Series RSM Room StatusMonitor Hands-On Training      The materials included in this compilation are for the use of Dwyer I...
Series RSM Hands-OnSetup ofTypicalApplication     RSM Room Status Monitor                   0.135”                     WC ...
Monitoring ScreenSilence buttonMenu buttonReset button          Negative Room                     - 0.0700”WC             ...
Main Menu ScreenUnitRoom                             MENUAlarm              Unit               Room                    0.1...
Unit Setup ScreenPasswordProtection                              SETUP UNIT  Locks out          Password                  ...
Room Setup ScreenRoom type:  Negative                         SETUP ROOM  Positive        Room Type       Negative Room  N...
Room Mode ScreenRoom Mode:  Occupied                          ROOM MODE  No Isolation        Please SET the Room ModeIf “N...
Alarm Setup ScreenMute Time Out: Maximum time alarm can be           ALARM SETUP                  Latch Alarm        Yes  ...
Monitoring ScreenClick Door toOpen and Close                            Door Open                      Negative Room      ...
Calibration ScreenPush-buttonZero and Span                         CALIBRATION                          Negative Room     ...
QuestionsTo order a free catalog or for more information contact;        Dwyer Instruments, Inc., P.O. Box 373,           ...
Upcoming SlideShare
Loading in...5
×

Series RSM Training

318

Published on

The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc.
©Copyright 2011 Dwyer Instruments, Inc.

Published in: Business, Technology
0 Comments
0 Likes
Statistics
Notes
  • Be the first to comment

  • Be the first to like this

No Downloads
Views
Total Views
318
On Slideshare
0
From Embeds
0
Number of Embeds
0
Actions
Shares
0
Downloads
0
Comments
0
Likes
0
Embeds 0
No embeds

No notes for slide
  • Silence: Shuts off audible alarmMenu: Access to Main Menu functionsReset: Resets the alarm condition if the unit is in “Latched” mode
  • Setup for 1. Password Protection, 2. Analog Output, 3. Engineering Units, 4. Display Averaging (dampening)Dampening provides a steadier display output
  • Room type box will change depending on the lower and upper limits. If both entries are positive, the room will be a Positive Room. If both are negative, the room will be a Negative Room and if the lower limit is negative and the Upper Limit is positive the room will be a Neutral Room.Operator Password:Security to limit availability of “Occupied/No Isolation” setting (“No Isolation” is for unoccupied rooms that require no alarming) This setting is available by clicking on the Room Type text from the Monitoring Screen
  • Accessible by clicking on Room Type text (Negative, Positive, or Neutral) from the Monitoring Screen. Occupied: standard operation. No Isolation: all alarms are disabled regardless of pressure condition. Useful when room is unoccupied and requires no alarming
  • Latch Alarm: When activated, requires acknowledgement on Monitoring Screen to clear the alarm state.Door Alarm Input: If door status switch is installed, selecting “Yes” will add the intermediate Yellow color to the Monitoring screen when the door is open and the pressure is still within limits.Volume: 1-4. 4 is the loudest (85 db)
  • Must be within 5% of zero and full scale for calibration to be accurate
  • Series RSM Training

    1. 1. Series RSM Room StatusMonitor Hands-On Training The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2011 Dwyer Instruments, Inc
    2. 2. Series RSM Hands-OnSetup ofTypicalApplication RSM Room Status Monitor 0.135” WC START!
    3. 3. Monitoring ScreenSilence buttonMenu buttonReset button Negative Room - 0.0700”WC 0.135”Room Type WCPressure Limits -0.1000 -0.0500 Silence Menu ResetActual Pressure
    4. 4. Main Menu ScreenUnitRoom MENUAlarm Unit Room 0.135”BACnet Alarm WC BACnetSelf Test Self Test Calibration BackCalibration
    5. 5. Unit Setup ScreenPasswordProtection SETUP UNIT Locks out Password protection Yes No Change everything Analog Output 0.135”4-20 0-5 0-10 except “Silence” WC Eng. Unit “WC Pa mmWC button Display Averaging 5 Secs Save & Exit Cancel
    6. 6. Room Setup ScreenRoom type: Negative SETUP ROOM Positive Room Type Negative Room Neutral 0.135” Lower Limit -0.100 Upper Limit -0.050Established by Yes WC OperatorPassword No Changepressure limits Save & Exit Cancelof room
    7. 7. Room Mode ScreenRoom Mode: Occupied ROOM MODE No Isolation Please SET the Room ModeIf “No Isolation” 0.135” by selecting eitheris selected, all WC Occupied or No Isolation Occupied No Isolationalarms are Save & Exit Canceldisabled
    8. 8. Alarm Setup ScreenMute Time Out: Maximum time alarm can be ALARM SETUP Latch Alarm Yes No silenced while Audible Alarm 0.135” Door Alarm Input Yes Yes No No still in alarm WC Mute Time Out 5 Secs state Alarm Delay 5 Secs Volume 1 Up Down “Latch Alarm” Save & Exit Cancel must be on
    9. 9. Monitoring ScreenClick Door toOpen and Close Door Open Negative Room - 0.0700”WC 0.135” -0.1000 WC -0.0500 Silence Menu Reset
    10. 10. Calibration ScreenPush-buttonZero and Span CALIBRATION Negative Room 0.135” -0.0700 “WC Apply Zero ZERO WC Pressure Apply Full Scale Pressure SPAN Restore Exit Factory Setting
    11. 11. QuestionsTo order a free catalog or for more information contact; Dwyer Instruments, Inc., P.O. Box 373, Michigan City, IN., 46361 Telephone: (800) 872-9141 or (219) 879-8000 Fax: (219) 872-9057 Internet address: www.dwyer-inst.com E-mail: info@dwyer-inst.com

    ×