it is the ratio between the actual sound pressure and a fixed
reference pressure. SPL of a place can be measure with a sound level meter weighted
according to a specific frequency response pattern.
Figure 1: Some typical sound pressure levels
Calculation of sound pressure can be calculated with this formula:
56
3.1.3 Reverberation Time (RT)
Reverberation is the prolongation of sound as a result of successive reflections in an
enclosed space after the sound source is turned off. Reverberation time is defined as
the length of time required for sound to decay 6 decibels from its initial level. However,
a reverberation is different from than an echo where the former is perceived when the
reflected sound wave reaches your ear in less than 0.1 second after the original sound
wave. There is no time delay between the perception of the reflected sound wave and
the original sound wave since the original sound wave is still held in memory.
Reverberation Time (RT) is an important index for describing the acoustical quality of an
enclosure.
Formulas: 0.16 V
A
Where: RT= reverberation time (sec)
V=volume of the room (cu.m)
A=total absorption of room surfaces (sq.m sabins)
3.1.4 Sound Reduction Index (SRI)
The Sound Reduction Index (SRI) or Transmission Loss TL of a partition measures the
number of decibels lost when a sound of a given frequency is transmitted through the
partition.
RT =
57
3.2 Acoustics Precedent Studies
THE MUSIC CAFÉ, AUGUST WILSON CENTRE.
The café is located at sidewalk level, accessible directly from the street and from within
the centre. It will function as a traditional museum café and sidewalk café during the day.
A seating terrace is located outside and adjacent to the café. Wired for internet access
and designed to accommodate a wide range of emerging technologies, the Café
provides an electronic link to visitors worldwide.
Modelled after New York’s BAM café or Joe’s Pub the Café is also designed to
accommodate an on‐going menu of programs and to function as an alternative
performance space for intimate performances with limited seating for jazz, spoken word,
poetry and other new performance forms in a club setting at night. A portable stage and
theatrical lighting will be imported to support such performances as required. This space
is essential a large rectangular box with three glass sides, a hard floor, and sound
absorbing treatment on the ceiling (although behind baffles and ductwork). It is evident
design does recognizes the need for acoustical design elements, with hanging metal
baffles and acoustical blanket over 80% of the underside of the floor structure above.
Based on the use description provided by the architect, a reverberation time of
approximately 1.0 second would be ideal. This would place the space somewhere
between speech and speech/music use. According to the Architectural Acoustics:
Principles and Design, a very high STC value (60+) between the Music Café and lobby
would be desirable. This is important to both spaces, as a spoken word performance in
the café could suffer if a large crowd was gathering in the lobby for a performance in the
main theatre, while the lobby must remain quiet during a performance in the main theatre
if patrons are entering or exiting the auditorium since a main set of doors is directly
across from the café.
Figure 2: August Wilson Centre Figure 3: Interior of the Music Café
58
Figure 7.1.2 illustrates that the existing reverberation times are far from ideal. One
important consideration, however, is that the manufacturer of the metal baffle ceiling
system (Chicago Metallic) does not have acoustical data for the product. Therefore, the
product has been omitted from the calculations. Including the baffles in the calculation
would likely reduce the very high reverberation times at the lower frequencies, but it
would also reduce the reverberation times at the higher frequencies which are already
lower than ideal.
Additional analysis of the sound transmission class (STC) on the wall between the café
and the main lobby reveals a potential for unwanted noise transfer between the
spaces. At 46, the calculated STC falls far below the ideal value of 60+. This problem
is generated by the use of glass doors and partitions between the spaces. Changing
the glass type from ½” tempered glass to ½” laminated glass improves the STC to 49,
but this is only a marginal increase. To really improve this potentially negative situation,
significant changes to the architecture are required. These changes may include
changing the glass to another material such as wood or creating a small vestibule at the
entrances.
These changes, however, would significantly alter the architecture. It would be
appropriate to point out the problem to the architect, but it is unlikely that the changes
would be made. Improving the reverberation time is a much more realistic change. In
order to do this, the metal baffles and acoustical blanket are eliminated, replacing them
with floating fiberglass sound absorbing panels that are faced in perforated metal. This
59
product is pictured in Figure 7.1.3. This change will most likely reduce cost by replacing
two materials with one. Some changes were necessary in the location and type of HVAC
diffusers and sprinkler heads. However, these changes should not require significant
changes to the overall system. Figure 7.1.5 shows the new reverberation times based
on 900 square feet of the new acoustical panels. Figure 7.1.4 shows the proposed
layout of these panels.
60
The new reverberation times are very close to the desired values. According to
Architectural Acoustics: Principles and Design, optimum reverberation times at 125 hertz
should be 1.3 times the ideal reverberation time at 500 hertz and a multiplier of 1.15
should be used at 250 hertz. These multipliers are used to correct for the fact that the
human ear is less sensitive at lower frequencies. With these factors included, the new
design is very near the target. The new ceiling system will provide superior acoustical
performance at a reduced cost.
CONCLUSION:
In conclusion, noise reduction within a space can be achieved by two methods:
improvement of reverberation time and also increasing the STC value. Reverberation
time can be improved to ideal level through the use of absorptive materials on ceilings
and surrounding walls, providing an optimum acoustical environment. On the other hand,
STC values can be increased by changing the materials of the wall in between spaces,
which reduces transmission of sound from a space to another, eliminating unwanted
noise.
61
3.3 Research Methodology
3.3.1 Acoustic Measuring Equipment
3.3.1.1 Sound Level Meter
The device is used to measure the sound level in a particular point in
a space. The measured unit is in (dB).
Figure 4: Front and rear view of the measuring device
Specification
Manufacturer LUTRON Lighting
Model SL-4023SD
Dimension/ Weight 245x68x45 mm / 489g without battery
Range 30-130 dB
Linearity +- 1.5 dB
Grade of Accuracy Not assigned
3.3.1.2 Camera
Camera is used to capture the source of noise
such as mechanical devices, speakers, and
existing activities and also to record the existing
materials in the environment.
3.3.1.3 Measuring Tape
It is used to determine the positions of the sound
level meter from the ground level and also used
to determine the 1.5m x 1.5m grid on the studying
area.
62
3.3.2 Methodology
a) Preliminary study on the types of spaces to choose a suitable enclosed
area for the study of acoustics.
b) Obtain approval from the management office and conduct visits to the case
study site.
c) Measure and produce the technical drawings such as floor plans, sections
and elevation digitally based on on-site measurements.
d) After standardizing the drawings, determine the grid line of 2m x 2m
e) Delegate tasks among group members and clarify on the method of taking
readings and using the tools and equipment before data collection begins.
f) Collect data based on the proper procedures (read on 3.3.3).
g) Observe and record the existing external and internal noise sources.
h) Compile and tabulate the data or reading.
i) Carry out calculation and analysis. Draw a conclusion or recommendations
at the end of the analysis.
3.3.3 Data Collection Procedures
a) Draw grid lines of 2m x 2m on the site floor plan to identify the position of
data collecting.
b) Stand at the intersection point of the grid and hold the measuring device at
1m from the ground.
c) Wait patiently until the readings shown on the device are stable coherent
with the surrounding noise and record it down.
d) Stand firm and prevent talking while taking readings.
e) Specify the noise source that might affect the readings.
f) Repeat the steps above for the rest of the intersection points.
g) Conduct the study for peak hour (9pm) and non-peak hour (5pm) to
analyze different acoustics condition at different hour.
Figure 5 : One meter measured from the floor level to detect the
surrounding noise
63
Zone A is the bread retail area
situated at the ground floor of
Donutes Café. It covered the
entrances, reception, staircase to
upper floor and kitchens.
A total of 23 intersection points are
covered in Zone A.
13325mm
15000mm
22378mm
2000mm
2000mm
Zone B and C are the upper floors of
the café whereby reading areas are
situated. It provides the customers a
place to enjoy the pastries or drinks,
chatting, reading, meeting and etc.
A total of 25 intersection points are
covered in Zone B and 12 points in
Zone C.
In a nutshell, there are a total of 60
points in these three zones.
64
3.4 Case Study
SS15, as one of the most happening hangout spots in the Klang Valley consists of large
variety of trendy cafes, F&B outlets, recreational and entertainment space. In the row of
shop houses where Donutes cafe is situated are a wide range of commercial activities
such as lottery, bistro, car workshops, pharmacy, clinics and etc.
3.5 Existing Noise Sources
Situated at the corner slot adjacent to one of the busiest main road of SS15, Donutes
café has received plenty of noise mainly from the vehicles on the road, the current on-
going MRT project, and the blasting music from opposite bistro (at night). The site itself
lack of vegetation as a buffer zone. There are no tall trees surrounding the premise nor
any high fencing exposing the building itself to the surrounding.
Figure 6: Location and surroundings of Donute Café
Figure 7: External noise source from the surroundings
65
3.5.1 External Noise
3.5.1.1 Site Context
Opposite the Donutes café is a mix-development building houses a lot
of F&B business and one of them is the Naughty Nuri’s Bistro. The
bistro blasts its music out loud and can be heard from a far distance.
Needless to say, it is a major noise to Donutes Café especially at
Zone B&C.
Figure 8: Naughty Nuri’s Bistro located at the front entrance of café
Figure 9: Nasi Kandar Pelita located at the rear façade of the café
3.5.1.2 Vehicles
The honking and vehicle accelerating noise from the vehicles at main
road can cause undesirable noise during the after work rush hours
(5pm to 7pm).
66
3.5.2 Internal Noise
3.5.2.1 Human Activities
Most of the noises come from human activities such as chit-chatting,
laughing, greeting and etc. In Zone A, there are mainly three sound
sources: the reception (trading, requesting, complaining), the kitchen
(pastries and food are made, washing, baking, talking between chefs)
and the café (coffee blending, making, serving).
Figure 10: Activities occur at the reception counter
On the upper floor (zone B&C), noise level is solely based on the
human activities coming from the reading areas.
Figure 11: Social activities happen at night
67
3.5.2.2 Speakers
Speakers are distributed throughout the two floors to enable
announcements from the counter/café below and soft music to be
played at the background.
Figure 12: Speakers found located at the ceiling
3.5.2.3 Air Conditioners
Units of Air Conditioners are the main and only type of ventilation
devices found in Donutes Café. They are mainly Ceiling Cassette Unit
and evenly distributed to cover most of the room. They are high in
power and produce relatively low noise.
Figure 13: Units of ceiling cassette air conditioner found on the ceiling
68
3.5.2.4 Electrical Appliances
Appliances such as bread stand that generate cool air to keep food
like sandwiches and salads fresh comes with a mini air conditioner.
Hence, the bread stand produce noise on its own.
Figure 14: Speakers found located at the ceiling
69
3.5.3 Locations of the noise sources
Figure 14: Identification of noise sources found at ground floor.
Air-conditioner
Speakers
Display Fridge
Human Activity
70 dB
70
Figure 15: Identification of noise sources found at first floor.
Air-conditioner
Speakers
Display Fridge
Human Activity
70 dB
71
3.6 Materials and Properties
The application of materials is an important factor in determining the quality of acoustics
in an environment, especially controlling the reverberation time. The materials act as a
medium, be it solids, liquids and gases that will affect the total effect of sound produced
in an enclosed space, known as room acoustics. The sound waves can undergo
reflection, absorption, diffusion and diffraction with different shapes, characteristics,
surface texture and etc. of a material.
Below are the list of existing materials found on the three zones of the case study:
No. Zone Materials Color Absorption coefficient Surface
texture500
Hz
2000
Hz
4000
Hz
1. A,B,C Human - 0.46 0.51 0.50 -
3.6.1 Furniture Material
No. Zone Materials Color Absorption coefficient Surface
texture500
Hz
2000
Hz
4000
Hz
1. B,C Woven texture seating
Woven seating
Cold
color
0.28 0.28 0.70 Semi -
Rough
Wood Frame
72
2. A,B Laminated wood bookshelves Brown 0.07 0.09 0.09 0.07
3. A Bread display stands White
0.01 0.02 0.02
Smooth
Marble
Laminated
Wood Sheets
Brown 0.07 0.04 0.04 Smooth
Glass Transp
arent
0.12 0.04 0.02 Smooth
Steel Silver 0.09 0.11 0.11 Smooth
73
3.6.2 Wall Material
No. Zone Materials Color Absorption coefficient Surface
texture500
Hz
200
0 Hz
400
0 Hz
1. A,B,C Concrete wall with Plaster finish Purple
Paint
0.05 0.09 0.09 Smooth
with
texture
2. A,B,C Wood Laminate Sheets Brown 0.07 0.04 0.04 Smooth
3. A,B,C Exposed Concrete Grey 0.02 0.02 0.05 Smooth
74
4. A,B,C Glass Trans-
parent
0.12 0.04 0.02 Smooth
5. B Mirror Reflec
tive
0.12 0.04 0.02 Smooth
6. A Wood Door Grey
Paint
0.06 0.10 0.10 Rough
7. A Laminated Granite Sheets Dark
Grey
0.02 0.05 0.05 Semi-
Rough
75
3.6.3 Ceiling Material
No. Zone Materials Color Absorption coefficient Surface
texture500
Hz
2000
Hz
4000
Hz
1. A,B,C Concrete Ceiling with Black paint finish Black 0.05 0.09 0.09 Rough
2. B Wood Laminate Sheets Wood 0.07 0.04 0.04 Smooth
76
3.6.4 Floor Material
No. Zone Materials Color Absorption coefficient Surface
texture500
Hz
2000
Hz
4000
Hz
1. A,B Porcelain Floor Tiles Light
Grey
0.01 0.02 0.02 Semi
Smooth
2. A,B Laminated Wood Flooring Light
Brown
0.03 0.05 0.05 Smooth
3. C Exposed Concrete Dark
Grey
0.15 0.02 0.02 Smooth
77
3.7 Acoustic Tabulation and Analysis
3.7.1 Sound Intensity Level (SIL)
3.7.1.1 Sound Meter Reading of Retail Area (Zone A)
3.7.1.1.1 Peak Period
Position of the hearer
Highest readings
The noise are caused around the
cashier / reception area
78
3.7.1.1.2 Non-peak Period
Position of the hearer
The noise are caused by the heavy
flow of vehicles from the road
outside during evening
Noise caused
around the cashier
/reception area
79
Sound Intensity Level Calculation for Zone A (Peak Hour)
Highest Readings: 75, 73, 72
SIL = 10 log (
𝐼𝐼𝐴𝐴
𝐼𝐼𝑜𝑜
)
75 = 10 log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12 )
7.5 = log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12)
107.5 =
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12
IA = 1 x10-12 x 107.5
= 3.1623 x 10-5
Itotal = (3.1623 x 10-5) + (1.9953 x 10-5) + (1.5849 x 10-5) = 6.7425 x 10-5
Hence, SIL = 10 log (
𝐼𝐼
𝐼𝐼𝑜𝑜
)
= 10 log (
6.7425 𝑋𝑋 10−5
1 𝑋𝑋 10−12 )
= 78.29 dB
Sound Intensity Level Calculation for Zone A (Non - Peak Hour)
Highest Readings: 68.2, 65 ,73
SIL = 10 log (
𝐼𝐼𝐴𝐴
𝐼𝐼𝑜𝑜
)
68.2 = 10 log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12 )
6.82 = log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12)
106.82 =
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12
IA = 1 x10-12 x 106.82
= 6.6069 x 10-6
Itotal = (6.6069 x 10-6) + (3.1623 x 10-6) + (1.9933 x 10-5) = 2.9722 x 10-5
Hence, SIL = 10 log (
𝐼𝐼
𝐼𝐼𝑜𝑜
)
= 10 log (
6.7425 𝑋𝑋 10−5
1 𝑋𝑋 10−12 )
= 74.73 dB
SIL = 10 log (
𝐼𝐼 𝐵𝐵
𝐼𝐼𝑜𝑜
)
73 = 10 log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12 )
7.3 = log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12)
107.3 =
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12
IB = 1 x10-12 x 107.3
= 1.9953 x 10-5
SIL = 10 log (
𝐼𝐼𝐶𝐶
𝐼𝐼𝑜𝑜
)
72 = 10 log (
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12 )
7.2 = log (
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12)
107.2 =
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12
IC = 1 x 10-12 x 107.2
= 1.5849 x 10-5
SIL = 10 log (
𝐼𝐼 𝐵𝐵
𝐼𝐼𝑜𝑜
)
65 = 10 log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12 )
6.5 = log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12)
106.5=
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12
IB = 1 x10-12 x 106.5
= 3.1623 x 10-6
SIL = 10 log (
𝐼𝐼𝐶𝐶
𝐼𝐼𝑜𝑜
)
73 = 10 log (
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12 )
7.3 = log (
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12)
107.3 =
𝐼𝐼𝐶𝐶
1 𝑋𝑋 10−12
IC = 1 x 10-12 x 107.3
= 1.9933 x 10-5
80
3.7.1.1.3 Analysis
The noise at the ground floor (Zone A, retail area) are
mainly caused by two sources: cashier area and vehicles.
Due to the L shaped nature of the retail area, the noise
that propagates mainly from the front part of the building
are not able to reach the area behind, leaving some
acoustic shadow*. Such area can be determined by the
sound reflection ray diagrams below:
Regardless peak or non-peak period, the propagation of
sound rays from the highest readings are not able to
reach the upper right of the retail zone.
The difference in the sound intensity level between the
peak and non-peak period of Zone A is small, 78.29dB –
74.73 dB = 3.56dB.
*An acoustic shadow or sound shadow is an area through which sound waves fail to propagate, due to
topographical obstructions or disruption of the waves via phenomena such as wind currents, buildings,
or sound barriers.
Figure 16: Sound Reflective Rays
diagram of Zone A during Peak Hours
Figure 17: Sound Reflective Rays diagram of
Zone A during Non-Peak Hours
81
3.7.1.2 Sound Meter Reading of Reading Area (Zone B & C)
3.7.1.2.1 Peak Period
Position of the hearer
Noise caused by the
chatting of a group of
people at the table
and its location near
to the entrance of the
staircase.
82
3.7.1.2.2 Non-peak Period
Position of the hearer
Loudest noise in the
room caused by
chatting and social
activities
83
Sound Intensity Level Calculation for Zone B & C (Peak Hour)
Highest Readings: 79.6, 79.6, 74.4
SIL = 10 log (
𝐼𝐼𝐴𝐴
𝐼𝐼𝑜𝑜
)
79.6 = 10 log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12 )
7.96 = log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12)
107.96 =
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12
IA = 1 x10-12 x 107.96
= 9.120 x 10-5
Itotal = (9.120 x 10-5) + (9.120 x 10-5) = 1.824 x 10-4
Hence, SIL = 10 log (
𝐼𝐼
𝐼𝐼𝑜𝑜
)
= 10 log (
1.824 𝑋𝑋 10−4
1 𝑋𝑋 10−12 )
= 82.61 dB
Sound Intensity Level Calculation for Zone B & C(Non - Peak Hour)
Highest Readings: 73.5, 75.7, 69.8
SIL = 10 log (
𝐼𝐼𝐴𝐴
𝐼𝐼𝑜𝑜
)
73.5 = 10 log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12 )
7.35 = log (
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12)
107.35 =
𝐼𝐼𝐴𝐴
1 𝑋𝑋 10−12
IA = 1 x10-12 x 107.35
= 2.2387 x 10-5
Itotal = (2.2387 x 10-5) + (3.7154 x 10-5) = 5.9541 x 10-5
Hence, SIL = 10 log (
𝐼𝐼
𝐼𝐼𝑜𝑜
)
= 10 log (
5.9541 𝑋𝑋 10−5
1 𝑋𝑋 10−12 )
= 77.75 dB
SIL = 10 log (
𝐼𝐼 𝐵𝐵
𝐼𝐼𝑜𝑜
)
79.6 = 10 log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12 )
7.96 = log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12)
107.96 =
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12
IB = 1 x 10-12 x 107.96
= 9.120 x 10-5
SIL = 10 log (
𝐼𝐼 𝐵𝐵
𝐼𝐼𝑜𝑜
)
75.7 = 10 log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12 )
7.57 = log (
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12)
107.57=
𝐼𝐼 𝐵𝐵
1 𝑋𝑋 10−12
IB = 1 x 10-12 x 107.57
= 3.7154 x 10-5
84
3.7.1.2.3 Analysis
The noise at the first floor (Zone B&C, reading area)
are caused mainly by human activities such as chit-
chat, meeting, discussing and etc. During the peak
hours, the noise propagate and penetrate through
Zone C leaving the far edge of Zone B less
uninterrupted whereas in the non-peak hours, noises
filled up the entire Zone B and acoustic shadowing
the far edge of Zone C.
We can hereby make a statement that the upper and
lowest edges of first floor are the quietest areas,
because the noise propagated from the main source
are the weakest.
The difference in the sound intensity level between the
peak and non-peak period of Zone B is small, 82.61dB –
77.75 dB = 4.86dB.
Figure 18: Sound Reflective Rays diagram of
Zone B&C during Peak Hours
Figure 19: Sound Reflective Rays diagram of
Zone B&C during Non-Peak Hours
85
3.7.2 Reverberation Time (RT)
Reverberation time is the time taken for a sound to decay by 60dB from its
original level. It depends on the distance between the surfaces of the room,
the absorption of the surfaces and also the frequency of the sound.
Volume of Zone A – Retail Area
V = 173m2 X 3.5m
=605.5m3
Volume of Zone B & C– Reading Area
V = 116m2 X 3.5m
=406m3
86
3.7.2.1 Zone A- Retail Area (Peak)
Peak Hours, Material Absorption Coefficient (500 Hz)
Component Material Surface Area
(m2) / Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 65.3 0.05 3.265
Wood Laminated Sheets 30.8 0.15 4.62
Exposed Concrete 28.1 0.02 0.562
Glass 27.6 0.10 2.76
Mirror 15.7 0.10 1.57
Wood Door 2.1 0.15 0.315
Laminated Granite Sheets 25.4 0.02 0.508
Ceiling Concrete with Black Paint Finish 64.8 0.05 3.24
Suspended Plasterboard 43.2 0.8 34.56
Floor Porcelain Floor Tiles 102.8 0.01 1.028
Laminated Wood Flooring 13 0.03 0.39
Bread
Display
Stands
Marble 10 0.01 0.1
Wood Laminated 18 0.15 2.7
Glass 50.8 0.10 5.08
Steel 39.8 0.09 3.582
Occupants 10 0.46 4.6
Total Absorption (A) 68.88
RT= 0.16 X V
A
RT= 0.16 X 406
68.88
RT= 0.94s
The Reverberation Time for the Retail
Area at 500Hz during peak hours is
0.94s. This does not fall within the
comfort reverberation.
87
Peak Hours, Material Absorption Coefficient (2000 Hz)
Component Material Surface Area
(m2) / Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 65.3 0.09 5.877
Wood Laminated Sheets 30.8 0.10 3.08
Exposed Concrete 28.1 0.02 0.562
Glass 27.6 0.05 1.38
Mirror 15.7 0.05 0.785
Wood Door 2.1 0.10 0.21
Laminated Granite Sheets 25.4 0.05 1.27
Ceiling Concrete with Black Paint Finish 64.8 0.09 5.832
Suspended Plasterboard 43.2 0.6 25.92
Floor Porcelain Floor Tiles 102.8 0.02 2.056
Laminated Wood Flooring 13 0.05 0.65
Bread
Display
Stands
Marble 18 0.02 0.36
Wood Laminated 50.8 0.10 5.08
Glass 39.8 0.05 1.99
Steel 10 0.11 1.1
Occupants 10 0.51 5.1
Total Absorption (A) 61.252
RT= 0.16 X V
A
RT= 0.16 X 406
61.252
RT= 1.06s
The Reverberation Time for the Retail
Area at 2000Hz during peak hours is
1.06s. This does not fall within the
comfort reverberation.
88
3.7.2.2 Zone A -Retail Area (Non-Peak)
Non-Peak Hours, Material Absorption Coefficient (500 Hz)
Component Material Surface Area
(m2) / Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 65.3 0.05 3.265
Wood Laminated Sheets 30.8 0.15 4.62
Exposed Concrete 28.1 0.02 0.562
Glass 27.6 0.10 2.76
Mirror 15.7 0.10 1.57
Wood Door 2.1 0.15 0.315
Laminated Granite Sheets 25.4 0.02 0.508
Ceiling Concrete with Black Paint Finish 64.8 0.05 3.24
Suspended Plasterboard 43.2 0.8 34.56
Floor Porcelain Floor Tiles 102.8 0.01 1.028
Laminated Wood Flooring 13 0.03 0.39
Bread
Display
Stands
Marble 10 0.01 0.1
Wood Laminated 18 0.15 2.7
Glass 50.8 0.10 5.08
Steel 39.8 0.09 3.582
Occupants 3 0.46 1.38
Total Absorption (A) 65.66
RT= 0.16 X V
A
RT= 0.16 X 406
65.66
RT= 0.99s
The Reverberation Time for the Retail
Area at 500Hz during non-peak hours
is 0.99s. This does not fall within the
comfort reverberation.
89
Non-Peak Hours, Material Absorption Coefficient (2000 Hz)
Component Material Surface Area
(m2) / Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 65.3 0.09 5.877
Wood Laminated Sheets 30.8 0.10 3.08
Exposed Concrete 28.1 0.02 0.562
Glass 27.6 0.05 1.38
Mirror 15.7 0.05 0.785
Wood Door 2.1 0.10 0.21
Laminated Granite Sheets 25.4 0.05 1.27
Ceiling Concrete with Black Paint Finish 64.8 0.09 5.832
Suspended Plasterboard 43.2 0.6 25.92
Floor Porcelain Floor Tiles 102.8 0.02 2.056
Laminated Wood Flooring 13 0.05 0.65
Bread
Display
Stands
Marble 18 0.02 0.36
Wood Laminated 50.8 0.10 5.08
Glass 39.8 0.05 1.99
Steel 10 0.11 1.1
Occupants 3 0.51 1.53
Total Absorption (A) 57.682
RT= 0.16 X V
A
RT= 0.16 X 406
57.682
RT= 1.13s
The Reverberation Time for the Retail
Area at 2000Hz during non-peak
hours is 1.13s. It is slightly higher
than the comfort reverberation which
is 1s.
90
3.7.2.3 Zone B & C -Reading Area (Peak)
Peak Hours, Material Absorption Coefficient (500 Hz)
Component Material Surface Area (m2)
/ Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 87 0.05 4.35
Wood Laminated Sheets 29.2 0.15 4.38
Exposed Concrete 32.8 0.02 0.656
Glass 65 0.10 6.5
Ceiling Concrete with Black Paint Finish 128.6 0.05 6.43
Wood Laminated Sheet 44.7 0.15 6.705
Floor Porcelain Floor Tiles 110.3 0.01 1.103
Laminated Wood Flooring 29.6 0.03 0.888
Exposed Concrete 33.5 0.15 5.025
Woven Texture
Seating
Woven Seating 74.7 0.28 20.916
Wood Frame 24 0.15 3.6
Bookshelves Laminated Wood 35.4 0.15 5.31
Table Laminated Wood 17.2 0.15 2.58
Occupants 60 0.46 27.6
Total Absorption (A) 96.043
RT= 0.16 X V
A
RT= 0.16 X 605.5
96.043
RT= 1.01s
The Reverberation Time for the
Reading Area at 500Hz during peak
hours is 1.01s. This does not fall
within the comfort reverberation.
91
Peak Hours, Material Absorption Coefficient (2000 Hz)
Component Material Surface Area (m2)
/ Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 87 0.09 7.83
Wood Laminated Sheets 29.2 0.10 2.92
Exposed Concrete 32.8 0.02 0.656
Glass 65 0.05 3.25
Ceiling Concrete with Black Paint Finish 128.6 0.09 11.574
Wood Laminated Sheet 44.7 0.10 4.47
Floor Porcelain Floor Tiles 110.3 0.02 2.206
Laminated Wood Flooring 29.6 0.05 1.48
Exposed Concrete 33.5 0.02 0.67
Woven Texture
Seating
Woven Seating 74.7 0.28 20.916
Wood Frame 24 0.10 2.4
Bookshelves Laminated Wood 35.4 0.10 3.54
Table Laminated Wood 17.2 0.10 1.72
Occupants 60 0.51 30.6
Total Absorption (A) 94.232
RT= 0.16 X V
A
RT= 0.16 X 605.5
94.232
RT= 1.03s
The Reverberation Time for the
Reading Area at 2000Hz during peak
hours is 1.03s. This does not fall
within the comfort reverberation.
92
3.7.2.4 Zone B & C -Reading Area (Non-Peak)
Non-Peak Hours, Material Absorption Coefficient (500 Hz)
Component Material Surface Area (m2)
/ Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 87 0.05 4.35
Wood Laminated Sheets 29.2 0.15 4.38
Exposed Concrete 32.8 0.02 0.656
Glass 65 0.10 6.5
Ceiling Concrete with Black Paint Finish 128.6 0.05 6.43
Wood Laminated Sheet 44.7 0.15 6.705
Floor Porcelain Floor Tiles 110.3 0.01 1.103
Laminated Wood Flooring 29.6 0.03 0.888
Exposed Concrete 33.5 0.15 5.025
Woven Texture
Seating
Woven Seating 74.7 0.28 20.916
Wood Frame 24 0.15 3.6
Bookshelves Laminated Wood 35.4 0.15 5.31
Table Laminated Wood 17.2 0.15 2.58
Occupants 20 0.46 9.2
Total Absorption (A) 77.643
RT= 0.16 X V
A
RT= 0.16 X 605.5
77.643
RT= 1.25s
The Reverberation Time for the
Reading Area at 500Hz during non-
peak hours is 1.25s. It is slightly
higher than the comfort reverberation
which is 1s.
93
Non-Peak Hours, Material Absorption Coefficient (2000 Hz)
Component Material Surface Area (m2)
/ Quantity
Absorption
Coefficient
Sound
Absorption
Wall Concrete with Plaster Finish 87 0.09 7.83
Wood Laminated Sheets 29.2 0.10 2.92
Exposed Concrete 32.8 0.02 0.656
Glass 65 0.05 3.25
Ceiling Concrete with Black Paint Finish 128.6 0.09 11.574
Wood Laminated Sheet 44.7 0.10 4.47
Floor Porcelain Floor Tiles 110.3 0.02 2.206
Laminated Wood Flooring 29.6 0.05 1.48
Exposed Concrete 33.5 0.02 0.67
Woven Texture
Seating
Woven Seating 74.7 0.28 20.916
Wood Frame 24 0.10 2.4
Bookshelves Laminated Wood 35.4 0.10 3.54
Table Laminated Wood 17.2 0.10 1.72
Occupants 20 0.51 10.2
Total Absorption (A) 73.832
RT= 0.16 X V
A
RT= 0.16 X 605.5
73.832
RT= 1.31s
The Reverberation Time for the
Reading Area at 2000Hz during non-
peak hours is 1.31s. It is slightly
higher than the comfort reverberation
which is 1s.
94
3.7.2.5 Analysis
We have calculated the Reverberation Times (RT) for retail area and
reading area in 500Hz and 2000Hz to find out the ranges of values in
different sound frequency. The results are tabulated into the table
below:
Area Period Range (sec)
Zone A
(Retail Area)
Peak 0.94 - 1.06
Non-peak 0.99 - 1.13
Zone B & C
(Reading Area)
Peak 1.01 -1.03
Non-peak 1.25 - 1.31
It can be concluded that the RT during the non-peak is higher than
peak hours due to the decreasing of number of occupants in the room.
This is because human is also a sound absorber that plays a part in
affecting the RT of a space.
We have identified that Donutes Café has applied a design strategy in
reducing its bouncing noises from the surface. The design of double
ceiling of the retail area has efficiently reduced the RT by using
suspended plasterboard as sound absorber.
Figure 20: Suspended plaster boards found above the retail area
Figure 21: Suspended wooden panels found above the reading area
95
According to the illustration, the sound ray from the noise source (the
cashier) propagated and hit the ceiling first. The remaining sound ray
that is not reflected will be stopped absorbed by the suspended ceiling
as a second layer of sound barrier. It has significantly reduce the RT
from 1.99 - 2.21 (calculated values without suspended ceiling) to
around 0.94 - 1.13, a total difference around 1.3s.
Figure 22: Illustration showed the use of suspended ceiling as
second barrier
96
3.7.3 Sound Reduction Index (SRI)
Component Material Color Finish Surface
Area (m2
)
Sound
Reduction
Index (R)
(500Hz)
Transmission
Coefficient,
(T)
T=
1
𝑙𝑙𝑙𝑙 𝑙𝑙−1 (
𝑅𝑅
10
)
Wall Gypsum plasterboard Dark Grey Semi-
Rough
○AE
A13.19
A○BE
A21.98
52 6.310 X 10-6
Window Glass Transparent Smooth A○BE
A8.56 26 2.512 X 10-3
Door Glass Transparent Smooth A○AE
A12.46
A○BE
A3.85
30 1 X 10-3
Air-conditioner
Speakers
Display Fridge
Human Activity
A
B
97
Figure 23: Elevation of Wall A
3.7.3.1.1 Wall A
𝑇𝑇𝑂𝑂 =
(𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2)
(𝐴𝐴1+ 𝐴𝐴2)
=
�6.310 𝑋𝑋 10−6 𝑋𝑋 13.19�+� 1 𝑋𝑋 10−3 𝑋𝑋 12.46�
( 13.19+12.46 )
= 4.890 X 10-4
R= 10 log (
1
𝑇𝑇𝑜𝑜
)
= 10 log (
1
4.890 𝑋𝑋 10−4 )
= 10 log (2044.99)
= 33.11dB
Hence, overall SRI= 33.11dB.
98
3.7.3.1.2 Wall B
𝑇𝑇𝑂𝑂 =
(𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2)+(𝑇𝑇3 𝑋𝑋 𝐴𝐴3)
(𝐴𝐴1+ 𝐴𝐴2+ 𝐴𝐴3)
=
�3.981 𝑋𝑋 10−5 𝑋𝑋 21.98�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 8.56�+(1 𝑋𝑋 10−3 𝑋𝑋 3.85)
( 21.98+8.56+ 3.85 )
= 7.627 X 10-4
R= 10 log (
1
𝑇𝑇𝑜𝑜
)
= 10 log (
1
7.627 𝑋𝑋 10−4 )
= 10 log (1311.13)
= 31.18dB
Hence, overall SRI= 30.45dB
Figure 24: Elevation of Wall B
99
3.7.3.2 Zone B & C – Reading Zone
Component Material Color Finish Surface
Area (m2
)
Sound
Reduction
Index (R)
(500Hz)
Transmission
Coefficient,
(T)
T=
1
𝑙𝑙𝑙𝑙 𝑙𝑙−1 (
𝑅𝑅
10
)
Wall Brick wall Purple
Paint
Smooth A○CE
A17.01
A○DE
A 7.67
54 3.981 X 10-6
Window Glass Transpa
rent
Smooth A○CE
A14.88
A○DE
A14.55
26 2.512 X 10-3
Door Glass Transpa
rent
Smooth A○CE
A3.30 30 1 X 10-3
Air-conditioner
Speakers
Display Fridge
Human Activity
C
D
100
3.7.3.2.1 Wall C
𝑇𝑇𝑂𝑂 =
(𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2)
(𝐴𝐴1+ 𝐴𝐴2)
=
�3.981 𝑋𝑋 10−6 𝑋𝑋 31.10�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 12.22�
( 31.10+12.22 )
= 7.115 X 10-4
R= 10 log (
1
𝑇𝑇𝑜𝑜
)
= 10 log (
1
7.115 X 10−4
)
= 10 log (1405.56)
= 31.48 dB
Hence, overall SRI= 31.48dB
Figure 25: Elevation of Wall C
101
3.7.3.2.2 Wall D
𝑇𝑇𝑂𝑂 =
(𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2)
(𝐴𝐴1+ 𝐴𝐴2)
=
�3.981 𝑋𝑋 10−6 𝑋𝑋 7.67�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 14.55�+ � 1 𝑋𝑋 10−3 𝑋𝑋 3.3�
( 14.55+3.3+.67)
= 1.563 X 10-3
R= 10 log (
1
𝑇𝑇𝑜𝑜
)
= 10 log (
1
1.563 X 10−3
)
= 10 log (639.80)
= 28.06dB
Hence, overall SRI= 28.06dB
Figure 26: Elevation of Wall D
102
3.7.3.3 Analysis
Based on the calculations obtained, the gypsum plasterboard walls on
the ground floor give an SRI of 33.11dB and 30.45dB for Wall A and
Wall B respectively. This relates back to the sound pressure level data
recorded with exterior data being 84.7dB and interior data 58dB.
Noise from the external surrounding transmitted into the ground floor
retail area can be reduced up to 26.7dB as it passes through the
medium that separated interior and exterior. On the other hand, the
brick walls on the first floor give an SRI of 31.48dB and 28.06
respectively to Wall C and Wall D. An abundance of glass used on
Wall D causes it to have a low reduction index. This relates back to
the sound pressure level data recorded with exterior data being 83dB
and interior data 63.6dB. Noise from the external surrounding
transmitted into the first floor reading area can be reduced up to 20.63
dB as it passes through the medium separating them.
One of the factor that contributes to the transmission of noise into the
internal space is through the leakage of sound via the gap present in
between glass doors and the walls. The presence of this gap is to
prevent the shatter of glass doors when it is being shut with a great
impact. However, this gap allows noise to leak into interior space,
increasing sound pressure level within the space.
Figure 27: Direct impact sound through gap between glass doors and walls.
103
3.8 Conclusion
From the analysis, it is evident that the sound level within the café is higher than the
recommended value of 45dB for restaurants. This is due to the placement of the building within
the site context of a chaotic environment: corner lot adjacent to the main road, with no vegetation
acting as buffering zone. At the same time, it is also located right beside SS15 Courtyard, which
houses numerous restaurants, contributing even more to the increase in sound level.
Besides that, the reverberation time of the space also does not fall into the comfortable zone of
1 second with the highest value being 1.31 seconds and the lowest value being 0.94 seconds.
This is due to the abundance of materials with low absorption coefficient like concrete, wood and
glass covering large percentages of the surface area within the café. Therefore, little sound is
absorbed by these materials and majority of the sound waves are reflected back into the internal
space causing multiple reflections from different surfaces within the café. However, this situation
can be improved by the usage of sound absorbing materials like carpets and curtains which will
reduce the sound energy as sound waves pass through it, facilitating reduction in reverberation
time which in turn reduces sound levels.
In addition to that, the sound reduction index of this café is also relatively low as compared to the
standard sound reduction index of a typical wall, which is 35dB. The highest value obtained is
33.11dB and lowest value being 28.06dB. This is mainly due to the extensive use of glass
enveloping the façade. In order to improve this situation, the thickness of the glass can be
increased or the area of glass covering the walls can be decreased. Moreover, a sound lock can
also be installed to prevent leakage of sound through penetrations of walls for services
installation purposes or gaps in between doors and walls.
In conclusion to the findings from this analysis, the acoustic condition in Donutes Café is below
average in terms of its functional space requirement. The high reverberation time and low sound
reduction levels require adequate changes to the materials covering surfaces within the café to
achieve a comfortable acoustical environment.
Figure 28: An example of achieving ideal reverberation time through usage of materials
with good absorbance.
104
4.0 BIBLIOGRAPHY

More Related Content

What's hot

An Acoustic Case Study on Calvary Convention Centre Presentation Slides
An Acoustic Case Study on Calvary Convention Centre Presentation SlidesAn Acoustic Case Study on Calvary Convention Centre Presentation Slides
An Acoustic Case Study on Calvary Convention Centre Presentation Slidesdouglasloon
 
PJCC AUDITORIUM COM.pptx
PJCC AUDITORIUM COM.pptxPJCC AUDITORIUM COM.pptx
PJCC AUDITORIUM COM.pptxSNEHALGUPTA13
 
Light as an architectural elemant1
Light as an architectural  elemant1Light as an architectural  elemant1
Light as an architectural elemant1Architecture
 
Acoustic design process
Acoustic design processAcoustic design process
Acoustic design processAbhishek kumar
 
Intro to auditorium design
Intro to auditorium designIntro to auditorium design
Intro to auditorium designDivya Kothari
 
Architectural acoustics
Architectural acoustics Architectural acoustics
Architectural acoustics Geeva Chandana
 
Project 1 : Auditorium - A Case Study of Acoustic Design
Project 1 : Auditorium - A Case Study of Acoustic DesignProject 1 : Auditorium - A Case Study of Acoustic Design
Project 1 : Auditorium - A Case Study of Acoustic DesignBryan Yeoh
 
a case study of acoustic design presentation
a case study of acoustic design presentationa case study of acoustic design presentation
a case study of acoustic design presentationYen Min Khor
 
Building Science 2 : A Case Study on Acoustic Design
Building Science 2 : A Case Study on Acoustic DesignBuilding Science 2 : A Case Study on Acoustic Design
Building Science 2 : A Case Study on Acoustic DesignNicole Foo
 
Sydney opera house acoustical features
Sydney opera house acoustical featuresSydney opera house acoustical features
Sydney opera house acoustical featuresRohit Bhatt
 
acoustic and viewing angle analysis of an auditorium building
acoustic and viewing angle analysis of an auditorium buildingacoustic and viewing angle analysis of an auditorium building
acoustic and viewing angle analysis of an auditorium buildingSaleh Ahmed
 
Daylighting slideshare
Daylighting slideshareDaylighting slideshare
Daylighting slideshareParween Karim
 
Case study college of architecture
Case study college of architecture Case study college of architecture
Case study college of architecture Abhijeet Roy
 
acoustical defects in enclosed space
acoustical defects in enclosed spaceacoustical defects in enclosed space
acoustical defects in enclosed spaceEjas Halu Mohammed
 

What's hot (20)

An Acoustic Case Study on Calvary Convention Centre Presentation Slides
An Acoustic Case Study on Calvary Convention Centre Presentation SlidesAn Acoustic Case Study on Calvary Convention Centre Presentation Slides
An Acoustic Case Study on Calvary Convention Centre Presentation Slides
 
PJCC AUDITORIUM COM.pptx
PJCC AUDITORIUM COM.pptxPJCC AUDITORIUM COM.pptx
PJCC AUDITORIUM COM.pptx
 
Light as an architectural elemant1
Light as an architectural  elemant1Light as an architectural  elemant1
Light as an architectural elemant1
 
Natural lighting
Natural lightingNatural lighting
Natural lighting
 
Acoustic design process
Acoustic design processAcoustic design process
Acoustic design process
 
Intro to auditorium design
Intro to auditorium designIntro to auditorium design
Intro to auditorium design
 
Architectural acoustics
Architectural acoustics Architectural acoustics
Architectural acoustics
 
Project 1 : Auditorium - A Case Study of Acoustic Design
Project 1 : Auditorium - A Case Study of Acoustic DesignProject 1 : Auditorium - A Case Study of Acoustic Design
Project 1 : Auditorium - A Case Study of Acoustic Design
 
a case study of acoustic design presentation
a case study of acoustic design presentationa case study of acoustic design presentation
a case study of acoustic design presentation
 
Day lighting
Day lightingDay lighting
Day lighting
 
Building Science 2 : A Case Study on Acoustic Design
Building Science 2 : A Case Study on Acoustic DesignBuilding Science 2 : A Case Study on Acoustic Design
Building Science 2 : A Case Study on Acoustic Design
 
Daylighting
DaylightingDaylighting
Daylighting
 
Theatre acoustics
Theatre acousticsTheatre acoustics
Theatre acoustics
 
Open air theater
Open air theaterOpen air theater
Open air theater
 
Sydney opera house acoustical features
Sydney opera house acoustical featuresSydney opera house acoustical features
Sydney opera house acoustical features
 
acoustic and viewing angle analysis of an auditorium building
acoustic and viewing angle analysis of an auditorium buildingacoustic and viewing angle analysis of an auditorium building
acoustic and viewing angle analysis of an auditorium building
 
Daylighting slideshare
Daylighting slideshareDaylighting slideshare
Daylighting slideshare
 
Kimbell art museum
Kimbell art museumKimbell art museum
Kimbell art museum
 
Case study college of architecture
Case study college of architecture Case study college of architecture
Case study college of architecture
 
acoustical defects in enclosed space
acoustical defects in enclosed spaceacoustical defects in enclosed space
acoustical defects in enclosed space
 

Viewers also liked

BUILDING TECHNOLOGY PROJECT 2 BRIEF
BUILDING TECHNOLOGY PROJECT 2 BRIEFBUILDING TECHNOLOGY PROJECT 2 BRIEF
BUILDING TECHNOLOGY PROJECT 2 BRIEFJoyeeLee0131
 
REPORT AND CALCULATION
REPORT AND CALCULATIONREPORT AND CALCULATION
REPORT AND CALCULATIONJoyeeLee0131
 
BUILDING TECHNOLOGY PROJECT 2 REPORT
BUILDING TECHNOLOGY PROJECT 2 REPORTBUILDING TECHNOLOGY PROJECT 2 REPORT
BUILDING TECHNOLOGY PROJECT 2 REPORTJoyeeLee0131
 
Bb science project 2
Bb science project 2Bb science project 2
Bb science project 2Pinkie95
 
BUILDING TECHNOLOGY PROJECT 1 BRIEF
BUILDING TECHNOLOGY PROJECT 1 BRIEFBUILDING TECHNOLOGY PROJECT 1 BRIEF
BUILDING TECHNOLOGY PROJECT 1 BRIEFJoyeeLee0131
 
Cognitive Mapping of Brickfield
Cognitive Mapping of Brickfield Cognitive Mapping of Brickfield
Cognitive Mapping of Brickfield JoyeeLee0131
 
Reaction Papers toward Theories of Architecture & Urbanism
Reaction Papers toward Theories of Architecture & UrbanismReaction Papers toward Theories of Architecture & Urbanism
Reaction Papers toward Theories of Architecture & UrbanismJoyeeLee0131
 
Building Science Project 1 Brief
Building Science Project 1 BriefBuilding Science Project 1 Brief
Building Science Project 1 BriefJoyeeLee0131
 
Acoustics India Private Limited | Buildingacoustics.in
Acoustics India Private Limited | Buildingacoustics.inAcoustics India Private Limited | Buildingacoustics.in
Acoustics India Private Limited | Buildingacoustics.inAcoustics India
 
Building Science II: Lighting Report
Building Science II: Lighting ReportBuilding Science II: Lighting Report
Building Science II: Lighting ReportEe Dong Chen
 
Organic Semiconductor Technology
Organic Semiconductor TechnologyOrganic Semiconductor Technology
Organic Semiconductor Technologysamiseecs
 
Organic solar cell
Organic solar cellOrganic solar cell
Organic solar cellAnish Das
 
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDEINTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDEno suhaila
 
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...Galala University
 
High-rise structural systems
High-rise structural systemsHigh-rise structural systems
High-rise structural systemsAkshay Revekar
 
LIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESLIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESShamba Sarkar
 

Viewers also liked (18)

BUILDING TECHNOLOGY PROJECT 2 BRIEF
BUILDING TECHNOLOGY PROJECT 2 BRIEFBUILDING TECHNOLOGY PROJECT 2 BRIEF
BUILDING TECHNOLOGY PROJECT 2 BRIEF
 
REPORT AND CALCULATION
REPORT AND CALCULATIONREPORT AND CALCULATION
REPORT AND CALCULATION
 
BUILDING TECHNOLOGY PROJECT 2 REPORT
BUILDING TECHNOLOGY PROJECT 2 REPORTBUILDING TECHNOLOGY PROJECT 2 REPORT
BUILDING TECHNOLOGY PROJECT 2 REPORT
 
Bb science project 2
Bb science project 2Bb science project 2
Bb science project 2
 
BUILDING TECHNOLOGY PROJECT 1 BRIEF
BUILDING TECHNOLOGY PROJECT 1 BRIEFBUILDING TECHNOLOGY PROJECT 1 BRIEF
BUILDING TECHNOLOGY PROJECT 1 BRIEF
 
TG Architects and Construction
TG Architects and Construction TG Architects and Construction
TG Architects and Construction
 
Cognitive Mapping of Brickfield
Cognitive Mapping of Brickfield Cognitive Mapping of Brickfield
Cognitive Mapping of Brickfield
 
Reaction Papers toward Theories of Architecture & Urbanism
Reaction Papers toward Theories of Architecture & UrbanismReaction Papers toward Theories of Architecture & Urbanism
Reaction Papers toward Theories of Architecture & Urbanism
 
Building Science Project 1 Brief
Building Science Project 1 BriefBuilding Science Project 1 Brief
Building Science Project 1 Brief
 
Acoustics India Private Limited | Buildingacoustics.in
Acoustics India Private Limited | Buildingacoustics.inAcoustics India Private Limited | Buildingacoustics.in
Acoustics India Private Limited | Buildingacoustics.in
 
Building Science II: Lighting Report
Building Science II: Lighting ReportBuilding Science II: Lighting Report
Building Science II: Lighting Report
 
Organic Semiconductor Technology
Organic Semiconductor TechnologyOrganic Semiconductor Technology
Organic Semiconductor Technology
 
Organic solar cell
Organic solar cellOrganic solar cell
Organic solar cell
 
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDEINTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
INTERIOR LIGHTING DESIGN A STUDENT'S GUIDE
 
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...
Architectural Design Concepts Approaches - كونسيبت التصميم المعمارى و الفكرة ...
 
High-rise structural systems
High-rise structural systemsHigh-rise structural systems
High-rise structural systems
 
Light & acoustics
Light & acousticsLight & acoustics
Light & acoustics
 
LIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURESLIGHT AND LIGHTING FIXTURES
LIGHT AND LIGHTING FIXTURES
 

Similar to BUILDING SCIENCE II: ACOUSTICS AND LIGHTING ANALYSIS OF DONUTES CAFE, SS15

Building Science 2
Building Science 2Building Science 2
Building Science 2Gertrude Lee
 
Building Science 1 (Project 1)
Building Science 1 (Project 1)Building Science 1 (Project 1)
Building Science 1 (Project 1)Soh Shing
 
Light report compiled
Light report compiledLight report compiled
Light report compiledPreston Liew
 
Building science ii project 1 compiled
Building science ii project 1 compiledBuilding science ii project 1 compiled
Building science ii project 1 compiledDevinchi
 
Lighting Analysis Project 1
Lighting Analysis Project 1Lighting Analysis Project 1
Lighting Analysis Project 1J-Sern Phua
 
Building science 2
Building science 2Building science 2
Building science 2Baddy Peigun
 
Report Bscience 2 Evaluation Performance Lighting & Acoustics
Report Bscience 2 Evaluation Performance Lighting & AcousticsReport Bscience 2 Evaluation Performance Lighting & Acoustics
Report Bscience 2 Evaluation Performance Lighting & AcousticsCrysmond Goh
 
Building Science II
Building Science IIBuilding Science II
Building Science IIIvy Yee
 
Bscience group proj
Bscience group projBscience group proj
Bscience group projjerryycc
 
Lighting & Acoustic Analysis
Lighting & Acoustic AnalysisLighting & Acoustic Analysis
Lighting & Acoustic AnalysisKelvin Fong
 
Building science 2 project 1
Building science 2 project 1Building science 2 project 1
Building science 2 project 1Jannah Jailani
 
Building Science II : Project 1
Building Science II : Project 1Building Science II : Project 1
Building Science II : Project 1Patricia Kong
 
Final bscience report compilation
Final bscience report compilationFinal bscience report compilation
Final bscience report compilationkerneng
 
Building Science Report
Building Science ReportBuilding Science Report
Building Science ReportLiew Hong Zhi
 
B science 2 project 1
B science 2 project 1B science 2 project 1
B science 2 project 1Ah Jun
 
Building Science II
Building Science IIBuilding Science II
Building Science IIjernjack
 

Similar to BUILDING SCIENCE II: ACOUSTICS AND LIGHTING ANALYSIS OF DONUTES CAFE, SS15 (20)

Building Science 2
Building Science 2Building Science 2
Building Science 2
 
Building Science 1 (Project 1)
Building Science 1 (Project 1)Building Science 1 (Project 1)
Building Science 1 (Project 1)
 
Light report compiled
Light report compiledLight report compiled
Light report compiled
 
Building science ii project 1 compiled
Building science ii project 1 compiledBuilding science ii project 1 compiled
Building science ii project 1 compiled
 
Lighting Analysis Project 1
Lighting Analysis Project 1Lighting Analysis Project 1
Lighting Analysis Project 1
 
LIGHTING
LIGHTINGLIGHTING
LIGHTING
 
Building science 2
Building science 2Building science 2
Building science 2
 
Report Bscience 2 Evaluation Performance Lighting & Acoustics
Report Bscience 2 Evaluation Performance Lighting & AcousticsReport Bscience 2 Evaluation Performance Lighting & Acoustics
Report Bscience 2 Evaluation Performance Lighting & Acoustics
 
Final report
Final reportFinal report
Final report
 
Building Science II
Building Science IIBuilding Science II
Building Science II
 
Bscience group proj
Bscience group projBscience group proj
Bscience group proj
 
Lighting & Acoustic Analysis
Lighting & Acoustic AnalysisLighting & Acoustic Analysis
Lighting & Acoustic Analysis
 
Bscience
BscienceBscience
Bscience
 
Building science 2 project 1
Building science 2 project 1Building science 2 project 1
Building science 2 project 1
 
Building Science II : Project 1
Building Science II : Project 1Building Science II : Project 1
Building Science II : Project 1
 
Final bscience report compilation
Final bscience report compilationFinal bscience report compilation
Final bscience report compilation
 
Final bscience report compilation
Final bscience report compilationFinal bscience report compilation
Final bscience report compilation
 
Building Science Report
Building Science ReportBuilding Science Report
Building Science Report
 
B science 2 project 1
B science 2 project 1B science 2 project 1
B science 2 project 1
 
Building Science II
Building Science IIBuilding Science II
Building Science II
 

More from JoyeeLee0131

Personal Values Statement
Personal Values StatementPersonal Values Statement
Personal Values StatementJoyeeLee0131
 
Presentation on Flat Roof Double in Safari Roof House
Presentation on Flat Roof Double in Safari Roof HousePresentation on Flat Roof Double in Safari Roof House
Presentation on Flat Roof Double in Safari Roof HouseJoyeeLee0131
 
Table of Content & Abstracts
Table of Content & AbstractsTable of Content & Abstracts
Table of Content & AbstractsJoyeeLee0131
 
Case Study Paper Topic Proposal
Case Study Paper Topic ProposalCase Study Paper Topic Proposal
Case Study Paper Topic ProposalJoyeeLee0131
 
B. structure project 2 brief august 2015
B. structure project 2 brief august 2015B. structure project 2 brief august 2015
B. structure project 2 brief august 2015JoyeeLee0131
 
B. structure project 1 brief august 2015
B. structure project 1 brief august 2015B. structure project 1 brief august 2015
B. structure project 1 brief august 2015JoyeeLee0131
 
Building Structure Project 1 Analysis Report
Building Structure Project 1 Analysis ReportBuilding Structure Project 1 Analysis Report
Building Structure Project 1 Analysis ReportJoyeeLee0131
 
Building Service Project 2 Case Study Report
Building Service Project 2 Case Study ReportBuilding Service Project 2 Case Study Report
Building Service Project 2 Case Study ReportJoyeeLee0131
 
Lembah Bujang Site Analysis
Lembah Bujang Site AnalysisLembah Bujang Site Analysis
Lembah Bujang Site AnalysisJoyeeLee0131
 
PANTHEON - Solid & Surface Construction
PANTHEON - Solid & Surface ConstructionPANTHEON - Solid & Surface Construction
PANTHEON - Solid & Surface ConstructionJoyeeLee0131
 
Building Construction Project 1 Brief
Building Construction Project 1 BriefBuilding Construction Project 1 Brief
Building Construction Project 1 BriefJoyeeLee0131
 
Building Construction Project 1 Shelter Report
Building Construction Project 1 Shelter ReportBuilding Construction Project 1 Shelter Report
Building Construction Project 1 Shelter ReportJoyeeLee0131
 
Measure Drawings Penang Lian Huat Company JAN 2015
Measure Drawings Penang Lian Huat Company JAN 2015Measure Drawings Penang Lian Huat Company JAN 2015
Measure Drawings Penang Lian Huat Company JAN 2015JoyeeLee0131
 
35 final jackroof detail r1 ready plot a1 titleblock landscape updated
35 final jackroof detail r1 ready plot a1 titleblock landscape updated35 final jackroof detail r1 ready plot a1 titleblock landscape updated
35 final jackroof detail r1 ready plot a1 titleblock landscape updatedJoyeeLee0131
 
34 final staircase detail ready plot a1 titleblock landscape updated
34 final staircase detail  ready plot a1 titleblock landscape updated34 final staircase detail  ready plot a1 titleblock landscape updated
34 final staircase detail ready plot a1 titleblock landscape updatedJoyeeLee0131
 
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updatedJoyeeLee0131
 
33 final window detail fg1 ready plot a1 titleblock landscape updated
33 final window detail fg1 ready plot a1 titleblock landscape updated33 final window detail fg1 ready plot a1 titleblock landscape updated
33 final window detail fg1 ready plot a1 titleblock landscape updatedJoyeeLee0131
 
Coutour & topography
Coutour & topographyCoutour & topography
Coutour & topographyJoyeeLee0131
 

More from JoyeeLee0131 (20)

Personal Values Statement
Personal Values StatementPersonal Values Statement
Personal Values Statement
 
Presentation on Flat Roof Double in Safari Roof House
Presentation on Flat Roof Double in Safari Roof HousePresentation on Flat Roof Double in Safari Roof House
Presentation on Flat Roof Double in Safari Roof House
 
Table of Content & Abstracts
Table of Content & AbstractsTable of Content & Abstracts
Table of Content & Abstracts
 
Case Study Paper Topic Proposal
Case Study Paper Topic ProposalCase Study Paper Topic Proposal
Case Study Paper Topic Proposal
 
Report
ReportReport
Report
 
B. structure project 2 brief august 2015
B. structure project 2 brief august 2015B. structure project 2 brief august 2015
B. structure project 2 brief august 2015
 
B. structure project 1 brief august 2015
B. structure project 1 brief august 2015B. structure project 1 brief august 2015
B. structure project 1 brief august 2015
 
Building Structure Project 1 Analysis Report
Building Structure Project 1 Analysis ReportBuilding Structure Project 1 Analysis Report
Building Structure Project 1 Analysis Report
 
Building Service Project 2 Case Study Report
Building Service Project 2 Case Study ReportBuilding Service Project 2 Case Study Report
Building Service Project 2 Case Study Report
 
Lembah Bujang Site Analysis
Lembah Bujang Site AnalysisLembah Bujang Site Analysis
Lembah Bujang Site Analysis
 
PANTHEON - Solid & Surface Construction
PANTHEON - Solid & Surface ConstructionPANTHEON - Solid & Surface Construction
PANTHEON - Solid & Surface Construction
 
Building Construction Project 1 Brief
Building Construction Project 1 BriefBuilding Construction Project 1 Brief
Building Construction Project 1 Brief
 
Building Construction Project 1 Shelter Report
Building Construction Project 1 Shelter ReportBuilding Construction Project 1 Shelter Report
Building Construction Project 1 Shelter Report
 
Measure Drawings Penang Lian Huat Company JAN 2015
Measure Drawings Penang Lian Huat Company JAN 2015Measure Drawings Penang Lian Huat Company JAN 2015
Measure Drawings Penang Lian Huat Company JAN 2015
 
35 final jackroof detail r1 ready plot a1 titleblock landscape updated
35 final jackroof detail r1 ready plot a1 titleblock landscape updated35 final jackroof detail r1 ready plot a1 titleblock landscape updated
35 final jackroof detail r1 ready plot a1 titleblock landscape updated
 
34 final staircase detail ready plot a1 titleblock landscape updated
34 final staircase detail  ready plot a1 titleblock landscape updated34 final staircase detail  ready plot a1 titleblock landscape updated
34 final staircase detail ready plot a1 titleblock landscape updated
 
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated
32 final window detail lw5 lw6 ready plot a1 titleblock landscape updated
 
33 final window detail fg1 ready plot a1 titleblock landscape updated
33 final window detail fg1 ready plot a1 titleblock landscape updated33 final window detail fg1 ready plot a1 titleblock landscape updated
33 final window detail fg1 ready plot a1 titleblock landscape updated
 
Coutour & topography
Coutour & topographyCoutour & topography
Coutour & topography
 
Studio+finl+skch
Studio+finl+skchStudio+finl+skch
Studio+finl+skch
 

Recently uploaded

办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书zdzoqco
 
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...Yantram Animation Studio Corporation
 
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...Rishabh Aryan
 
306MTAMount UCLA University Bachelor's Diploma in Social Media
306MTAMount UCLA University Bachelor's Diploma in Social Media306MTAMount UCLA University Bachelor's Diploma in Social Media
306MTAMount UCLA University Bachelor's Diploma in Social MediaD SSS
 
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档208367051
 
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Servicejennyeacort
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubaikojalkojal131
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degreeyuu sss
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVAAnastasiya Kudinova
 
How to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIHow to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIyuj
 
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一F La
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一F dds
 
Pharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfPharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfAayushChavan5
 
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档208367051
 
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一Fi L
 
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full NightCall Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full Nightssuser7cb4ff
 
shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back17lcow074
 
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...katerynaivanenko1
 
Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Rndexperts
 
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一z xss
 

Recently uploaded (20)

办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
办理卡尔顿大学毕业证成绩单|购买加拿大文凭证书
 
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...
Unveiling the Future: Columbus, Ohio Condominiums Through the Lens of 3D Arch...
 
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
DAKSHIN BIHAR GRAMIN BANK: REDEFINING THE DIGITAL BANKING EXPERIENCE WITH A U...
 
306MTAMount UCLA University Bachelor's Diploma in Social Media
306MTAMount UCLA University Bachelor's Diploma in Social Media306MTAMount UCLA University Bachelor's Diploma in Social Media
306MTAMount UCLA University Bachelor's Diploma in Social Media
 
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
 
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
PORTAFOLIO   2024_  ANASTASIYA  KUDINOVAPORTAFOLIO   2024_  ANASTASIYA  KUDINOVA
PORTAFOLIO 2024_ ANASTASIYA KUDINOVA
 
How to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AIHow to Empower the future of UX Design with Gen AI
How to Empower the future of UX Design with Gen AI
 
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
办理(宾州州立毕业证书)美国宾夕法尼亚州立大学毕业证成绩单原版一比一
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
 
Pharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdfPharmaceutical Packaging for the elderly.pdf
Pharmaceutical Packaging for the elderly.pdf
 
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
 
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一
办理学位证加州州立大学洛杉矶分校毕业证成绩单原版一比一
 
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full NightCall Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
 
shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back
 
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
 
Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025
 
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
办理(UC毕业证书)查尔斯顿大学毕业证成绩单原版一比一
 

BUILDING SCIENCE II: ACOUSTICS AND LIGHTING ANALYSIS OF DONUTES CAFE, SS15

  • 1. SCHOOLOFARCHITECTURE,BUILDING &DESIGN CENTREOFARCHITECTURESTUDIESINSOUTHEASTASIA (MASSA) BACHELOROFSCIENCE(HONOURS)(ARCHITECTURE) BUILDING SCIENCE2(BLD61303) LEEJO YEE LIM YEEQUN LING HUISIM LIEW QIAO LI CHUNG WEIJING CHANPINQI 0314880 0319121 0313855 0315671 0313789 0314676 TUTOR:MREDWINCHAN PROJECT1:LIGHTING &ACOUSTIC PERFORMANCEEVALUTION&DESIGN DONUTESSS15
  • 2. 1 | P a g e CONTENTS PAGE 1.0 INTRODUCTION 1.1 Aim and Objective 1.2 Site Information 1.2.1 Site Introduction 1.2.2 Site Selection Reasons 1.2.3 Technical Drawings 2.0 LIGHTING PERFORMANCE EVALUATION 2.1 Literature Review 2.1.1 Architectural Lighting 2.1.2 Daylight Factor 2.1.3 Lumen Method 2.2 Precedent Studies 2.2.1 Introduction 2.2.2 Daylighting 2.2.3 Artificial Lighting 2.2.4 Conclusion 2.3 Research Methodology 2.3.1 Light Measuring Equipment (Digital Lux Meter) 2.3.2 Data Collection Method 2.4 Case Study 2.4.1 Introduction 2.4.2 Zoning 2.5 Existing Lighting Conditions 2.5.1 Existing Light Fixture 2.5.2 Materials 2.6 Lighting Data Analysis 2.6.1 Daytime Lux Reading 2.6.1.1 Zone A 2.6.1.2 Zone B & C 2.6.2 Night Time Lux Reading 2.6.2.1 Zone A 2.6.2.2 Zone B & C 2.6.3 Observation and Discussion 2.7 Lighting Calculation Analysis 2.7.1 Daylight Factor Analysis 2.7.1.1 Zone A 2.7.1.2 Zone B 2.7.1.3 Zone C
  • 3. 2 | P a g e 2.7.2 Artificial Lighting Analysis 2.7.2.1 Zone A 2.7.2.2 Zone B 2.7.2.3 Zone C 2.8 Conclusion 3.0 ACOUSTIC PERFORMANCE EVALUATION 3.1 Literature Review 3.1.1 Architecture Acoustic 3.1.2 Sound Pressure Level (SPL) 3.1.3 Reverberation Time (RT) 3.1.4 Sound Reduction Index (SRI) 3.2 Precedent Studies 3.3 Research Methodology 3.3.1 Acoustic Measuring Equipment 3.3.1.1 Digital Sound Level Meter 3.3.1.2 Camera 3.3.1.3 Measuring Tape 3.3.2 Methodology 3.3.3 Data Collection Procedures 3.4 Case Study 3.5 Existing Noise Sources 3.5.1 External Noise 3.5.1.1 Site Context 3.5.1.2 Vehicles 3.5.2 Internal Noise 3.5.2.1 Human Activities 3.5.2.2 Speakers 3.5.2.3 Air Conditioners 3.5.2.4 Electrical Appliances 3.5.3 Location of the Noise Sources 3.6 Materials and Properties 3.6.1 Furniture Material 3.6.2 Wall Material 3.6.3 Ceiling Material 3.6.4 Floor Material 3.7 Acoustic Tabulation and Analysis 3.7.1 Sound Intensity Level (SIL) 3.7.1.1 Sound Meter Reading of Retail Area (Zone A) 3.7.1.1.1 Peak Period 3.7.1.1.2 Non-Peak Period 3.7.1.1.3 Analysis 3.7.1.2 Sound Meter Reading of Reading Area (Zone B&C)
  • 4. 3 | P a g e 3.7.1.2.1 Peak Period 3.7.1.2.2 Non-Peak Period 3.7.1.2.3 Analysis 3.7.2 Reverberation Time (RT) 3.7.2.1 Zone A-Retail (Peak) 3.7.2.2 Zone A-Retail Area ( Non-Peak) 3.7.2.3 Zone B & C- Reading Area (Peak) 3.7.2.4 Zone B & C- Reading Area ( Non-Peak ) 3.7.2.5 Analysis 3.7.3 Sound Reduction Index (SRI) 3.7.3.1 Zone A- Retail Area 3.7.3.1.1 Wall A 3.7.3.1.2 Wall B 3.7.3.2 Zone B & C- Reading Zone 3.7.3.2.1 Wall C 3.7.3.2.2 Wall D 3.7.3.3 Analysis 4.0 BIBLIOGRAPHY
  • 5. 4 | P a g e CHAPTER This chapter discuss on the aim and objective of this case study. Besides, this chapter also includes the introduction of site chosen and reason behind. 1I N T R O
  • 6. 5 | P a g e 1.0 INTRODUCTION 1.1 Aim and Objective This Project mainly focus on the lighting and acoustic study of the case study, Donutes SS15. Lighting design essential element in architectural design and interior design. Via lighting, solid volumes, colours, enclosed spaces and textures can only come to sight. Successive building are building where standard required amount of lighting is achieved. Acoustic design is an element which concerned with control of sound in spaces especially enclosed spaces. The requirement varies in accordance to various functions. It is crucial and essential to enhance the desired sound and to eliminate noise and undesired noise. This project is mainly exploring students to the way of designing a good lighting system and good acoustic system via a series of calculation. The objective of the lighting analysis is to understand the daylighting and lighting besides acoustic characteristic and acoustic requirement in the case study. Moreover, the study’s objective is to determine the characteristic and function of the day lighting and artificial lighting and sound & acoustic within the intended space. Finally is to critically report and analyse the space based on the data collected. 1.2 Site Information 1.2.1 Site Introduction Donutes, a 24-hours operating bakery and café that is located in the brim of SS15, Subang Jaya has emerged as the favourite gathering spot for local community, especially youngsters. Originally from Taiwan, the bakery brand has expanded and reached the shore of Malaysia in the year of 2013 when its first branch opened in Bandar Puteri Puchong, followed by the second franchise in Damansara (2014) and the third one in Subang Jaya (2015). We have chosen this café as our case study not only because its experience in designing a good café atmosphere and also the high human traffic in the building.
  • 7. 6 | P a g e Figure 1.2.1: Exterior of Donutes Café Figure 1.2.2: Outdoor smoking area Figure 1.2.3: Interior of the café first floor – reading area
  • 8. 7 | P a g e CHAPTER Lighting or illumination is the deliberate use of light to achieve a practical or aesthetic effect. Lighting includes the use of both artificial light sources like lamps and light fixtures, as well as natural illumination by capturing daylight. Daylighting using windows, skylights, or light shelves is sometimes used as the main source of light during daytime in buildings. 2L I G H T
  • 9. 8 | P a g e 2.1 Literature Review 2.1.1 Architecture Lighting Importance of Light in Architecture Light is the most important factor in the appreciation and understanding of Architecture. The relationship between light and architecture is grounded in the principles of physics; it is about energy and matter but in this particular case it also implies an emotional effect on people. The word of space is directly connected to the way light integrates with it. Light interact with us and environment by our vision, experience and interpretation on elements. Based on architecture study, in any dimension we can analyze such as space, material or colour, it is essentially dependent on the lighting situation that involves both the object and the observer. The dynamic daylight and the controlled artificial lighting are able to affect not only distinct physical measurable setting in a space, but also to instigate and provoke different visual experiences and moods. In addition, light can perceive different atmospheres in the same physical environment. It also integrates an element of basic relevance for design of spaces which plays a significant role in the discussion of quality in architecture. Natural Daylighting & Artificial Electrical Lighting Natural light has always been important for architects. In a way, architects sculpt buildings in order that the light can play off their different surfaces. If done well, space and light can evoke positive emotional responses in people. Although architects should always strive towards achieving a building which can draw in as much natural daylight as possible, it is almost impossible to go on without electrical lighting taking into consideration in design especially that it need to function both day and night. Moreover, certain building typologies and uses are not suitable for daylighting such as museums and galleries because exposure to natural light could damage the artifacts. It is an important understanding of limitations and opportunities in using natural daylighting as well as artificial lighting and be able to apply it architecturally to achieve the best performing building. Balance between Science & Art The balance of science & art will create a visually appropriate light scene accordingly to the character and use of a space .Sciences of light production and luminaire photometric are important as they are balanced with the artistic application of light as a medium in our built environment. Electrical lighting systems and daylighting systems should be integrated together while considering the impacts of it. There are three fundamental aspects in architectural lighting design for the illumination of building and spaces, including the aesthetic appeal, ergonomic aspect and energy efficiency of illumination. Aesthetic appeal focuses on the importance of illumination in retail environments. Ergonomic aspect is the measurement of how much function the lighting produces. Energy efficiency covers the issue of light wastage due to over illumination which could happen by unnecessary illumination of spaces or over providing light sources for aesthetic purposes. Each of these aspects are important when lighting works are carried out. It allows exploration on the attractiveness of the design by either providing subtle or strong lighting sources which creates different emotions for the users.
  • 10. 9 | P a g e 2.1.2 Daylight Factor It is a ratio that represents the amount of illumination available indoors relative to the illumination present outdoors at the same time under overcast skies. Daylight factor is usually used to obtain the internal natural lighting levels as perceived on a plane or surface, in order to determine the sufficiency of natural lighting for the users in a particular space to conduct their activities. It is also simply known to be the ratio of internal light level to external light level, as shown below: Daylight Factor, DF Indoor Illuminance, Ei Outdoor Illuminance, Eo Where, Ei = Illuminance due to daylight at a point on the indoor working planes, Eo = Simultaneous outdoor illuminance on a horizontal plane from an unobstructed hemisphere of overcast sky. Zone DF (%) Distribution Very bright > 6 Large (including thermal and glare problem) Bright 3 – 6 Good Average 1 -3 Fair Dark 0 – 1 Poor Table 2.1 Daylight Factor and Distribution.
  • 11. 10 | P a g e 2.1.3 Lumen Method Lumen method is used to determine the number of lamps that should be installed in a space. This can be done by calculating the total illuminance of the space based on the number of fixtures and determine whether or not that particular space has enough lighting fixtures. The number of lamps can be calculated by the formula below: Where, N = Number of lamps required E = Illuminance level required (Lux) A = Area at working plane height (m2) F = Average luminous flux from each lamp (lm) UF = Utilisation factor, an allowance for the light distribution of the luminaire and the room surfaces MF = Maintenance factor, an allowance for reduced light output because of deterioration and dirt Room Index, RI, is the ratio of room plan area to half wall area between the working and luminaire planes. Which can be calculated by: Where, L = Length of room W = Width of room Hm = Mounting height, the vertical distance between the working plane and the luminaire
  • 12. 11 | P a g e 2.2 PRECEDENT STUDY 2.2.1 Introduction Place: The Netherlands (Zwijndrecht) Building type: Secondary school Contact: Truus de Bruin-Hordijk (Faculty of Architecture, Technical University Delft, The Netherlands) Measurements were done in two classrooms. Classroom A, which is facing North-West, is experienced as dark by teachers. Another classroom B, which is facing South-East, is experienced bright by teachers. The judgement of the lighting expert is negative for classroom A and is neutral for classroom B. Both classrooms have grey walls and much furniture in it (Figure 2.2.1). Dimensions of the classrooms are: 7.2 x 7.2 x 3 m3. These are normal standard dimensions for primary and secondary classrooms in The Netherlands. Figure 2.2.1 Classroom B (window side and corridor side)
  • 13. 12 | P a g e 2.2.2 Daylighting The daylight factors were measured on 23 September 2008 by a (not complete) overcast sky. Table 2.2.1 and 2.2.2 show the daylight situation of the classrooms with daylight factors measured on a regular grid on table height (0.75 m). Table 2.2.3 shows the daylight factors in the middle on the blackboard and the outer left and right part of the blackboard. Classroom A has a green chalk board, whereas classroom B has a white board. The table proved that the daylight factor is decreased below 0.5% on the corridor side of classroom. Black Board Teacher desk 2.2 0.56 0.30 8.9 2.5 0.66 0.29 11.6 2.9 0.74 0.29 12.3 2.3 0.63 0.31 Table 2.2.1 The daylight factors (%) on student table height in classroom A. White Board Teacher desk 2.2 0.77 0.42 8.3 2.4 0.88 0.4 8.5 2.7 0.86 0.46 8.8 2.3 0.72 0.34 Table 2.2.2 The daylight factors (%) on student table height in classroom B. Board type Left Middle Right Black board 3 1 0.4 White board 2.4 0.82 0.38 Table 2.2.3 The daylight factors (%) on the boards in both classrooms. Window Zone Corridor Zone Window Zone Corridor Zone
  • 14. 13 | P a g e Figures below show luminance pictures, taken with a luminance camera with a fish-eye lens, from the back-side of the classrooms. It shows the situation for a sitting student with eye level on 1.2 m. The figures show the daylight situation with and without electrical lighting. Figure 2.2.4 Classroom A without electrical lighting Figure 2.2.5 Classroom A with electrical lighting Figure 2.2.6 Classroom B without electrical lighting
  • 15. 14 | P a g e Figure 2.2.7 Classroom B with electrical lighting 2.2.3 Artificial Lighting Both classrooms have six high-efficient surface-mounted luminaires with mirror reflector (Philips TCS298), each luminaire with one Philips TL5 HO 49 W/830 lamp (Figure 2.2.8) with electronic ballast. The illuminance on the work plane is 350 lx at full power. The school has replaced the old lamps and luminaires some years ago. The lamps were placed in two rows of three luminaires parallel to the window façade. The lamps were dimmable and have daylight sensors. There were also presence detectors in these classrooms (Figure 2.2.9). There was also asymmetric board lighting. Figure 2.2.8 Philips TL5 Lamp Figure 2.2.9 New Lighting Installation The luminance values in the windows of the classroom A are higher than in the windows of classroom B, because of the presence of trees outside the classroom B. That can explain the difference in the measured daylight factors, and so more energy savings are expected due to daylight sensors. The luminance images illustrate how the automatic dimming of the electric lighting can compensate an asymmetrical day-light distribution on the work plane (windows zone/corridor zone), and on the blackboard.
  • 16. 15 | P a g e 2.2.4 Conclusion In conclusion, natural light is important and can be affected by other side factor, for example the condition outside the window. Natural light provide enough light to work but not causing discomfort by the over exposed reflection on white surface like white painted wall and book. Direct light from the windows may perceive as uncomfortable when having a high contrast ratios, without electrical lighting. Therefore, most of the seat placed in the middle of class, due to the comfortable yet sufficient light. This case study can apply into our site. Café by consider the people occupancy according to light condition, furniture arrangement and artificial light placement. 2.3 RESEARCH METHODOLOGY 2.3.1 Light Measuring Equipment a) Lux Meter Lux meter also known as Light meter is used to measure the intensity of light illumination as distinguished by the human eye. The value gained does not correspond to the object value of energy radiated, as different wavelength within specific spectrum is perceived with varying sensitivity by the eye. Therefore, lux meter reading is reading that are taken in consideration of this variables. Most Lux meter registers brightness with an integrated photodetector. The photodetector is held perpendicular to the light source for optimal exposure. Readouts are presented via digital PhotodetectorLCD Display
  • 17. 16 | P a g e LCD display. Most Lux meter has measurement in variable range. The model of lux meter used in this case study is Lux LX-101. 2.3.2 Data Collection Method Procedure 1) Ground floor plan and first floor plan is measured and drawn. 2) 3 zones of case study area is determined and plotted with grid lines. 3) Measurement is taken at 1.5m and 1.0m high at each intersection points at different time (Daytime and Night time) 4) Procedure 3 is repeated. 1.5m 1.0m Figure 2.3.2.1 Position height of lux meter during measurement
  • 18. 17 | P a g e 2.4 CASE STUDY 2.4.1 Introduction Figure 2.4.1.1 Location of Donutes Cafe Figure 2.4.1.2 Exterior view of Donutes Cafe Donutes Café is one of the shops located at SS15, Subang Jaya. It is a 2-storey shop lot, with an open roof concept. The café is a place where mostly student’s hangout after classes and office staff relax after long hours of work. Peak hours of the café is usually during the night.
  • 19. 18 | P a g e The building itself is situated along a busy main road and surrounded by several high rise buildings, therefore noise pollution might occur at certain times. Part of the shop is designed with curtain walling. This allows natural daylighting to enter the space, besides being illuminated with artificial lightings. However it also produces glares into the shop during evening hours. The site has very minimal sun shading besides the surrounding buildings. This particular site was chosen as our case study due to its well known lighting design strategies used in the building and variety type of lighting, which allow us to expose to new knowledge. Figure 2.4.1.3 Interior Space during daytime Figure 2.4.1.4 Interior space at night
  • 20. 19 | P a g e 2.4.2 Zoning
  • 21. 20 | P a g e 2.5 EXISTING LIGHTING CONDITIONS LEGEND AB
  • 22. 21 | P a g e Figure 2.5.1 Ceiling Plan of Zone A (Colour referring to Light Specification List) AB
  • 23. 22 | P a g e LEGEND
  • 24. 23 | P a g e Figure 2.5.2 Ceiling Plan of Zone B and C (Colour referring to Light Specification List) AB AB
  • 25. 24 | P a g e Figure 2.5.3 Section A-A Figure 2.5.4 Section B-B
  • 26. 25 | P a g e 2.5.1 Existing Lighting Fixture Indication Image Light Type Philips Fluoresent Light Lamp Luminous Flux (lm) 1250 Specification Extra-long life of 50,000 hours Rated Colour Temperature 4100K Colour Rendering Index 98 Luminaire Type Open Fluorescent Strip light Wattage 8 Placement Hidden under ceiling or cabinet ( Display bread ) Light Type Leadare LED Bulb Lamp Luminous Flux (lm) 400 lm Specification E27 Life time approx. 25.000 hours. Rated Colour Temperature 5000K Colour Rendering Index 82 Luminaire Type Built in LED lamps Wattage 9 Placement Wall Lamp Light Type LED Downlight Lamp Luminous Flux (lm) 400 lm Specification Life time approx. 35.000 hours. Rated Colour Temperature 5000K Colour Rendering Index 82 Luminaire Type Built in LED lamps Downlight Wattage 40 Placement Ceiling Lamp Light Type Fluid Pendent Light Bulb Lamp Luminous Flux (lm) 800 Specification Life time approx. 4.000 hours Rated Colour Temperature 2700K Colour Rendering Index 100 Luminaire Type Decorative pendent Downward Wattage 60 Placement Ceiling Lamp Table 2.5.1.1 Light Specification
  • 27. 26 | P a g e 2.5.2 Materials Figure 2.5.2.1 Materials on Section A-A Figure 2.5.2.2 Materials on Section B-B
  • 28. 27 | P a g e No. Location Materials Color Reflectance Surface 1. 1 Table Brown 25 Semi -Rough 2. 1 Laminated wood bookshelves Brown 25 Smooth 3. 2,1,3,4 Bread display stands White 45 SmoothMarble Wood Laminated Sheets Brown 25 Smooth Glass Transpar ent 0 Smooth Steel Silver 12 Smooth Table 2.5.14 Furniture Material
  • 29. 28 | P a g e No. Location Materials Color Reflectance Surface 1. 5 Concrete wall with Plaster finish Purple Paint 6 Smooth with texture 2. 1 Wood Laminate Sheets Brown 25 Smooth Table 2.5.15 Wall Material
  • 30. 29 | P a g e 3. 6 Exposed Concrete Grey 35 Smooth 4. 3 Glass Trans- parent 0 Smooth Table 2.5.16 Wall Material
  • 31. 30 | P a g e 5. 7 Mirror Reflective 88 Smooth 7. 8 Laminated Granite Sheets Dark Grey 40 Semi- Rough Table 2.5.17 Wall Material
  • 32. 31 | P a g e No. Zone Materials Color Reflectance Surface 1. 9 Concrete Ceiling with Black paint finish Black 15 Rough 2. 2 Wood Laminate Sheets Wood 25 Smooth Table 2.5.18 Ceiling Material
  • 33. 32 | P a g e No. Zone Materials Color Reflectance Surface 1. 10 Porcelain Floor Tiles Light Grey 70 Semi Smooth 2. 2 Laminated Wood Flooring Light Brown 25 Smooth 3. 6 Exposed Concrete Dark Grey 39.5 Smooth Table 2.5.19 Floor Material
  • 34. 33 | P a g e 2.6 LIGHTING DATA ANALYIS 2.6.1 Daytime Lux Reading 2.6.1.1 Zone A Diagram 2.6.1 Daytime data result on Zone A . Data at 1.5m Height Data at 1.0m Height *
  • 35. 34 | P a g e Diagram 2.6.2. Daytime light contour on Zone A – 12pm Diagram 2.6.3 Daytime light contour on Zone A – 4pm The lux reading shown above shows the lux level during 4pm to 6pm interval. Partially, the artificial lighting were switched on during our data collection, but all of them are placing low to light up the floor. So, for the whole ground floor area, the main source of light during daytime is the sunlight. Referring to Diagram 2.6.1, the reading for the inner space are lower as it is deep inside and it rarely exposes to sunlight. The highest reading recorded is at the entrance area, where receive more sunlight through the glass sliding door.
  • 36. 35 | P a g e 2.6.1.1 Zone B and C Diagram 2.6.4 Daytime data result on Zone B and Zone C Data at 1.5m Height Data at 1.0m Height * Zone B Zone C
  • 37. 36 | P a g e Diagram 2.6.5 Daytime light contour on Zone B and Zone C Within Zone B, a distinctively high reading is recorded along the glasses area, as the glasses reflect the direct sunlight to the interior space. While the wall lights were switched on to light up the area of gridline C2 to C5 and B8 to B10, because of the daylight is blocked by the partition and furniture. Zone C is a semi-outdoor area where receives huge amount of sunlight as it is an open space and yet surrounded with glasses.
  • 38. 37 | P a g e 2.6.2 Night Time Lux Reading 2.6.2.1 Zone A Diagram 2.6.6 Night time data result on Zone A The readings taken at 9pm at the night, which fully dependant on artificial lightings inside. The higher lux readings are collected at the counter area (gridline C9-C11) as more artificial lightings are installed to provide brightness for clear vision for people to order or paying. Overall, the luminance level is above standard lux level, which is 200 lux (according to MS 1525). Data at 1.5m Height Data at 1.0m Height *
  • 39. 38 | P a g e Diagram 2.6.7 Night time light contour on Zone A Diagram 2.6.8 Ceiling Plan of Zone A According to Diagram 2.6.7, the area rendered with blue and purple area has lower luminance level while red and orange area has higher luminance level. As shown in Diagram 2.6.8, more downlights are installed around the counter and middle display area, which provide brighter environment and thus exceed standard 200 lux. While moving towards the kitchen area, the luminance level getting lower as that area is either walkway or corridor.
  • 40. 39 | P a g e 2.6.2.2 Zone B and C Diagram 2.6.9 Night time data result on Zone B and C The readings taken at 9pm at the night, which fully dependant on artificial lightings inside. At certain areas, the readings are extremely low, which may drop to 2 or 3 lux. This is because this area is main to be darker to create a more relaxing ambience. Overall, the luminance level is below the café standard luminance level, which is 200 lux. Data at 1.5m Height Data at 1.0m Height * Zone B Zone C
  • 41. 40 | P a g e Diagram 2.6.10 Night time light contour on Zone B and C
  • 42. 41 | P a g e Diagram 2.6.11 Ceiling plan of Zone B and C According to Diagram 2.6.10, the area rendered with blue and purple area has lower luminance level while red area has higher luminance level. As shown in Diagram 2.6.11, artificial lighting are all placing near to the table to provide brightness to only targeted place. Most of the light are decorative lighting and task lighting which did not provide general lighting to the whole area. Therefore, most of the area are rendered in blue and purple colour which is considered very poorly lid.
  • 43. 42 | P a g e 2.6.3 Observation and Discussion Observation 1 The readings of Zone A during daytime are lower than the readings collected during night time. Discussion 1 The walkway outside Zone A has affected the daylighting as greatly reduce the coming in sunlight because of the shaded. The artificial lighting is not bright compare to night time because ceiling downlight are only turning on at night. During nigh time, the space looks brighter as the light reflecting from ceiling and glasses. Hence, during daytime, the daylighting on Zone A is not sufficient. Figure 2.6.1 Daytime on Zone A Figure 2.6.2 Night time on Zone A
  • 44. 43 | P a g e Observation 2 In opposite, the readings of Zone B and C during daytime are higher than the readings collected during nigh time. Discussion 2 By exclusively using full glass window on the west, Zone B and C receives much sunlight compare to others. While during night time, decorative lightings and task lightings are used to focus on each table. Also, because of the dark colour of wall and ceiling to create a relaxing ambiance, the whole area looks dimmer. Figure 2.6.3 Zone B (Grid D to G) Figure 2.6.4 Night View on Zone B Figure 2.6.5 Night view on Zone C
  • 45. 44 | P a g e Observation 3 The readings collected at the inner space of Zone A, B and C are mostly under 200 lux, the standard illumination level. Discussion 3 The inner space area located far from the openings. The furniture and partitions are placing in layers and blocking much of the sunlight. Thus, they receive inadequate sunlight during daytime. Poor planning of placing artificial lightings was also darken down the area. Figure 2.6.6 Daytime on Zone B Figure 2.6.7 Daytime on Zone B Grid A-CGrid D-G
  • 46. 45 | P a g e Observation 4 Reading collected beside the glasses in Zone B are extremely high. Discussion 4 That area is good for lighting but the direct sunlight is causing discomfort to the sofa area. Although the shading panels are installed above and below the glasses, but when it comes to afternoon. Because of the heat and glare, people occupancy on daytime is lower compare to night time. Figure 2.6.4 Building West Facade Figure 2.6.5 Strong contrast of luminance level in Zone B
  • 47. 46 | P a g e 2.7 LIGHTING CALCULATION ANALYSIS 2.7.1 Daylight Factor Analysis 2.7.1.1 Zone A (Retail Area) Time Weather Luminance At 1m (1x) Average (1x) Luminance at 1.5m (1x) Average (1x) 4pm – 6pm Clear sky 28-77 62 lux 49 - 81 65.7 lux Table 2.5.1 Lux Reading at Zone A Average Lux Reading 4pm – 6pm 1m 62 1.5m 65.7 Average lux value 63.85 lux (64 lux) Table 2.5.2 Average Lux Value at Zone A Luminance Level Example 120,000 lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entire clear blue sky, midday 1000 – 2000 lux Typical over cast day, midday 400 lux Sunrise or sunset on clear day (ambient illumination) <200 lux Extreme of darkest storm clouds, midday 40 lux Fully overcast, sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise Table 2.5.3 Daylight intensity at different condition Date and Time 4pm – 6pm (26 April 2016) Average lux value reading 64 lux Daylight Factor Calculation Formula D = Standard direct sunlight 20,000 lux Calculation D=(64/20000) x 100% = 0.32% DF , % Distribution >6 Very Bright With thermal and glare problem 3 – 6 Bright 1 - 3 Average 0 - 1 Dark Table 2.5.4 Daylight Factor, DF Daylight factor at Zone A, retail area is relatively low. The calculation shown is 0.32 and which in the range of dark according to table provided in MS1525. This is due to the reason of the cantilevered floor above, which covers up the five-foot walkway. The prevention of direct sun exposure is purposely done to keep the indoor temperature low and thus keep the bread fresh. (E external) E internal x 100% E external (E internal)
  • 48. 47 | P a g e 2.7.1.2 Zone B (Reading Area) Time Weather Luminance At 1m (1x) Average (1x) Luminance at 1.5m (1x) Average (1x) 4pm – 6pm Clear sky 10-19840 186.7 lux 2-1020 1170.36 lux Table 2.5.5 Lux Reading at Zone B Average Lux Reading 4pm – 6pm 1m 186.7 1.5m 1170.36 Average lux value 678.5 lux Table 2.5.6 Average Lux Value at Zone B Luminance Level Example 120,000 lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entire clear blue sky, midday 1000 – 2000 lux Typical over cast day, midday 400 lux Sunrise or sunset on clear day (ambient illumination) <200 lux Extreme of darkest storm clouds, midday 40 lux Fully overcast, sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise Table 2.5.7 Daylight intensity at different condition Date and Time 4pm – 6pm (26 April 2016) Average lux value reading 678.5 lux Daylight Factor Calculation Formula D = Standard direct sunlight 20,000 lux Calculation D=(678.5/20000) x 100% = 2.89% DF , % Distribution >6 Very Bright With thermal and glare problem 3 – 6 Bright 1 - 3 Average 0 - 1 Dark Table 2.5.8 Daylight Factor, DF Daylight factor at zone B, reading area is considered high. The calculation shown is 2.89%, which in the range of bright according to the table provided in MS 1525. The existence of glass around the area had led high amount of lux to enter the interior space. This can save energy during daytime, as only partial artificial lights are needed. However, the glare created is unpreventable as its location is at the junction of turn in with existence of full wall of glass. Least shading device can be seen along the glass window. The customers will also experience the high amount of glare during the noontime, therefore shading device such as louvers is strongly recommended in this building. (E external) E internal x 100% E external (E internal)
  • 49. 48 | P a g e 2.7.1.3Zone C (Smoking Area) Time Weather Luminance At 1m (1x) Average (1x) Luminance at 1.5m (1x) Average (1x) 4pm – 6pm Clear sky 90-370 232.16 lux 50-530 201.9 lux Table 2.5.9 Lux Reading at Zone C Average Lux Reading 4pm – 6pm 1m 232.16 1.5m 201.9 Average lux value 217 lux Table 2.5.10 Average Lux Value at Zone C Luminance Level Example 120,000 lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entire clear blue sky, midday 1000 – 2000 lux Typical over cast day, midday 400 lux Sunrise or sunset on clear day (ambient illumination) <200 lux Extreme of darkest storm clouds, midday 40 lux Fully overcast, sunset/sunrise < 1 lux Extreme of darkest storm cloud, sunset/rise Table 2.5.11 Daylight intensity at different condition Date and Time 4pm – 6pm (26 April 2016) Average lux value reading 217 lux Daylight Factor Calculation Formula D = Standard direct sunlight 20,000 lux Calculation D=(217/20000) x 100% =1.0% DF , % Distribution >6 Very Bright With thermal and glare problem 3 – 6 Bright 1 - 3 Average 0 - 1 Dark Table 2.5.12 Daylight Factor, DF Daylight factor at zone C, smoking area is moderate but relatively low compare to reading area. The calculation shown is 1.0%, which is in the range of moderate according to the table provided inMS1525. It is a partially open space which location is facing northwest, thus allows high amount of lux to light up the place during daytime. (E external) E internal x 100% E external (E internal)
  • 50. 49 | P a g e 2.7.1 Zone A Lightings Dimensions of Space (L x W) (m) (6.0 x 6.5) / (6.8 x 15) Total Floor Area (m²) 107.8 Standard Illuminance Required (lux) 200 Type of Lighting Fixture Fluorescent Light (8W) LED E27 Bulb (9W) LED Downlight (12W) Number of Lighting Fixture / N 10 6 28 Lumen of Lighting Fixture / F (lm) 1250 700 900 Height of Luminaries (m) 3.5 2.0 3.5 Height of Working Plan (m) 1.3 1.3 1.3 Mounting Height / H (m) 2.2 0.7 2.2 Reflection Factors (%) Ceiling : 30.0 Wall : 10.0 Ceiling : 22.5 Wall : 10.0 Ceiling : 50.0 Wall : 10.0 Room Index 𝑅𝐼 = 𝐿 𝑥 𝑊 𝐻 𝑥 (𝐿 + 𝑊) = 6.0 x 6.5 / 2.2 x (6.0 + 6.5) = 1.4 , =6.8 x 15.0 / 2.2 x (6.8 + 15.0) =2.0 1.4 + 2.0 / 2.0 =1.7 =2.0 = 6.0 x 6.5 / 0.7 x (6.0 + 6.5) = 4.0 , =6.8 x 15.0 / 0.7 x (6.8 + 15.0) =6.7 4.0 + 6.7 / 2.0 =5.0 = 6.0 x 6.5 / 2.2 x (6.0 + 6.5) = 1.4 , =6.8 x 15.0 / 2.2 x (6.8 + 15.0) =2.1 1.4 + 2.1 / 2.0 =1.8 =2.0 Average Utilisation Factor / Refer Chart 0.29 0.72 0.78 Maintenance Factor 0.8 0.8 0.8 Average Illuminance /lux 1.5m: 281.0 Average Illuminance: (281+ 211.4) / 2=246.7 1.0m: 211.4 Number of Light Required 𝑁 = 𝐸 𝑥 𝐴 𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹 𝑁 = 200 𝑥 9.5m² 1250 𝑥 0.29 𝑥 0.8 = 6.5 = 7.0 𝑁 = 200 𝑥 12.3m² 700 𝑥 0.72 𝑥 0.8 = 6.0 𝑁 = 200 𝑥 86.05m² 900 𝑥 0.78 𝑥 0.8 = 30.6 = 31.0 Spacing requirement for light fitting S= 1.5 x Hm (Diffuse Light) 1.0 x Hm (Direct Light) S= 1.5 x 2.2 = 3.3m S= 1.0 x 0.7 = 0.7 m S= 1.0 x 3.5 = 3.5 m
  • 51. 50 | P a g e Total average lux in the retail area is 246.2 lux. The standard illuminance required for the room with retail purpose is 200 lux. It is bright-lit room where its illuminance exceeds 46.2 lux. As it is an area of bread display session of the bakery, it requires slightly higher illuminance to emphasize the cleanliness and food attractiveness. The area did a good job in creating a well-lit room for bread display as a variation of light fittings is seen throughout the area. However, it would be cost consuming in maintaining the light fittings. Instead of having 44 light bulbs of different type to achieve the required lux, suggestion of 38 LED down lights can be done in a cheaper way to light up the place.
  • 52. 51 | P a g e 2.7.2 Zone B Lightings Dimensions of Space (L x W) (m) (10 x 13) / (8 x 4) / (6 x 2.5) Total Floor Area (m²) 188.2 Standard Illumination Required (lux) 200 Type of Lighting Fixture Fluorescent Light (8W) LED E27 Bulb (9W) LED Downlight (12W) Fluid Pendant Light Bulb (60W) Number of Lighting Fixture / N 6 26 16 4 Lumen of Lighting Fixture / F (lm) 1250 700 900 800 Height of Luminaries (m) 3.0 2.0 3.0 2.3 Height of Working Plan (m) 0.45 0.7 0.7 0.45 Mounting Height / H (m) 2.55 1.3 2.3 1.85 Reflection Factors (%) Ceiling (Plywood) : 25.0 Wall (Grey paint) : 25.0 Ceiling (Grey paint) : 25.0 Wall (Grey paint) : 25.0 Ceiling (Plywood) : 25.0 Wall (Glass) : 0 Ceiling (White paint) : 70.0 Wall (Glass) : 0 Room Index 𝑅𝐼 = 𝐿 𝑥 𝑊 𝐻 𝑥 (𝐿 + 𝑊) = 10.0 x 13.0 / 2.55 x (10.0 + 13.0) = 2.2 , =8.0 x 4.0 / 2.55 x (8.0 + 4.0) =1.0 , =6.0 x 2.5 / 2.55 x (6.0 + 2.5) =0.7 , = 2.2 + 1.0 + 0.7 / 3.0 = 3.9 =4.0 = 10.0 x 13.0 / 1.3 x (10.0 + 13.0) = 4.3 , =8.0 x 4.0 / 1.3 x (8.0 + 4.0) =2.0 , =6.0 x 2.5 / 1.3 x (6.0 + 2.5) =1.35 , = 4.3 + 2 + 1.35 / 3.0 = 2.55 =3.0 = 10.0 x 13.0 / 2.3 x (10.0 + 13.0) = 2.45 , =8.0 x 4.0 / 2.3 x (8.0 + 4.0) =1.15 , =6.0 x 2.5 / 2.3 x (6.0 + 2.5) =0.77 , = 2.45+1.15+0.77/3.0 = 1.5 =2.0 = 10.0 x 13.0 / 1.85 x (10.0 + 13.0) = 3.0 , =8.0 x 4.0 / 1.85 x (8.0 + 4.0) =1.4 , =6.0 x 2.5 / 1.85 x (6.0 + 2.5) =1.0 , = 3.0 + 1.4 + 1.0 / 3.0 = 1.8 =2.0Average Utilisation Factor / Refer Chart 0.60 0.15 0.39 0.67 Maintenance Factor 0.8 0.8 0.8 0.8 Average Illuminance / Lux 1.5m: 49.7 Average Illuminance: (49.7 + 33) / 2= 41.35 1.0m: 33 Number of Light Required 𝑁 = 𝐸 𝑥 𝐴 𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹 𝑁 = 200 𝑥 12.6m² 1250 𝑥 0.15 𝑥 0.8 = 16.8 = 17.0 𝑁 = 200 𝑥 72.8m² 700 𝑥 0.6 𝑥 0.8 = 43.0 𝑁 = 200 𝑥 74.2m² 900 𝑥 0.67 𝑥 0.8 = 30.7 = 31.0 𝑁 = 200 𝑥 74.2m² 800 𝑥 0.39 𝑥 0.8 = 22.9 = 23.0 Spacing requirement for light fitting S= 1.5 x Hm (Diffuse Light) 1.0 x Hm (Direct Light) S= 1.5 x 2.55 = 3.8m S= 1.0 x 0.7 = 0.7m S= 1.0 x 2.3 = 2.3m S= 1.5 x 1.85 = 2.7m Data at 1.5m Height Data at 1.0m Height *
  • 53. 52 | P a g e Total average lux in the reading area is 41.35lux where standard lux required is 200 lux. It is a dimly lit up room which lacking 158.65lux. In order to achieve the required lux, 17 of LED Leadfare Bulb E27 lights, 11 of indirect fluorescent light E27, 23 more Fluid Pendant light bulb, and 31 more LED down light need to be added into the area to achieve 200lux. Instead of having 82 type of light fittings, 77 of fluid pendant light can used to achieve the standard illuminance and achieve the certain level of romantic and relaxing ambient.
  • 54. 53 | P a g e 2.7.3 Zone C Lightings Dimensions of Space (L x W) (m) (13.4 x 10.6) / (8.8 x 4.2) / (2.5 x 5.8) Total Floor Area (m²) 92.8 Standard Illumination Required (lux) 200 Type of Lighting Fixture LED Downlight (12W) Fluid Pendant Light Bulb (60W) Number of Lighting Fixture / N 7 5 Lumen of Lighting Fixture / F (lm) 800 900 Height of Luminaries (m) 2.3 4.0 Height of Working Plan (m) 0.45 0.45 Mounting Height / H (m) 1.85 3.55 Reflection Factors (%) Ceiling (Black paint) : 15.0 Wall (Glass) : 0 Ceiling (Black paint) : 15.0 Wall (Glass) : 0 Room Index 𝑅𝐼 = 𝐿 𝑥 𝑊 𝐻 𝑥 (𝐿 + 𝑊) = 13.4 x 10.6 / 3.55 x (13.4 + 10.6) = 2.0 , =8.8 x 4.2 / 3.55 x (8.8 + 4.2) =1.0 , =2.5 x 5.8 / 3.55 x (2.5 + 5.8) =1.0 , 2.0 + 1.0 + 1.0 / 3.0 = 1.0 = 13.4 x 10.6 / 1.85 x (13.4 + 10.6) = 3.0 , =8.8 x 4.2 / 1.85 x (8.8 + 4.2) =2 , =2.5 x 5.8 / 1.85 x (2.5 + 5.8) =1.0 , 3.0 + 2.0 + 1.0 / 3.0 = 3.0Average Utilisation Factor / Refer Chart 0.31 0.72 Maintenance Factor 0.8 0.8 Average Illuminance / Lux 1.5m: 18.3 Average Illuminance: (18.3 + 12.58) / 2= 15.45 1.0m: 12.58 Number of Light Required 𝑁 = 𝐸 𝑥 𝐴 𝐹 𝑥 𝑈𝐹 𝑥 𝑀𝐹 𝑁 = 200 𝑥 20.0m² 900 𝑥 0.72 𝑥 0.8 = 7.0 𝑁 = 200 𝑥 24.0m² 800 𝑥 0.31 𝑥 0.8 = 24.0 Spacing requirement for light fitting S= 1.5 x Hm (Diffuse Light) 1.0 x Hm (Direct Light) S= 1.0x 1.85 = 1.85m S= 1.5 x 3.5 = 5.25m
  • 55. 54 | P a g e Total average lux in smoking area is 15.45 lux. The standard illuminance required for the room is 200 lux. It is under insufficiency of light. The difference between the required lux with the current reading is 184.55 lux. It needs another 24 Fluid light bulbs to achieve the standard lux. The low reading is gained due to the large number of diffusing light around the area (Fluid Pendant Light). Low reflectance of the surrounding material also affect to the low reading, the dark colour ceiling paint and glass window.
  • 56. 55 | P a g e 2.8 CONCLUSION In conclusion, natural lighting in Donutes SS15 is relatively good based on the daylight factor calculation, which range around average to moderate. The sufficiency of day lighting strongly influenced by the openings provided. The strategic location at the corner lot had made Donutes SS15 a successful place for natural lighting. However, based on the data collected, there’s a huge contrast in daylight factor of the certain points although at the same floor area. This is caused by the existing partition and furniture being separated in to an enclosed area to form a semi-private space. Figure2.8.1Corner location of DonutesSS15 Figure2.8.2 Glass area along the edge of building (Reading Area)
  • 57. 56 | P a g e The low daylight factor reading is due to the existing sunshade along the five-foot walkway. The shaded area is then utilized to be a usable outdoor chatting area. However, this had blocked large amount of natural light to be able to strike through the interior. Therefore, some artificial lights are turned on during daytime to aid on the lighting effect, but overall appear dark inside except the bread display area with display lights on. Figure2.8.3 Glass area along the edge of building (Smoking Area) Figure2.8.4 Partition blocking the sun exposure to inner space Figure2.8.5 Contrast between lighting quality
  • 58. 57 | P a g e Artificial lighting is relatively considered good and had achieved the standard of 200lux at the ground floor retail area. Most of the artificial lights available in Donutes SS15 are located in low position and low in power. Therefore, there’re number of them but resulted in moderate lighting effect which is cost consuming and wasting energy. Most of the light fittings are ambient based, not meant for general lighting to bring out the ambience of a relaxing, eating and chatting area. Ordinary light fittings are not suitable for this building as it serves as a relaxing hang out area. It cannot be placed a standard spacing of lights like in factory. Therefore, the variation of light fittings is acceptable but only to be enhanced by improving the light bulb luminous flux, and increase the number. The placement of the luminaires should be able to follow the working planes, which are the table surface, allowing optional work to be carrying out in the comfortable light. Figure2.8.6 overhanging sunshade Figure2.8.7 Well-litted ground floor (Bread Display Area)
  • 59. 58 | P a g e Figure2.8.8 Dim lighted smoking area
  • 60. CHAPTER Sound is a mechanical wave which travels through a medium from one location to another. This motion through a medium occurs as one particle of the medium interacts with its neighbouring particle, transmitting the mechanical motion and corresponding energy to it. 3 S O U N D 55
  • 61. 3.0 ACOUSTIC PERFORMANCE EVALUATION 3.1 Literature Review 3.1.1 Architecture Acoustic Architecture acoustic is the branch of physic study that deals with the production, control, transmission, reception and effects of sound. The study of acoustics is important when designing a desirable atmosphere with concern and control of sound in spaces. The aim of the study is to preserve and enhanced desired sound in one space and on the other hand reduce or eliminate sound that interrupt with our activities known as noise. 3.1.2 Sound Pressure Level (SPL) It is a term most often used in measuring the magnitude of sound in decibels (dB). It is a relative quantity in that it is the ratio between the actual sound pressure and a fixed reference pressure. SPL of a place can be measure with a sound level meter weighted according to a specific frequency response pattern. Figure 1: Some typical sound pressure levels Calculation of sound pressure can be calculated with this formula: 56
  • 62. 3.1.3 Reverberation Time (RT) Reverberation is the prolongation of sound as a result of successive reflections in an enclosed space after the sound source is turned off. Reverberation time is defined as the length of time required for sound to decay 6 decibels from its initial level. However, a reverberation is different from than an echo where the former is perceived when the reflected sound wave reaches your ear in less than 0.1 second after the original sound wave. There is no time delay between the perception of the reflected sound wave and the original sound wave since the original sound wave is still held in memory. Reverberation Time (RT) is an important index for describing the acoustical quality of an enclosure. Formulas: 0.16 V A Where: RT= reverberation time (sec) V=volume of the room (cu.m) A=total absorption of room surfaces (sq.m sabins) 3.1.4 Sound Reduction Index (SRI) The Sound Reduction Index (SRI) or Transmission Loss TL of a partition measures the number of decibels lost when a sound of a given frequency is transmitted through the partition. RT = 57
  • 63. 3.2 Acoustics Precedent Studies THE MUSIC CAFÉ, AUGUST WILSON CENTRE. The café is located at sidewalk level, accessible directly from the street and from within the centre. It will function as a traditional museum café and sidewalk café during the day. A seating terrace is located outside and adjacent to the café. Wired for internet access and designed to accommodate a wide range of emerging technologies, the Café provides an electronic link to visitors worldwide. Modelled after New York’s BAM café or Joe’s Pub the Café is also designed to accommodate an on‐going menu of programs and to function as an alternative performance space for intimate performances with limited seating for jazz, spoken word, poetry and other new performance forms in a club setting at night. A portable stage and theatrical lighting will be imported to support such performances as required. This space is essential a large rectangular box with three glass sides, a hard floor, and sound absorbing treatment on the ceiling (although behind baffles and ductwork). It is evident design does recognizes the need for acoustical design elements, with hanging metal baffles and acoustical blanket over 80% of the underside of the floor structure above. Based on the use description provided by the architect, a reverberation time of approximately 1.0 second would be ideal. This would place the space somewhere between speech and speech/music use. According to the Architectural Acoustics: Principles and Design, a very high STC value (60+) between the Music Café and lobby would be desirable. This is important to both spaces, as a spoken word performance in the café could suffer if a large crowd was gathering in the lobby for a performance in the main theatre, while the lobby must remain quiet during a performance in the main theatre if patrons are entering or exiting the auditorium since a main set of doors is directly across from the café. Figure 2: August Wilson Centre Figure 3: Interior of the Music Café 58
  • 64. Figure 7.1.2 illustrates that the existing reverberation times are far from ideal. One important consideration, however, is that the manufacturer of the metal baffle ceiling system (Chicago Metallic) does not have acoustical data for the product. Therefore, the product has been omitted from the calculations. Including the baffles in the calculation would likely reduce the very high reverberation times at the lower frequencies, but it would also reduce the reverberation times at the higher frequencies which are already lower than ideal. Additional analysis of the sound transmission class (STC) on the wall between the café and the main lobby reveals a potential for unwanted noise transfer between the spaces. At 46, the calculated STC falls far below the ideal value of 60+. This problem is generated by the use of glass doors and partitions between the spaces. Changing the glass type from ½” tempered glass to ½” laminated glass improves the STC to 49, but this is only a marginal increase. To really improve this potentially negative situation, significant changes to the architecture are required. These changes may include changing the glass to another material such as wood or creating a small vestibule at the entrances. These changes, however, would significantly alter the architecture. It would be appropriate to point out the problem to the architect, but it is unlikely that the changes would be made. Improving the reverberation time is a much more realistic change. In order to do this, the metal baffles and acoustical blanket are eliminated, replacing them with floating fiberglass sound absorbing panels that are faced in perforated metal. This 59
  • 65. product is pictured in Figure 7.1.3. This change will most likely reduce cost by replacing two materials with one. Some changes were necessary in the location and type of HVAC diffusers and sprinkler heads. However, these changes should not require significant changes to the overall system. Figure 7.1.5 shows the new reverberation times based on 900 square feet of the new acoustical panels. Figure 7.1.4 shows the proposed layout of these panels. 60
  • 66. The new reverberation times are very close to the desired values. According to Architectural Acoustics: Principles and Design, optimum reverberation times at 125 hertz should be 1.3 times the ideal reverberation time at 500 hertz and a multiplier of 1.15 should be used at 250 hertz. These multipliers are used to correct for the fact that the human ear is less sensitive at lower frequencies. With these factors included, the new design is very near the target. The new ceiling system will provide superior acoustical performance at a reduced cost. CONCLUSION: In conclusion, noise reduction within a space can be achieved by two methods: improvement of reverberation time and also increasing the STC value. Reverberation time can be improved to ideal level through the use of absorptive materials on ceilings and surrounding walls, providing an optimum acoustical environment. On the other hand, STC values can be increased by changing the materials of the wall in between spaces, which reduces transmission of sound from a space to another, eliminating unwanted noise. 61
  • 67. 3.3 Research Methodology 3.3.1 Acoustic Measuring Equipment 3.3.1.1 Sound Level Meter The device is used to measure the sound level in a particular point in a space. The measured unit is in (dB). Figure 4: Front and rear view of the measuring device Specification Manufacturer LUTRON Lighting Model SL-4023SD Dimension/ Weight 245x68x45 mm / 489g without battery Range 30-130 dB Linearity +- 1.5 dB Grade of Accuracy Not assigned 3.3.1.2 Camera Camera is used to capture the source of noise such as mechanical devices, speakers, and existing activities and also to record the existing materials in the environment. 3.3.1.3 Measuring Tape It is used to determine the positions of the sound level meter from the ground level and also used to determine the 1.5m x 1.5m grid on the studying area. 62
  • 68. 3.3.2 Methodology a) Preliminary study on the types of spaces to choose a suitable enclosed area for the study of acoustics. b) Obtain approval from the management office and conduct visits to the case study site. c) Measure and produce the technical drawings such as floor plans, sections and elevation digitally based on on-site measurements. d) After standardizing the drawings, determine the grid line of 2m x 2m e) Delegate tasks among group members and clarify on the method of taking readings and using the tools and equipment before data collection begins. f) Collect data based on the proper procedures (read on 3.3.3). g) Observe and record the existing external and internal noise sources. h) Compile and tabulate the data or reading. i) Carry out calculation and analysis. Draw a conclusion or recommendations at the end of the analysis. 3.3.3 Data Collection Procedures a) Draw grid lines of 2m x 2m on the site floor plan to identify the position of data collecting. b) Stand at the intersection point of the grid and hold the measuring device at 1m from the ground. c) Wait patiently until the readings shown on the device are stable coherent with the surrounding noise and record it down. d) Stand firm and prevent talking while taking readings. e) Specify the noise source that might affect the readings. f) Repeat the steps above for the rest of the intersection points. g) Conduct the study for peak hour (9pm) and non-peak hour (5pm) to analyze different acoustics condition at different hour. Figure 5 : One meter measured from the floor level to detect the surrounding noise 63
  • 69. Zone A is the bread retail area situated at the ground floor of Donutes Café. It covered the entrances, reception, staircase to upper floor and kitchens. A total of 23 intersection points are covered in Zone A. 13325mm 15000mm 22378mm 2000mm 2000mm Zone B and C are the upper floors of the café whereby reading areas are situated. It provides the customers a place to enjoy the pastries or drinks, chatting, reading, meeting and etc. A total of 25 intersection points are covered in Zone B and 12 points in Zone C. In a nutshell, there are a total of 60 points in these three zones. 64
  • 70. 3.4 Case Study SS15, as one of the most happening hangout spots in the Klang Valley consists of large variety of trendy cafes, F&B outlets, recreational and entertainment space. In the row of shop houses where Donutes cafe is situated are a wide range of commercial activities such as lottery, bistro, car workshops, pharmacy, clinics and etc. 3.5 Existing Noise Sources Situated at the corner slot adjacent to one of the busiest main road of SS15, Donutes café has received plenty of noise mainly from the vehicles on the road, the current on- going MRT project, and the blasting music from opposite bistro (at night). The site itself lack of vegetation as a buffer zone. There are no tall trees surrounding the premise nor any high fencing exposing the building itself to the surrounding. Figure 6: Location and surroundings of Donute Café Figure 7: External noise source from the surroundings 65
  • 71. 3.5.1 External Noise 3.5.1.1 Site Context Opposite the Donutes café is a mix-development building houses a lot of F&B business and one of them is the Naughty Nuri’s Bistro. The bistro blasts its music out loud and can be heard from a far distance. Needless to say, it is a major noise to Donutes Café especially at Zone B&C. Figure 8: Naughty Nuri’s Bistro located at the front entrance of café Figure 9: Nasi Kandar Pelita located at the rear façade of the café 3.5.1.2 Vehicles The honking and vehicle accelerating noise from the vehicles at main road can cause undesirable noise during the after work rush hours (5pm to 7pm). 66
  • 72. 3.5.2 Internal Noise 3.5.2.1 Human Activities Most of the noises come from human activities such as chit-chatting, laughing, greeting and etc. In Zone A, there are mainly three sound sources: the reception (trading, requesting, complaining), the kitchen (pastries and food are made, washing, baking, talking between chefs) and the café (coffee blending, making, serving). Figure 10: Activities occur at the reception counter On the upper floor (zone B&C), noise level is solely based on the human activities coming from the reading areas. Figure 11: Social activities happen at night 67
  • 73. 3.5.2.2 Speakers Speakers are distributed throughout the two floors to enable announcements from the counter/café below and soft music to be played at the background. Figure 12: Speakers found located at the ceiling 3.5.2.3 Air Conditioners Units of Air Conditioners are the main and only type of ventilation devices found in Donutes Café. They are mainly Ceiling Cassette Unit and evenly distributed to cover most of the room. They are high in power and produce relatively low noise. Figure 13: Units of ceiling cassette air conditioner found on the ceiling 68
  • 74. 3.5.2.4 Electrical Appliances Appliances such as bread stand that generate cool air to keep food like sandwiches and salads fresh comes with a mini air conditioner. Hence, the bread stand produce noise on its own. Figure 14: Speakers found located at the ceiling 69
  • 75. 3.5.3 Locations of the noise sources Figure 14: Identification of noise sources found at ground floor. Air-conditioner Speakers Display Fridge Human Activity 70 dB 70
  • 76. Figure 15: Identification of noise sources found at first floor. Air-conditioner Speakers Display Fridge Human Activity 70 dB 71
  • 77. 3.6 Materials and Properties The application of materials is an important factor in determining the quality of acoustics in an environment, especially controlling the reverberation time. The materials act as a medium, be it solids, liquids and gases that will affect the total effect of sound produced in an enclosed space, known as room acoustics. The sound waves can undergo reflection, absorption, diffusion and diffraction with different shapes, characteristics, surface texture and etc. of a material. Below are the list of existing materials found on the three zones of the case study: No. Zone Materials Color Absorption coefficient Surface texture500 Hz 2000 Hz 4000 Hz 1. A,B,C Human - 0.46 0.51 0.50 - 3.6.1 Furniture Material No. Zone Materials Color Absorption coefficient Surface texture500 Hz 2000 Hz 4000 Hz 1. B,C Woven texture seating Woven seating Cold color 0.28 0.28 0.70 Semi - Rough Wood Frame 72
  • 78. 2. A,B Laminated wood bookshelves Brown 0.07 0.09 0.09 0.07 3. A Bread display stands White 0.01 0.02 0.02 Smooth Marble Laminated Wood Sheets Brown 0.07 0.04 0.04 Smooth Glass Transp arent 0.12 0.04 0.02 Smooth Steel Silver 0.09 0.11 0.11 Smooth 73
  • 79. 3.6.2 Wall Material No. Zone Materials Color Absorption coefficient Surface texture500 Hz 200 0 Hz 400 0 Hz 1. A,B,C Concrete wall with Plaster finish Purple Paint 0.05 0.09 0.09 Smooth with texture 2. A,B,C Wood Laminate Sheets Brown 0.07 0.04 0.04 Smooth 3. A,B,C Exposed Concrete Grey 0.02 0.02 0.05 Smooth 74
  • 80. 4. A,B,C Glass Trans- parent 0.12 0.04 0.02 Smooth 5. B Mirror Reflec tive 0.12 0.04 0.02 Smooth 6. A Wood Door Grey Paint 0.06 0.10 0.10 Rough 7. A Laminated Granite Sheets Dark Grey 0.02 0.05 0.05 Semi- Rough 75
  • 81. 3.6.3 Ceiling Material No. Zone Materials Color Absorption coefficient Surface texture500 Hz 2000 Hz 4000 Hz 1. A,B,C Concrete Ceiling with Black paint finish Black 0.05 0.09 0.09 Rough 2. B Wood Laminate Sheets Wood 0.07 0.04 0.04 Smooth 76
  • 82. 3.6.4 Floor Material No. Zone Materials Color Absorption coefficient Surface texture500 Hz 2000 Hz 4000 Hz 1. A,B Porcelain Floor Tiles Light Grey 0.01 0.02 0.02 Semi Smooth 2. A,B Laminated Wood Flooring Light Brown 0.03 0.05 0.05 Smooth 3. C Exposed Concrete Dark Grey 0.15 0.02 0.02 Smooth 77
  • 83. 3.7 Acoustic Tabulation and Analysis 3.7.1 Sound Intensity Level (SIL) 3.7.1.1 Sound Meter Reading of Retail Area (Zone A) 3.7.1.1.1 Peak Period Position of the hearer Highest readings The noise are caused around the cashier / reception area 78
  • 84. 3.7.1.1.2 Non-peak Period Position of the hearer The noise are caused by the heavy flow of vehicles from the road outside during evening Noise caused around the cashier /reception area 79
  • 85. Sound Intensity Level Calculation for Zone A (Peak Hour) Highest Readings: 75, 73, 72 SIL = 10 log ( 𝐼𝐼𝐴𝐴 𝐼𝐼𝑜𝑜 ) 75 = 10 log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 ) 7.5 = log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12) 107.5 = 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 IA = 1 x10-12 x 107.5 = 3.1623 x 10-5 Itotal = (3.1623 x 10-5) + (1.9953 x 10-5) + (1.5849 x 10-5) = 6.7425 x 10-5 Hence, SIL = 10 log ( 𝐼𝐼 𝐼𝐼𝑜𝑜 ) = 10 log ( 6.7425 𝑋𝑋 10−5 1 𝑋𝑋 10−12 ) = 78.29 dB Sound Intensity Level Calculation for Zone A (Non - Peak Hour) Highest Readings: 68.2, 65 ,73 SIL = 10 log ( 𝐼𝐼𝐴𝐴 𝐼𝐼𝑜𝑜 ) 68.2 = 10 log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 ) 6.82 = log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12) 106.82 = 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 IA = 1 x10-12 x 106.82 = 6.6069 x 10-6 Itotal = (6.6069 x 10-6) + (3.1623 x 10-6) + (1.9933 x 10-5) = 2.9722 x 10-5 Hence, SIL = 10 log ( 𝐼𝐼 𝐼𝐼𝑜𝑜 ) = 10 log ( 6.7425 𝑋𝑋 10−5 1 𝑋𝑋 10−12 ) = 74.73 dB SIL = 10 log ( 𝐼𝐼 𝐵𝐵 𝐼𝐼𝑜𝑜 ) 73 = 10 log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 ) 7.3 = log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12) 107.3 = 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 IB = 1 x10-12 x 107.3 = 1.9953 x 10-5 SIL = 10 log ( 𝐼𝐼𝐶𝐶 𝐼𝐼𝑜𝑜 ) 72 = 10 log ( 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12 ) 7.2 = log ( 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12) 107.2 = 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12 IC = 1 x 10-12 x 107.2 = 1.5849 x 10-5 SIL = 10 log ( 𝐼𝐼 𝐵𝐵 𝐼𝐼𝑜𝑜 ) 65 = 10 log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 ) 6.5 = log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12) 106.5= 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 IB = 1 x10-12 x 106.5 = 3.1623 x 10-6 SIL = 10 log ( 𝐼𝐼𝐶𝐶 𝐼𝐼𝑜𝑜 ) 73 = 10 log ( 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12 ) 7.3 = log ( 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12) 107.3 = 𝐼𝐼𝐶𝐶 1 𝑋𝑋 10−12 IC = 1 x 10-12 x 107.3 = 1.9933 x 10-5 80
  • 86. 3.7.1.1.3 Analysis The noise at the ground floor (Zone A, retail area) are mainly caused by two sources: cashier area and vehicles. Due to the L shaped nature of the retail area, the noise that propagates mainly from the front part of the building are not able to reach the area behind, leaving some acoustic shadow*. Such area can be determined by the sound reflection ray diagrams below: Regardless peak or non-peak period, the propagation of sound rays from the highest readings are not able to reach the upper right of the retail zone. The difference in the sound intensity level between the peak and non-peak period of Zone A is small, 78.29dB – 74.73 dB = 3.56dB. *An acoustic shadow or sound shadow is an area through which sound waves fail to propagate, due to topographical obstructions or disruption of the waves via phenomena such as wind currents, buildings, or sound barriers. Figure 16: Sound Reflective Rays diagram of Zone A during Peak Hours Figure 17: Sound Reflective Rays diagram of Zone A during Non-Peak Hours 81
  • 87. 3.7.1.2 Sound Meter Reading of Reading Area (Zone B & C) 3.7.1.2.1 Peak Period Position of the hearer Noise caused by the chatting of a group of people at the table and its location near to the entrance of the staircase. 82
  • 88. 3.7.1.2.2 Non-peak Period Position of the hearer Loudest noise in the room caused by chatting and social activities 83
  • 89. Sound Intensity Level Calculation for Zone B & C (Peak Hour) Highest Readings: 79.6, 79.6, 74.4 SIL = 10 log ( 𝐼𝐼𝐴𝐴 𝐼𝐼𝑜𝑜 ) 79.6 = 10 log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 ) 7.96 = log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12) 107.96 = 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 IA = 1 x10-12 x 107.96 = 9.120 x 10-5 Itotal = (9.120 x 10-5) + (9.120 x 10-5) = 1.824 x 10-4 Hence, SIL = 10 log ( 𝐼𝐼 𝐼𝐼𝑜𝑜 ) = 10 log ( 1.824 𝑋𝑋 10−4 1 𝑋𝑋 10−12 ) = 82.61 dB Sound Intensity Level Calculation for Zone B & C(Non - Peak Hour) Highest Readings: 73.5, 75.7, 69.8 SIL = 10 log ( 𝐼𝐼𝐴𝐴 𝐼𝐼𝑜𝑜 ) 73.5 = 10 log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 ) 7.35 = log ( 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12) 107.35 = 𝐼𝐼𝐴𝐴 1 𝑋𝑋 10−12 IA = 1 x10-12 x 107.35 = 2.2387 x 10-5 Itotal = (2.2387 x 10-5) + (3.7154 x 10-5) = 5.9541 x 10-5 Hence, SIL = 10 log ( 𝐼𝐼 𝐼𝐼𝑜𝑜 ) = 10 log ( 5.9541 𝑋𝑋 10−5 1 𝑋𝑋 10−12 ) = 77.75 dB SIL = 10 log ( 𝐼𝐼 𝐵𝐵 𝐼𝐼𝑜𝑜 ) 79.6 = 10 log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 ) 7.96 = log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12) 107.96 = 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 IB = 1 x 10-12 x 107.96 = 9.120 x 10-5 SIL = 10 log ( 𝐼𝐼 𝐵𝐵 𝐼𝐼𝑜𝑜 ) 75.7 = 10 log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 ) 7.57 = log ( 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12) 107.57= 𝐼𝐼 𝐵𝐵 1 𝑋𝑋 10−12 IB = 1 x 10-12 x 107.57 = 3.7154 x 10-5 84
  • 90. 3.7.1.2.3 Analysis The noise at the first floor (Zone B&C, reading area) are caused mainly by human activities such as chit- chat, meeting, discussing and etc. During the peak hours, the noise propagate and penetrate through Zone C leaving the far edge of Zone B less uninterrupted whereas in the non-peak hours, noises filled up the entire Zone B and acoustic shadowing the far edge of Zone C. We can hereby make a statement that the upper and lowest edges of first floor are the quietest areas, because the noise propagated from the main source are the weakest. The difference in the sound intensity level between the peak and non-peak period of Zone B is small, 82.61dB – 77.75 dB = 4.86dB. Figure 18: Sound Reflective Rays diagram of Zone B&C during Peak Hours Figure 19: Sound Reflective Rays diagram of Zone B&C during Non-Peak Hours 85
  • 91. 3.7.2 Reverberation Time (RT) Reverberation time is the time taken for a sound to decay by 60dB from its original level. It depends on the distance between the surfaces of the room, the absorption of the surfaces and also the frequency of the sound. Volume of Zone A – Retail Area V = 173m2 X 3.5m =605.5m3 Volume of Zone B & C– Reading Area V = 116m2 X 3.5m =406m3 86
  • 92. 3.7.2.1 Zone A- Retail Area (Peak) Peak Hours, Material Absorption Coefficient (500 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 65.3 0.05 3.265 Wood Laminated Sheets 30.8 0.15 4.62 Exposed Concrete 28.1 0.02 0.562 Glass 27.6 0.10 2.76 Mirror 15.7 0.10 1.57 Wood Door 2.1 0.15 0.315 Laminated Granite Sheets 25.4 0.02 0.508 Ceiling Concrete with Black Paint Finish 64.8 0.05 3.24 Suspended Plasterboard 43.2 0.8 34.56 Floor Porcelain Floor Tiles 102.8 0.01 1.028 Laminated Wood Flooring 13 0.03 0.39 Bread Display Stands Marble 10 0.01 0.1 Wood Laminated 18 0.15 2.7 Glass 50.8 0.10 5.08 Steel 39.8 0.09 3.582 Occupants 10 0.46 4.6 Total Absorption (A) 68.88 RT= 0.16 X V A RT= 0.16 X 406 68.88 RT= 0.94s The Reverberation Time for the Retail Area at 500Hz during peak hours is 0.94s. This does not fall within the comfort reverberation. 87
  • 93. Peak Hours, Material Absorption Coefficient (2000 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 65.3 0.09 5.877 Wood Laminated Sheets 30.8 0.10 3.08 Exposed Concrete 28.1 0.02 0.562 Glass 27.6 0.05 1.38 Mirror 15.7 0.05 0.785 Wood Door 2.1 0.10 0.21 Laminated Granite Sheets 25.4 0.05 1.27 Ceiling Concrete with Black Paint Finish 64.8 0.09 5.832 Suspended Plasterboard 43.2 0.6 25.92 Floor Porcelain Floor Tiles 102.8 0.02 2.056 Laminated Wood Flooring 13 0.05 0.65 Bread Display Stands Marble 18 0.02 0.36 Wood Laminated 50.8 0.10 5.08 Glass 39.8 0.05 1.99 Steel 10 0.11 1.1 Occupants 10 0.51 5.1 Total Absorption (A) 61.252 RT= 0.16 X V A RT= 0.16 X 406 61.252 RT= 1.06s The Reverberation Time for the Retail Area at 2000Hz during peak hours is 1.06s. This does not fall within the comfort reverberation. 88
  • 94. 3.7.2.2 Zone A -Retail Area (Non-Peak) Non-Peak Hours, Material Absorption Coefficient (500 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 65.3 0.05 3.265 Wood Laminated Sheets 30.8 0.15 4.62 Exposed Concrete 28.1 0.02 0.562 Glass 27.6 0.10 2.76 Mirror 15.7 0.10 1.57 Wood Door 2.1 0.15 0.315 Laminated Granite Sheets 25.4 0.02 0.508 Ceiling Concrete with Black Paint Finish 64.8 0.05 3.24 Suspended Plasterboard 43.2 0.8 34.56 Floor Porcelain Floor Tiles 102.8 0.01 1.028 Laminated Wood Flooring 13 0.03 0.39 Bread Display Stands Marble 10 0.01 0.1 Wood Laminated 18 0.15 2.7 Glass 50.8 0.10 5.08 Steel 39.8 0.09 3.582 Occupants 3 0.46 1.38 Total Absorption (A) 65.66 RT= 0.16 X V A RT= 0.16 X 406 65.66 RT= 0.99s The Reverberation Time for the Retail Area at 500Hz during non-peak hours is 0.99s. This does not fall within the comfort reverberation. 89
  • 95. Non-Peak Hours, Material Absorption Coefficient (2000 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 65.3 0.09 5.877 Wood Laminated Sheets 30.8 0.10 3.08 Exposed Concrete 28.1 0.02 0.562 Glass 27.6 0.05 1.38 Mirror 15.7 0.05 0.785 Wood Door 2.1 0.10 0.21 Laminated Granite Sheets 25.4 0.05 1.27 Ceiling Concrete with Black Paint Finish 64.8 0.09 5.832 Suspended Plasterboard 43.2 0.6 25.92 Floor Porcelain Floor Tiles 102.8 0.02 2.056 Laminated Wood Flooring 13 0.05 0.65 Bread Display Stands Marble 18 0.02 0.36 Wood Laminated 50.8 0.10 5.08 Glass 39.8 0.05 1.99 Steel 10 0.11 1.1 Occupants 3 0.51 1.53 Total Absorption (A) 57.682 RT= 0.16 X V A RT= 0.16 X 406 57.682 RT= 1.13s The Reverberation Time for the Retail Area at 2000Hz during non-peak hours is 1.13s. It is slightly higher than the comfort reverberation which is 1s. 90
  • 96. 3.7.2.3 Zone B & C -Reading Area (Peak) Peak Hours, Material Absorption Coefficient (500 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 87 0.05 4.35 Wood Laminated Sheets 29.2 0.15 4.38 Exposed Concrete 32.8 0.02 0.656 Glass 65 0.10 6.5 Ceiling Concrete with Black Paint Finish 128.6 0.05 6.43 Wood Laminated Sheet 44.7 0.15 6.705 Floor Porcelain Floor Tiles 110.3 0.01 1.103 Laminated Wood Flooring 29.6 0.03 0.888 Exposed Concrete 33.5 0.15 5.025 Woven Texture Seating Woven Seating 74.7 0.28 20.916 Wood Frame 24 0.15 3.6 Bookshelves Laminated Wood 35.4 0.15 5.31 Table Laminated Wood 17.2 0.15 2.58 Occupants 60 0.46 27.6 Total Absorption (A) 96.043 RT= 0.16 X V A RT= 0.16 X 605.5 96.043 RT= 1.01s The Reverberation Time for the Reading Area at 500Hz during peak hours is 1.01s. This does not fall within the comfort reverberation. 91
  • 97. Peak Hours, Material Absorption Coefficient (2000 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 87 0.09 7.83 Wood Laminated Sheets 29.2 0.10 2.92 Exposed Concrete 32.8 0.02 0.656 Glass 65 0.05 3.25 Ceiling Concrete with Black Paint Finish 128.6 0.09 11.574 Wood Laminated Sheet 44.7 0.10 4.47 Floor Porcelain Floor Tiles 110.3 0.02 2.206 Laminated Wood Flooring 29.6 0.05 1.48 Exposed Concrete 33.5 0.02 0.67 Woven Texture Seating Woven Seating 74.7 0.28 20.916 Wood Frame 24 0.10 2.4 Bookshelves Laminated Wood 35.4 0.10 3.54 Table Laminated Wood 17.2 0.10 1.72 Occupants 60 0.51 30.6 Total Absorption (A) 94.232 RT= 0.16 X V A RT= 0.16 X 605.5 94.232 RT= 1.03s The Reverberation Time for the Reading Area at 2000Hz during peak hours is 1.03s. This does not fall within the comfort reverberation. 92
  • 98. 3.7.2.4 Zone B & C -Reading Area (Non-Peak) Non-Peak Hours, Material Absorption Coefficient (500 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 87 0.05 4.35 Wood Laminated Sheets 29.2 0.15 4.38 Exposed Concrete 32.8 0.02 0.656 Glass 65 0.10 6.5 Ceiling Concrete with Black Paint Finish 128.6 0.05 6.43 Wood Laminated Sheet 44.7 0.15 6.705 Floor Porcelain Floor Tiles 110.3 0.01 1.103 Laminated Wood Flooring 29.6 0.03 0.888 Exposed Concrete 33.5 0.15 5.025 Woven Texture Seating Woven Seating 74.7 0.28 20.916 Wood Frame 24 0.15 3.6 Bookshelves Laminated Wood 35.4 0.15 5.31 Table Laminated Wood 17.2 0.15 2.58 Occupants 20 0.46 9.2 Total Absorption (A) 77.643 RT= 0.16 X V A RT= 0.16 X 605.5 77.643 RT= 1.25s The Reverberation Time for the Reading Area at 500Hz during non- peak hours is 1.25s. It is slightly higher than the comfort reverberation which is 1s. 93
  • 99. Non-Peak Hours, Material Absorption Coefficient (2000 Hz) Component Material Surface Area (m2) / Quantity Absorption Coefficient Sound Absorption Wall Concrete with Plaster Finish 87 0.09 7.83 Wood Laminated Sheets 29.2 0.10 2.92 Exposed Concrete 32.8 0.02 0.656 Glass 65 0.05 3.25 Ceiling Concrete with Black Paint Finish 128.6 0.09 11.574 Wood Laminated Sheet 44.7 0.10 4.47 Floor Porcelain Floor Tiles 110.3 0.02 2.206 Laminated Wood Flooring 29.6 0.05 1.48 Exposed Concrete 33.5 0.02 0.67 Woven Texture Seating Woven Seating 74.7 0.28 20.916 Wood Frame 24 0.10 2.4 Bookshelves Laminated Wood 35.4 0.10 3.54 Table Laminated Wood 17.2 0.10 1.72 Occupants 20 0.51 10.2 Total Absorption (A) 73.832 RT= 0.16 X V A RT= 0.16 X 605.5 73.832 RT= 1.31s The Reverberation Time for the Reading Area at 2000Hz during non- peak hours is 1.31s. It is slightly higher than the comfort reverberation which is 1s. 94
  • 100. 3.7.2.5 Analysis We have calculated the Reverberation Times (RT) for retail area and reading area in 500Hz and 2000Hz to find out the ranges of values in different sound frequency. The results are tabulated into the table below: Area Period Range (sec) Zone A (Retail Area) Peak 0.94 - 1.06 Non-peak 0.99 - 1.13 Zone B & C (Reading Area) Peak 1.01 -1.03 Non-peak 1.25 - 1.31 It can be concluded that the RT during the non-peak is higher than peak hours due to the decreasing of number of occupants in the room. This is because human is also a sound absorber that plays a part in affecting the RT of a space. We have identified that Donutes Café has applied a design strategy in reducing its bouncing noises from the surface. The design of double ceiling of the retail area has efficiently reduced the RT by using suspended plasterboard as sound absorber. Figure 20: Suspended plaster boards found above the retail area Figure 21: Suspended wooden panels found above the reading area 95
  • 101. According to the illustration, the sound ray from the noise source (the cashier) propagated and hit the ceiling first. The remaining sound ray that is not reflected will be stopped absorbed by the suspended ceiling as a second layer of sound barrier. It has significantly reduce the RT from 1.99 - 2.21 (calculated values without suspended ceiling) to around 0.94 - 1.13, a total difference around 1.3s. Figure 22: Illustration showed the use of suspended ceiling as second barrier 96
  • 102. 3.7.3 Sound Reduction Index (SRI) Component Material Color Finish Surface Area (m2 ) Sound Reduction Index (R) (500Hz) Transmission Coefficient, (T) T= 1 𝑙𝑙𝑙𝑙 𝑙𝑙−1 ( 𝑅𝑅 10 ) Wall Gypsum plasterboard Dark Grey Semi- Rough ○AE A13.19 A○BE A21.98 52 6.310 X 10-6 Window Glass Transparent Smooth A○BE A8.56 26 2.512 X 10-3 Door Glass Transparent Smooth A○AE A12.46 A○BE A3.85 30 1 X 10-3 Air-conditioner Speakers Display Fridge Human Activity A B 97
  • 103. Figure 23: Elevation of Wall A 3.7.3.1.1 Wall A 𝑇𝑇𝑂𝑂 = (𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2) (𝐴𝐴1+ 𝐴𝐴2) = �6.310 𝑋𝑋 10−6 𝑋𝑋 13.19�+� 1 𝑋𝑋 10−3 𝑋𝑋 12.46� ( 13.19+12.46 ) = 4.890 X 10-4 R= 10 log ( 1 𝑇𝑇𝑜𝑜 ) = 10 log ( 1 4.890 𝑋𝑋 10−4 ) = 10 log (2044.99) = 33.11dB Hence, overall SRI= 33.11dB. 98
  • 104. 3.7.3.1.2 Wall B 𝑇𝑇𝑂𝑂 = (𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2)+(𝑇𝑇3 𝑋𝑋 𝐴𝐴3) (𝐴𝐴1+ 𝐴𝐴2+ 𝐴𝐴3) = �3.981 𝑋𝑋 10−5 𝑋𝑋 21.98�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 8.56�+(1 𝑋𝑋 10−3 𝑋𝑋 3.85) ( 21.98+8.56+ 3.85 ) = 7.627 X 10-4 R= 10 log ( 1 𝑇𝑇𝑜𝑜 ) = 10 log ( 1 7.627 𝑋𝑋 10−4 ) = 10 log (1311.13) = 31.18dB Hence, overall SRI= 30.45dB Figure 24: Elevation of Wall B 99
  • 105. 3.7.3.2 Zone B & C – Reading Zone Component Material Color Finish Surface Area (m2 ) Sound Reduction Index (R) (500Hz) Transmission Coefficient, (T) T= 1 𝑙𝑙𝑙𝑙 𝑙𝑙−1 ( 𝑅𝑅 10 ) Wall Brick wall Purple Paint Smooth A○CE A17.01 A○DE A 7.67 54 3.981 X 10-6 Window Glass Transpa rent Smooth A○CE A14.88 A○DE A14.55 26 2.512 X 10-3 Door Glass Transpa rent Smooth A○CE A3.30 30 1 X 10-3 Air-conditioner Speakers Display Fridge Human Activity C D 100
  • 106. 3.7.3.2.1 Wall C 𝑇𝑇𝑂𝑂 = (𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2) (𝐴𝐴1+ 𝐴𝐴2) = �3.981 𝑋𝑋 10−6 𝑋𝑋 31.10�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 12.22� ( 31.10+12.22 ) = 7.115 X 10-4 R= 10 log ( 1 𝑇𝑇𝑜𝑜 ) = 10 log ( 1 7.115 X 10−4 ) = 10 log (1405.56) = 31.48 dB Hence, overall SRI= 31.48dB Figure 25: Elevation of Wall C 101
  • 107. 3.7.3.2.2 Wall D 𝑇𝑇𝑂𝑂 = (𝑇𝑇1 𝑋𝑋 𝐴𝐴1)+(𝑇𝑇2 𝑋𝑋 𝐴𝐴2) (𝐴𝐴1+ 𝐴𝐴2) = �3.981 𝑋𝑋 10−6 𝑋𝑋 7.67�+� 2.512 𝑋𝑋 10−3 𝑋𝑋 14.55�+ � 1 𝑋𝑋 10−3 𝑋𝑋 3.3� ( 14.55+3.3+.67) = 1.563 X 10-3 R= 10 log ( 1 𝑇𝑇𝑜𝑜 ) = 10 log ( 1 1.563 X 10−3 ) = 10 log (639.80) = 28.06dB Hence, overall SRI= 28.06dB Figure 26: Elevation of Wall D 102
  • 108. 3.7.3.3 Analysis Based on the calculations obtained, the gypsum plasterboard walls on the ground floor give an SRI of 33.11dB and 30.45dB for Wall A and Wall B respectively. This relates back to the sound pressure level data recorded with exterior data being 84.7dB and interior data 58dB. Noise from the external surrounding transmitted into the ground floor retail area can be reduced up to 26.7dB as it passes through the medium that separated interior and exterior. On the other hand, the brick walls on the first floor give an SRI of 31.48dB and 28.06 respectively to Wall C and Wall D. An abundance of glass used on Wall D causes it to have a low reduction index. This relates back to the sound pressure level data recorded with exterior data being 83dB and interior data 63.6dB. Noise from the external surrounding transmitted into the first floor reading area can be reduced up to 20.63 dB as it passes through the medium separating them. One of the factor that contributes to the transmission of noise into the internal space is through the leakage of sound via the gap present in between glass doors and the walls. The presence of this gap is to prevent the shatter of glass doors when it is being shut with a great impact. However, this gap allows noise to leak into interior space, increasing sound pressure level within the space. Figure 27: Direct impact sound through gap between glass doors and walls. 103
  • 109. 3.8 Conclusion From the analysis, it is evident that the sound level within the café is higher than the recommended value of 45dB for restaurants. This is due to the placement of the building within the site context of a chaotic environment: corner lot adjacent to the main road, with no vegetation acting as buffering zone. At the same time, it is also located right beside SS15 Courtyard, which houses numerous restaurants, contributing even more to the increase in sound level. Besides that, the reverberation time of the space also does not fall into the comfortable zone of 1 second with the highest value being 1.31 seconds and the lowest value being 0.94 seconds. This is due to the abundance of materials with low absorption coefficient like concrete, wood and glass covering large percentages of the surface area within the café. Therefore, little sound is absorbed by these materials and majority of the sound waves are reflected back into the internal space causing multiple reflections from different surfaces within the café. However, this situation can be improved by the usage of sound absorbing materials like carpets and curtains which will reduce the sound energy as sound waves pass through it, facilitating reduction in reverberation time which in turn reduces sound levels. In addition to that, the sound reduction index of this café is also relatively low as compared to the standard sound reduction index of a typical wall, which is 35dB. The highest value obtained is 33.11dB and lowest value being 28.06dB. This is mainly due to the extensive use of glass enveloping the façade. In order to improve this situation, the thickness of the glass can be increased or the area of glass covering the walls can be decreased. Moreover, a sound lock can also be installed to prevent leakage of sound through penetrations of walls for services installation purposes or gaps in between doors and walls. In conclusion to the findings from this analysis, the acoustic condition in Donutes Café is below average in terms of its functional space requirement. The high reverberation time and low sound reduction levels require adequate changes to the materials covering surfaces within the café to achieve a comfortable acoustical environment. Figure 28: An example of achieving ideal reverberation time through usage of materials with good absorbance. 104